Text

O.,4 7.

i ENCLOSURE 1 NOTICE OF VIOLATION l

Virginia Electric and' Power Company Docket.No. 50-281 Surry Unit 2 License No. DPR-37 The followingaviolation was identified during an inspection conducted on

.-December 1,-- 1984 - January 4, 1985..The -Severity Level was assigned in zaccordance.with the-NRC Enforcement' Policy (10 CFR Part 2, Appendix-C).

Technical Specification.(TS) 3.6.B.1 requires -that prior to exceeding 350 F or 450 psig in the : Reactor Coolant System (RCS), one of the three auxiliary

'feedwater--(AFW) pumps for the opposite unit shall be available.. In addi -

tion, TS 3.6.D requires that the system piping, valves, and control board indication. required for the operation of the opposite unit AFW pump be available.

Contrary to the above, Unit' 2 was operated at full power from September 28, 1984, to. 0ctober 30, 1984, with the Unit 1 AFW pumps not available to Unit 2 because the motor operated cross-tie valve MOV-FW-260A.was closed and not available -(without -indication) due to the tagout 'and opening of its-electrical breaker -1H1-211.

This'isaSeverityLevelIVviolation(SupplementI)andappliestoUnit2.

Pursuant. to 10 CFR 2.201, you are required to submit to this office within -30

' days.of ~ the date of this Notice, a written statement or explanation in. reply,-

y' including:

(1) admission or denial of the alleged violations; (2) the reasons for the violations,1f admitted; (3) the corrective steps which have been taken and the results achieved; -(4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved.'-

Security.or:-safeguards information should be submitted as an enclosure to

-facilitate withholding it from public disclosure as required by 10'CFR 2.790(d) or 10'CFR 73.21.

- Date:

l 8505230611 850401 PDR ADOCK 05000280 G

PDR

.6

... ~

L.e--m.