ENCLOSURE 2 NOTICE OF DEVIATION

,

Virginia Electric and Power Company Docket Nos. 50-338 and 50-339

~

North Anna Units 1 and 2 License Nos. NPF-4 and NPF-7 I

The following deviation was identified during an inspection conducted on April 1 - May 5,1985.

Section 15.2.11 of the North Anna Updated Final Safety Analysis Report (UFSAR) states, " excessive loading by the operator or by system demand would be limited by the turbine load limiter".

Correspondence with Westinghouse indicated that the turbine governor valve position limiter was the load limiter discussed in the UFSAR.

Contrary to the above, excessive loading by the operator or system demand was not limited by the turbine load limiter, in that plant operating pro-cedures 1(2)-0P-2.1 set the governor valve position limiter to the maximum setting allowing reactor power to increase above the maximum designed power.

Please provide, in writing within 30 days of the date of this Notice, a descrip-tion of corrective actions regarding this deviation, actions taken to avoid further deviations, and the dates when these actions were or will be completed.

Security or safeguards information should be submitted as an enclosure to facilitate withholding it from public disclosure as required by 10 CFR 2.790(d)

or 10 CFR 73.21.