Text
.
O targ
'k UNITED STATES g
NUCLEAR REGULATORY COMMISSION
~
b h
- j WASHINGTON, D. C. 20555
\\....*/
CAROLINA POWER & LIGHT COMPANY DOCKET NO. 50-325 BRUNSWICK STEAM ELECTRIC PLANT, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 84 License No. DPR-71 1.
The Nuclear Regulatory Comission (the Commission) has found that:
A.
The application for amendment by Carolina Power & Light Company (the licensee) dated February 13, 1985, as supplemented April 4,1985 complies with the standards and re Act of 1954, as amended (the Act) quirements of the Atomic Energy and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's rc7ulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. OPR-71 is hereby amended to read as follows:
8507030303 850621 DR ADOCK 000 3y5 l
. i 2.
Technical Specifications The Technical Specifications contained in Appendices A and B, as revised through Amendment Nc. 84, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEAR REGULATORY COMMISSION Domenic B. Vassallo, Chief Operating Reactors Branch #2 Division of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance:
June 21, 1985
1 A~tTACHMENT TO LICENSE AMENDMENT NO. 84 FACILITY OPERATING LICENSE NO. DPR-71 DOCKET NO. 50-325 Revise the Appendix A Technical Specifications by removing page 3/4 5-6 l
and inserting revised page 3/4 5-6.
The changed area is indicated by a vertical line.
r S
1
.s (BSEP-1-45)
I l-4 EMERGENCY CORE COOLING SYSTEMS
}
SURVEILLANCE REQUIREMENTS (Continued) i 2.
Verifying that each valve (manual, power-operated, or automatic) in the flow path that is not locked, sealed, or otherwise secured in position, is in its correct position.
I c.
At least once per 92 days by:
l
- 1.
Verifying that each CSS pump can be starred from the control i
I room and develops a flow of at least 4625 gym on recirculation flow against a system head corresponding to a reactor vessel pressure of > 113 psig.
2.
Performing a CHANNEL CALIBRATION of the core spray header aP instrumentation (E21-dPIS-N004A,B) and verifying the set point to be 5, +J.5, psid greater than the normal indicated AP.
d.
At least once per 18 months by performing a system functional test which includes simulated automatic actuation of the system throughout its emergency operating sequence and verifying that each automatic valve in the flow path actuates to its correct position. Actual injection of coolant into the reactor vessel is excluded from this,
test.
I 4
- The surveillance test required by this licence in Appendix A, paragraph 4.5.3.1.C.1, regarding the flow test of the core spray system may be postponed during the current refueling outage (Reload 4) until within 48 l
hours after restoration of the suppression chamber to operable status but f.
in any case no later than October 30, 1985.
l F
L BRUNSWICK - UNIT 1 3/45-6 Amendment No. 84