.9 Public Service Electric and Gas Cornpany
' Thomes J. Martin 80 Park Plaza, Newark, NJ 07101 201430-8316 Mailing Address: P.O. Box 570, Newark, NJ 07101
. Vice President Engineering and Construction April 30, 1985
(:
Dr. Thomas E. Murley, Administrator U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406
Dear Dr. Murley:
SIGNIFICANT CONSTRUCTION DEFICIENCY MISAPPLIED SEQUENCER RELAYS HOPE CREEK GENERATING STATION On January 18, 1985, a verbal report-was made to Region I, Office of Inspection and Enforcement representative, Mr. J.
Strosnider, advising of a potentially significant construc-tion deficiency concerning series 07 sequencer relays that may have been misapplied for their intended function.
On February 19, 1985, an interim report was submitted to your office.
The following final report is provided in accordance with 10CFR50.55 (e).
Description of the Deficiency Our Architect / Engineer and Constructor, Bechtel, has ade. sed us that twenty-six (26) of the emergency load sequencer output relays supplied by Consolidated Controls Corporation to input the Bailey controls system and associated switchgear have been misapplied.
The manufacturer, Airpax-North American Philips, has indicated that the contact gap in the fully open position may be insufficient.to quench the arc drawn when breaking 125VDC.
Consequently, the contacts may weld together resulting in a subsequent misoperation of the circuit.
A total of 144 of the series 07 relays are ir. stalled in panels lA428, 1B428, 1C428 and 1D428.
.Our investigation identified two (2) scenarios involving twenty-six (26) relays where the noted condition presents a problem.
8505230095 850430 gDR ADOCK 05000354 PDR I O El 4
t.
k
.5 Dr. T. E. Murley 2
4/30/85 1.
Process Start Inhibit Signal (PSIS) outputs to.the same switchgear, energize two relays in parallel, one of which has a contact in the start circuit.
The PSIS is present continuously while the sequencer is.in operation and can only be reset by the operator at the completion of the sequence.
When the sequencer is reset, the back electro-magnetic force (EMF) generated by the collapsing field of the relay coils will cause an arc to be drawn across the
_PSIS relay contact and the magnitude of this could poten-tially cause the contact to weld shut.
Eight (8) relays are affected.
2.-
Outputs to the Bailey logic modules consist of the Bus Power Failure Fanout (LOP Fanout), LOCA Fanout, LOCA and LOP Fanoutnand Sequencer Fanout (sequencing start signals and PSIS).
The Bailey input circuit has a steady state current value of 0.0045 amperes per input circuit.
The worst case was identified as Bus Power Failure Fanout inputs to 56 circuits resulting in 0.25 amperes steady state current.
Consequently, the contact of the Bus Power Failure Fanout relays could potentially weld together resulting in a subsequent misoperation of this circuit.
Eighteen (18) relays were identified as Bus Power Failure
-Fanout (LOP Fanout), LOCA Fanout, LOCA and LOP Fanout to Bailey cabinets and switchgears for valves closing and breakers tripping in the events of LOCA and LOP.
In the case'of Bus Power Failure Fanout, the relays provide LOP signals to AC lE MOV OVERLOAD / POWER FAILURE monitors.
In summary, the design of the AIRPAX sequencer relays has
. limited 125VDC application, indicating that the relays should
.not be used in high loading applications.
. Safety Analysis Bechtel Project Engineering has performed an analysis of safety implications based upon the two scenarios described above.
They are as follows:
1.
In'the first scenario with PSIS contacts welded shut, the PSIS would-not clear to Diesel Generator Room Recirculation Fans. -This would cause the sequence start signals to remain sealed-in, therefore the Diesel Generator Recirculation Fans could no longer sequence start.
Under a Design Basis Event (DBE), both room recirculation fans would start simultaneously the instant that diesel generator comes on line.
This could cause improper loading of the diesel, k
FT
!i Dr.
T.
E. Murley 3
4/30/85 L2.
In the second situation, with LOCA and LOP Fanout relay contacts welded shut, many components that trip on LOCA and LOP events would not be operating.
Bus Power Failure signals to all the AC lE MOV OVLD/PF monitors would be
~
activated.
Although this condition would not affect safe shutdown, it would prohibit the plant from operating at power.
As described in paragraph 1 above, the.noted deficiency could cause improper loading and subsequent tripping of the Emergency Diesel Generator. -Had the problem gone andetected and uncor-rected, safe shutdown of the plant could have been adversely affected.
We therefore consider the subject deficiency to be-reportable in accordance with 10CFR50.55 (e).
Corrective Action The twenty-six (26) affected relays will be replaced by Struthers-Dunn relays.which are qualified for high loading application at 125VDC. ~The rework will be tracked and con-trolled by Nonconformance Report No. 6415.
Very truly yours, M