ML20127A673

From kanterella
Jump to navigation Jump to search

Discusses Licensee Objections to Manpower Requirements for Operating Reactors Re Number of Individuals on Fire Brigade in Response to NRC 780526 & 0605 Requests
ML20127A673
Person / Time
Site: Monticello, Prairie Island  
Issue date: 06/22/1978
From: Mayer L
NORTHERN STATES POWER CO.
To:
Office of Nuclear Reactor Regulation
References
TAC-6587, NUDOCS 8712170251
Download: ML20127A673 (2)


Text

..

NSEW3%0EM NORTHERN 5 TATE 5 POWER COMPANY

- ~ ~... ~.. _ ~ ~.. _.. _

p, 1 J

]

June 22, 1978 Director Office of Nucicar Reactor Regulation U S Nucicar Regulatory Conraission Washington, DC 20555 t.

MONTICELLO NUCLEAR GENERATING PIANT Docket No. 50-263 License No. DPR-22 PRAIRIE IS1AND NUCLEAR GENERATING PIANT Docket No. 50-282 License No. DPR-42 50-306 DPR-60 Nuclear Plant Fire Brigade Requirements In letters dated May 26, 1978 and June 5, 1978 from Mr Victor Stello, Director, Division of Operating Reactors, Northern States Power Company was requested to re-view a document entitled, " Manpower Requirements for Operating Reactors" and to inform the Ca::rnission Staff within twenty days if we continue to object to their position on minimum fire brigade size.

" Manpower Requirements for Operating Reactors" tequires a fire brigade of at least five members and permits up to three members of the security organization to serve on the fire brigade.

In letters dated December 16, 1978 and December 22, 1978, Northern States Power Cocipany took objection to the requirement for a continuous five-man fire brigade.

In these letters, we provided a detailed analysis of the requirements placed on our nucicar plant fire brigades and supplied justification for a three-man brigade.

We continue to believe that a three-man fire brigade is sufficient. Increasing the size of the fire brigade to five individuals on a continuous basis through the use of two more security personnel would greatly increase the training requirements placed on the guard force. Since our guards are provided by a contractor, this training would be impractical to conduct.

It may be acceptable, however, to augment fully trained members of the fire brigade with security personnel to assist in support activities such as cocznunications, obtaining equipment, filling air cylinders, and other tasks not requiring the ccanplete training program the Corrtission Staff has outlined for regular fire brigade members.

Our philosophy for protection against fires is that of defensc. in depth; that is, fire prevention, prompt detection and extinguishment, and provisions for mini-mizing the effects of fires. All of these principles have been applied at our l

facilities. Fire brigades deal with the extinguishment of fires that are not i

automatically coped with.

In this regard detection systems are installed and frequent plant inspections are made so that any fire would be detected at its

~

/

\\

V fm' L 67/2/ 70 x/ y' /

/

w

\\\\

i

a b ORTHERN OTATED POWE COMPANY Office of Nucicar Reactor Regulation Page 2 June 22, 1978 inception. In certain plant areas automatic systems are actuated to extinguish any fires that are detected. In other areas, initial reliance may be placed on the use of manually actuated systems. In addition, it. has been recognized that a back-up manually operated water fire extinguishing sys'em could be required. The number of persons required to operate this manual water fire extinguishing system establishes the minimum size of the fire brigade. Should a fire occur, the loca-tion would be identified by an operator or by the fire detection system. Use of water hoses would require at least two persons to don breathing apparatus, if needed, and enter the area.

Since the fire hoses are permanently installed, do not utilize solid streams, and are of a size (1 inch) that one person could handle, the prime reason for two persons to enter the area is for personnel safety.

In the case of trained persons entering an environment they are familiar with and know beforehand the potential for danger, there is no need to have a separate

" fire supervisor" at the scene to_ observe and direct their efforts. This is not to say that one individual should not be in charge of the fire fighting efforts, rather it is to emphasize that when two trained individuals enter an area to fight a fire their initial efforts should be set by their understanding of the potential nature of the fire and their training to respond. After the initial two-man response it may be desirable to augment the efforts at the scene by another in-dividual who may be the supervisor or person who relays information from the scene to the supervisor. Since all equipment utilized in the initial phases of fire fighting is pre-installed and breathing apparatus tirements are to have at least two spare tanks availabic, we are of the op. -

a that additional dedicated fire fighting personnel are not required.

Our current Technical Specificationo require a fire brigade of at least three members to be on site at all times in addition to the minimum number of individuals required to safely shut down the reactors from outside the control room. When the probability of fire is significant, such 'as during normal working hours while operating and during refueling outages, the number of individuals able to respond to a fire exceeds the recommended five. We believe current requirements on fire brigade size are adequate and no change in the Technical Specification require-ments are necessary. We will be available to discuss this issue in detail during the site fire protection inspections planned for later this year.

oY'O.

L 0 Mayer, PE Manager of Nuclear Support Services LoM/DMM/ak-cc:

Dir IE-III G Charnoff

'l}