3-I iILLINOIS-POWER' COMPANY CPS No.

1907.20

'CLINTON POWER ~ STATION CLASS CODE: FNQA r

. TITLE:.

RADI0 ACTIVE SOURCE CONTROL, LEAK TESTING, AND-ACCOUNTABILITY Scope of Revision:

i l

{.

i 1 CONTROLLED COPY

^

~ ~ -

i

).

l.

I 1

I l-f LIST OF E m CTIVE TCFs 1)

TCF NUMBER EFF.'DATE EXP. DATE YCTERGER - EFF. DATE EXP. DATE

{

A'

!L 4

h4.

PREPARER Mark D, odds, GROUP SUPERVISOR DEPARTMENT HEAD Aptrrm_

ASST. PWR. PLT. MNGR.

//

/L T M eld V

INTERFACE p" -

. CONCURRENCE p;pg# -

n.

n T

/

.CCCD-, % b.n

> 8N%/wJNfA CONCURRENCE ClcTCN AAa J e19 /sc FRG 4% ///45 v,w/sr POWER PLANT [7//A, NAGER ~

MA W////h/u DATE

/

I

( ).

'~

ALARA COM11mF(7 9(LW

~' ~ f

~

l i

~

]

DLD15 Page No.

1 of 14 I

Rev. No.

O h

b ! N002 47 C

PDR

' ~ ~ ~ - - ~

i l

~. #

CPS No. 1907.20 1.0 PURPOSE

~

To establish the necessary controls for the possession of radioactive sources.

2.0.

DISCUSSION / DEFINITIONS' 2.l~

Discussion Controls are required for radioactive sources due to their radioactive nature and the. requirements of regulatory agencies.

These controls include accountability, inventory, leak testing, and activity t;.

calculations.

2.2 Definitions 2.2.1-Byproduct Material - Any radioactive 3j material (excluding Special Nuclear

.i-Material (SNM)) yielded in or made l.

radioactive by exposure to the radiation t L incident to the process of producing or j

-[

utilizing SNM.

!-1 2.2.2 Exempt Quantity - That quantity of material not requiring a specific or c(.-

use, transfer, or ownership.

general license for receipt, possession,.

2.2.3 Exempt Quantity of' Byproduct Material -

-l That amount of Byproduct Material which is less than the values stated in 10CFR30.70 or 10CFR30.71.

x"

2. 2.- 4

.Non-exempt material That quantity of.

material that requires a. specific, license for receipt, possession, use, transfer, or

' ownership.

This may also include material received under a General License, t

2.2.5 Sealed Source - radioactive material (liquid or solid) that is permanently g

bonded, fixed or contained, in a manner designed to prevent release and dispersal of the radioactive material under the most severe conditions,'which are likely to be encountered in normal use and handling.

4

\\

.j.

-DLD15 Page No.

2 of 14 x

Rev. No.

O s

+7

.1 - <. + n.3.....,,.

y,.,

CPS'No. 1907.20

,q:

2. :2. 6 Source Material - (1) Uranium or thorium, l(~ L or any combination thereof, in any

+

15 :

L physical-or chemical form: (2) ores which contain by weight one-twentieth.of one percent (0.05%).or more of (a) uranium, j,

(b) thorium or (c) any combination f

thereof: source material does not include q

_SNM.

s 1-j 2.2.7 Special Nuclear Material (SNM) - (1)

Plutonium, uranium-233, uranium enriched in the isotope 233 or in,the isotope 235, and any other material which the Commission, pursuant to the provisions of I'w Section 51 of the Act, determines to be

"~

special nuclear materials or (2) any material artificially enriched by any of i.

the foregoing but does not include source material.

-2.2.8 Startup Source - Byproduct. material that is encased in a capsule designed to prevent leakage or escape.

Its purpose is to ensure on scale Source Range Monitor indication prior to rod withdrawal.-

3.0 RESPONSIBILITY 3.1 The Supervisor - Radiation Protection (S-RP) is

-responsible.for the implementation of this procedure.

The S-RP is also responsible for the following pertaining to. quantities of SNM that Radiation Protection (RP)-has accepted subcustody: (1) inventory and accountability: (2) leak testing: (3)-storage (4) maintaining required records: (5) authorizing 1

transfers and (6) informing the SNM Custodian of any change _in status / location.

s

'3. 2 _

The Supervisor - Radiological Oaerations (S-RO) is responsible for the review of this procedure.

3 3.3 The Supervisor - Technical is responsible for the control and accountability of SNM in accordance with CPS No.-1898.00, SPECIAL NUCLEAR MATERIAL PROGRAM.

4.0

~ PRECAUTIONS A

.>L M

l'

~

-DLD15 Page No.

3 of 14 l

Rev. No.

0 J

m. - -.,.,.,

y

CPS-No. 1907.20

5.0 PREREQUISITES

C.

~

When utilizing sources or moving radioactive material which change an area radiological condition, the area shall be posted in accordance.with CPS No. 1905.20, RADIOLOGICAL AREA POSTING and access controlled in accordance with CPS No.

-1906.10, ACCESS CONTROL - RADIATION PROTECTION.

6.0 LIMITATIONS AND ACTIONS

~ 6.1 Only those. personnel successfully completing a source handling qualification program may handle licensed

. radioactive material (RAM) without direct supervision.

r,.

~^

-6.2

'All sealed sources that are.not installed in an instrument cn other piece of equipment shall be stored in a controlled storage area.

Locked cabinets or drawers in the RadChem Laboratory, RP Office or counting rooms will be used for storing small

. calibration and check sources.

Sealed liquid sources shall.be stored in the RadChem~1aboratory, the Whole I:

' Body Counting Room, or the Radiation Protection Instrument Calibration Facility (RPICF).

The neutron irradiator and SNM calibration check sources shall be stored in the RPICF.

The remainder of the sealed g

sources shall be stored in the locked RPICF.

s 6.3 Byproduct material storage areas and storage areas.for SNM in which RP has subcustody shall be adequately.

secured, shielded and labeled.

The RPICF shall be-under strict lock and key security with access controlled by RP personnel.

Keys shall be controlled in accordance with CPS No. 1905.21, RADIOLOGICAL KEY CONTROL.

7.0 MATERIALS AND/OR TEST EQUIPMENT None DLD15.

Page No.

4 of 14 Rev. No.

O

..____,,.,.y._,

.p..-..._.__..._

c.

.l 1 CPS No. 1907.20 8.0 PROCEDURE

~

8.1 Accountability 8.1.l~

Upon receipt or production of a radioactive source, initiate accountability as;follows:

NOTE In-house production of a radioactive source meeting the requirements of Section 8.3 for leak testing shall be entered into surveillance tracking in accordance with CPS No. 1011.02, SURVEILLANCE TESTING.

..]

1-8.1.1.1 Non-exempt Byproduct Material - Initiate CPS No. 1907.20F001, RADIOACTIVE SOURCE RECORD and retain the RADIOACTIVE SOURCE RECORD in the Non-exempt Source Binder.

Enter the material into the Source Tracking Book.

8.1.1.2 Exempt Byproduct Material - Enter the l~

material into the Source Tracking Book.

I 8.1.2 Place the material in an approval storage f(

location and update the source inventory record at the storage location.

8.1.2.1 Sources temporarily removed from their

?

storage location (less than one day) need only an entry made on the source inventory record to denote its location.

8.1.2.2 Sources permanently removed require.an entry in~the Source Tracking Book and source inventory record to denote the new location. -Update to source inventory record at the new location.-

p 8.1.3 Receipt of a liquid radioactive source shall also require the initiation of CPS No. 1930.01F002, CONTROLLED SUBSTANCE ACCOUNTABILITY RECORD.

8.1.4 Disposal of a radioactive source shall be documented.

DLD15 Page No.

5 of 14 Rev. No.

O

,! --..-. ~,,._...._ _..._.-.

i J

'A CPS No. 1907.20

~

8.1.4.1 Non-exempt material requires entries in C

the RADIOACTIVE SOURCE RECORD, Source Tracking Book, and source inventory record.

8.1.4.2 Exempt material requires an entry in the.

Source ~ Tracking Book and source inventory record.

8.2 Inventory-8.2.1 A physical inventory of each radioactive source shall be~ conducted every ~six months.-

8.2.1.1 Documentation of the inventory-for non-exempt source is accomplished by the following entry on the RADIOACTIVE SOURCE RECORD: (1) Date the inventory was conducted (2) " CONDUCTED SOURCE INVENTORY": and.(3) Signature of the

[

individual performing the inventory.

1 j

8.2.1.2

. Documentation of the inventory for exempt t

. sources is accomplished by the entries of-i 8.2.1.1 in the Source Tracking Book.

following the last entry of the Book.

8.2.1.3 The inventory of liquid sources shall ensure the amount depleted (if' applicable) is accounted for on CPS No. 1930.01F002.

l

.i:

8.2.2 Concurrent with the inventory of.

non-exempt material, any device shall have its on-off mechanism and indicator (if agplicable)-tested for proper operation.

Tae results of these test shall be d:

recorded on the RADIOACTIVE SOURCE RECORD in the storage section with the following.

I words (or equivalent):

Date, conducted

F mechanism test Sat. (or Unsat.), and je signature of the individual conducting the test.

NOTE If the same individual performed the

't inventory and conducted the mechanism j'

test, one signature ~following both

[

required entries will satisfy the signature requirement.

1(L DLD15 Page No.

6 of 14 Rev. No.

0

+ee-*..i ag-m v

  • mmuM'fse--

wws-s1 w'-es--wF

'r-'-f "F

&P-"r*

Ter-'-*--+f--

  • w-

--wP'

2. L..,

.... _... ~. _.

3

3. -

~:

JI T l CPS.No. 1907.20 l

8.2.3 If the inventory results indicate the loss or theft of licensed radioactive material, or uaon discovery of the failure or damage of the on-off mechanism or indicator, the

. action of CPS No. 1909.20, RADIOLOGICAL REPORTS, shall be initiated.

Additionally, and for the loss of any radioactive source (exempt quantity sources included) a Radiological Infraction / Occurrence Report shall be initiated in accordance with CPS No.

1909.21, RADIOLOGICAL INFRACTION /0CCURRENCE REPORTS.

1"9 8.3 Leak Testing A

8.3.1

'Each sealed source, containing radioactive material in excess of 100 microcuries of beta and/or gamma or 10 mlErocuries of

~j alpha, (other than Hydrogen 3 or Krypton) with a half-life greater than thirty days, 1

and in any form other-than~ gas shall be tested for leakage and/or contamination.

Ij.

8.3.2 Each category of= sealed sources shall be leak tested at the frequency described r,

below:

a)

Sources in use.(excluding startup sources and fission detectors 3reviously subject to core flux).

3ach sealed source containing radioactive material that meets the requirements of 8.2.1 shall be tested for leakage and/or contamination at i

intervals not to exceed six (6) months except that each source deiignated for emitting alpha shall be tested at intervals Hot to exceed three (3)'

months.

~

DLD15 Page No.

7 of 14 7

i Rev. No.

O I

..x__._

m_. -.---- -....---.

. I PJ CPS No. 1907.20 T*

' r'.

b)

Stored sources not in use - Each fission detector and. sealed source

(--

that meet the requirements of 8.2.1, except alpha emitting sources, need not be leak tested if stored in their original shipping container.

Each fission detector and sealed source shall be leak tested prior to use.or transfer to another licensee unless tested within the time limits given above.

. Sealed sources, that meet the requirements of 8.2.1, received i

without certificate indicating the last leak test data shall be tested e

't>

prior-to being placed in service.

.l' c)

Startup sources and fission detectors Each sealed startup. source and. fission detector shall be tested within 31 days prior to being subjected to core flux or installed in the-core and following repair or maintenance to the source.

d)

Sealed sources suspected to be damaged Each sealed source for which there is.

I.

reason to believe it has been damaged shall be leak tested immediately.

8.3.3 Leak testing of sealed sources, startup sources or fission detectors shall be accomplished in accordance with CPS No.

9974.01, SEALED SOURCE CONTAMINATION LEAK TEST.

. -['I 8.3.4 Document.the results on the applicable

'l '

RADIOACTIVE SOURCE RECORD and retain CPS No. 9974.01D001, SEALED SOURCE CONTAMINATION LEAK TEST DATA SHEET,'in accordance with CPS No. 7017.01, RADIATION PROTECTION RECORDS.

8.3.5 If the results indicate the presence of

p 0.005 microcuries of removable j?

contamination, initiate the actions T

required in accordance with CPS No.

1909.20.

.U i

IQ j.

~

DLD15 Page No.

8 of 14 Rev. No.

O e

Eg

,/;

',j,'

CPS No. 1907.20

.h '

p I;

8.4

-Activity Calculation

!.['

~

8.4.1-Exempt and non-exempt radioactive source, excluding fission detectors, startup sources and sources used to response check instruments or detection systems,- shall be l'

decay corrected once every six' months using the below formula:

.693t A

=A e

where t

g t

t = Activity renaining after time t A

=

A Original activity

['r e

= Base of the natural logarithm

-[

t

= Elapsed time

,i t% = Half-life of the isotope 8.4.1.1 Sources with a half-life greater than.3.5 years, but less than seven years, shall have been decay corrected within three months prior to use.

8.4.1.2 Prior to using a source with a half-life i

of 3.5 years or_less,_a decay correction shall be performed if five percent. of the radioactive half-life has passed since the

(

last decay calculation.

8.4.1.3 Radioactive sources required to be decay corrected shall have a statement in the Remarks section of the RADI0 ACTIVE SOURCE RECORD stating decay calculations are require and the periodicity in which'they are performed.

8.4.2 Enter the results in the Activity.section of the RADIOACTIVE SOURCE RECORD.

Compare the above results with the limits of Section 8.2.1 to determine if the source requires periodic leak testing.

If leak testing is no longer required, a SURVTRAC System Data Input Sheet should be submitted in accordance with CPS No.

1011.02 to remove the source from the tracking system, and a statement in the remarks section stating decay calculations are no longer required.

i t.t-I I

f DLD15' Page No.

9 of 14 o

j~

Rev. No.

O C

... u a a..

.._..... w -

i CPS No. 1907.20

,1:

8.5 Subcustody Control of SNM by RP Personnel 8.5.1 Subcustody Receipt Requirements Custody of'SNM from the'S.NM._ Custodian to.

-the RP Department.shall be transferred a written document stating that the RP Department assumes subcustody.

The t.

document shall contain the signatures of both-the SNM Custodian and S-RP prior to transfer of the material.

]

8.5.2' Accountability

{d 8.5.2.1 Accountability shall be maintained by an 3

entry into the Source Tracking Book and the source inventory record.

8.5.2.2 Source movement shall be in accordance l

with 8.1.2.1 and 8.1.2.2 except that permanent changes shall be made only after

!J prior written approval from the S-RP and SNM Custodian.

if 8.5.3 Leak Testing i:

Leak testing shall be performed in.

i accordance with-Section 8.3.3-through 8.3.5.

Leak testing shall be performed every six_mo.nt_hs for plutonium sources.

I p

8.5.4 Inventory

-8.5.4.1 Inventory shall be performed in accordance-with Section 8.2.

The Power Plant Manager I

(PPM) may request a special inventory be conducted at any time.

8.5.4.2 The results of the inventory, in addition to the required documentation, shall be reported to the_ PPM, the Supervisor -

Nuclear Fuel Cycle, and the SNM Custodian.

8.5.5 Activity Calculation i

Activity Calculations shall be in

{

accordance with Section 8.4.

~[

8.6 Labeling 8.6.1 Ensure a label is attached to the material or container with the following information:

-DLD15 Page No.

10 of 14 Rev. No.

O

n.c.._..

.._.a.

't,' ' v, CPS No.-1907.20 i

8.6.1.1 The words;" Caution (or' Danger) l~(

Radioactive Material" (magenta on yellow).

8.6.1.2 The symbol and mass number of the isotope (s) present or description of the isotope origin and the original activity.

8.6.2

For Am241 or Pu, a label. stating the following or equivalent shall.be attached to the source or container:

"The receipt, possession, use and transfer of this source, Model

,. Serial-No.

are subject to a general license and the regulations of.the a

U.S. Nuclear Regulatory. Commission or of a state with'which the commission:has entered into an agreement for the exercise of regulatory authority.

Do not remove this label.

1 Caution - Radioactive Material - This

]~

source contains (Americium 241)

(Plutonium).

Do no't touch the radioactive f

portion of this source.

Name of Manufacturer or Importer 8.6.3 For Ra226, a label stating the following or equivalent shall be attached te the source or container:

"The receipt, possession, use and transfer-of this source, Model Serial No.-

, are subject i

?

to a general license and the regulations of an Agreement State or Licensing State.

Da Not remove this label.

Caution - Es.dioactive Material - This f

source contains Radium 226.

Do Not touch

~

the radioactive portion of this source.

')

Name of Manufacturer or Importer 8.6.4 For sources received without an identification number, or all liquid standards received.the following identification system shall be utilized:

w

'DLD15 Page No.

11 of 14 Rev. No.

0

'?

CPS No. 1907.20 i

8.6.4.1 XX-YY where XX is the last two numerals of C.

the year (e.g. 84 for 1984) and YY is a sequential number beginning at 01.

8.6.4.2 Each source made from a liquid standard shall be labeled as follows XX-YY-ZZ where i

XX-YY are the original designators

+

1 assigned and ZZ is a sequential number beginning at 01 (e.g., the fifth source produced from liquid standard 84-02 would

?

be labeled 84-02-05.

8.6.4.3 A binder shall be established to track the utilization of the identification system j

designators.

An index shall be j

established to assign the XX-YY designator and each liquid standard shall have a j

section to track the XX-YY-ZZ designator.

8.7 Documentation 8.7.1 Non-Exempt Source Binder 8.7.1.1 A Non-Exempt Source Binder shall be established to store the RADIOACTIVE j

SOURCE RECORDS.

8.7.1.2 In addition to storing the RADIOACTIVE SOURCE RECORDS, a section shall be established in the Binder to totalize I

licensable quantities of radioactive material by isotope.

8.7.2 Source Tracking Book j

8.7.2.1 A logbook shall be established to track radioactive source movements, t'

8.7.2.2 The source Tracking Book shall be divided into three cactions:

(1) Non-exempt i

Byproduct; (3) Exempt Byproduct; and (3)

SNM.

8.7.2.3 Only one source shall be entered per page.

Each page should contain the following

]

headers:

(1) Source ID; (2) Date; and (3)

Storage Location.

i 8.7.2.4 The Source Tracking Book shall be maintained in the RP Office.

i L

DLD15 Page No.

12 of 14 I

Rev. No.

0 k

c

?

CPS No. 1907.20-4, 8.'7.3 Source Inventory Record-8.7.3.1 A source inventory record.shall be maintained at each storage location for.

sources not. installed in an instrument or other piece of equipment.-

.j; 8.7.3.2 The source inventory record shall be a logbook for that-storage location.

The' source inventory record shall contain the source stored at that location and have 11 the following headers:

(1) Source ID; (2)

Date; (3) Date Moved; and (4) Moved to.

3 i

3 8.7.4 All documentation shall be retained in L

accordance with CPS No. 7017.01, RADIATION PROTECTION RECORDS.

i 9.0 ACCEPTANCE ~ CRITERIA L'

Leak testing of applicable sealed sources reveals removable contamination is less than 0.005_microcur,ie_s_ or the appropriate actions have been taken.

ii' 10.0 FINAL CONDITIONS

!I;.

All radioactive sources are accounted for and are in their 3-E designated storage location or other storage. location as fi designated by the appropriate source inventory record, or a j

report has been initiated in accordance-with CPS No~ 1909.20 and CPS No. 1909.21 for the loss or theft of radioactive

.j material.-

j-i i

11.0 REFERENCES

11.1 10 CFR 20, 30, 31, 70 f

11.2' CPS No. 1011.02,. SURVEILLANCE TESTING 1-1 11.3 CPS No. 1898.00, SPECIAL NUCLEAR MATERIAL PROGRAM 1 -

'11.4 CPS No. 1909.20,. RADIOLOGICAL REPORTS 11.5 CPS No. 1909.21, RADIOLOGICAL INFRACTION /0CCURRENCE

-l' REPORTS l

11.6 CPS No'. 7017. 01, RADIATION PROTECTION RECORDS

-i i

C l

j' DLD15 Page No.

13 of 14 Rev. No.

0 4

~

CPS No. 1907.20 l

11.7 CPS No. 9974.01, SEALED SOURCE CONTAMINATION LEAK TEST 11.8 CPS No. 9974.01D001, SEALED SOURCE CONTAMINATION LEAK TEST DATA SHEET 12.0 APPENDICES None 13.0 DOCUMENTS l

CPS No. 1907.20F001, RADIOACTIVE SOURCE RECORD I

i 1

1

)

s I

,b DLD15 Page No.

14 of 14 Rev. No.

O k

j ef' LASS CODE: FNQN i

ji C

~

CPS No. 1907.20F001 j

(Rev. 0) 3 DOCUMENT TITLE PAGE i

Document

Title:

RADIOACTIVE SOURCE RECORD 1

Prepared By:

Mark Dodds APPROVED BY:

9 k)

  1. / F/

Signat'ure/Date j

QE: b bh 8/9/85~

a

~-

1 PRc:

h f,fA Q

</3 </r

/

/

(

CONTROJ_ED COPY

}

i

.....=

~

. t.

-i -CLASS CODE: FNQN.

. CPS No. 1907.20F001 (Rev. 0)

RADIOACTIVE SOURCE RECORD f

Radionuclide Physical Form

~

i Identification No.

Date Received 1

Original Activity As of Certificate No.

Vendor Model No.

STORAGE LEAK TEST ACTIVITY Date Locations Date Results Init.

Date Activity Init.

l.

]

ll-t-

i I

REMARKS:

9 L

t Reviewed by:

DLD15 Page 1

of 1

-.__