f',,.
Docket No. 50-219 December 7,1992 Distribution:
Docket file ACRS (10)
NRC & Local PDRs JFRogge, RI Mr. John J. Barton PD l-4 Plant Vice President and Director SVarga GPU Nuclear Corporation JCalvo Oyster Creek Nuclear Generating Station SNorris Post Office Box 388 ADromerick Forked River, New Jersey 08731 OGC HAshar
Dear Mr. Barton:
SUBJECT:
EVALUATION OF UPPER REACTOR BUILDING AND NON-SAFETY ARCHITECTURAL COMPONENTS SUBJECTED 10 TORNADO-WIND LOADING - ITEMS 1 AND 110F SEP TOPlc 111-2 (TAC NO. M79165)
The staff has completed the review of the upper portion of the Reactor Building subjected to tornado-wind generated loadings, and the consequences of tornado missile damage to certain non-safety architectural components.
Based on the prior reviews by the staff (1983 to 1988), the subsequent responses to the staff requests for additional information, and audit of some of the licensee calculations, the staff concludes that the upper steel-framed portion of the Reactor Building will be able to withstand the tornado-wind loading generated by a total wind-speed (i.e., rotational plus translational) of up to 306 km/h (190 mi/h), when the )lanned modifications to the steel framing are completed. This is accepta)1e to the staff.
With respect to tornado missile damage to non-safety architectural components (mechanical equipment access opening), the staff conclu_es that even in the unlikely failure of mechanical components near the access door, a system consisting of the isolation cc,ndenser (IC), torus, and a core spray pump, was available both for shutting down the plant and for maintaining it in a shutdown mode. is our Safety Evaluation regarding these items.
Based on the above, the staff considers these items resolved and SEP Topic 111-2 closed.
Sincerely, Original signed by Alexander W. Dromerick, Senior Project Manager Project Directorate I-4 Division of Reactor Projects - I/II Office of Nuclear Reactor Regulation
Enclosure:
090005 As stated cc w/ enclosure:
See next page Off!CE LA:PDI-4 PM;RDI-4_
biPDJ-4 SO AN8bcn JStob KAME DM 12/~7 /92
/N/ 7/92 l7,/
/92
/ /
/ / ['
0FFICIAL RECORD COPY
/
1 I
Document Name: G:\\DROMFRIC\\M79165.SE.
9212110155 921207 b '0 7
DR ADOCK 0500 9
y 7
r m
f.*
4 q
Mr. John J. Barton Oyster Creek Nuclear GPU Nuclear Corporation Generating Station cc:
Ernest L. Blake, Jr., Esquire Resident Inspector Shaw, Pittman, Potts & Trowbridge c/o U.S. Nuclear Regulatory Commission 2300 N Street, NW.
Post Office Box 445 Washington, DC 20037 Forked River, New Jersey 08731 Regional Administrator, Region I Kent Tosch, Chief U.S. Nuclear Regulatory Commission New Jersey Department of 4/5 Allendale Road Environmental Protection King of Prussia, Pennsylvania 19406 Bureau of Nuclear Engineering CN 415 BWR Licensing Manager Trenton, New Jersey 08625 GPU Nuclear Corporation 1 Upper Pond Road Parsippany, New Jersey 07054 Mayor
~,
Lacey Township 818 West Lacey Road Forked River, New Jersey 08731 Licensing Manager Oyster Creek Nuclear Generating Station Mall Stop:
Site Emergency Bldg.
Post Office Box 388 Forked River, New Jersey 08731 i
_ _,, -.