l Earthquake :
HC L PF CA L CAJ L.4 "T I o M Response Spectrum : Instructure Realistic Frequency : GlP - Flexible F
A c f D A~
Percent Damping : GIP - 5.00 l
Spectral Values :
Direction Acceleration (g's)
North - South 2.40 East - West 2.40 Vertical 0.57 Angle (N-S Direction makes with the X Axis) : 0.00 Combination Criteria : SRSS Welahts :
Number of Weights : 3 No Weight X
Y Z
1 2.73E+003 1.80E+001 1.80E+001 6.60E+001 2
9.00E+002 1.80E+001 1.80E+001 1.90E+001 3
5.99E+003 1.80E+001 1.80E+001
-1.19E+002 Forces :
Number of Extemal Forces : 0 Moments :
Number of External Moments : 0 Allowables :
Anchor:
j Number of Anchor types : 1 Tens Shear Tens Shear Ultimate Ultirnate Inter Inter Saft Saft Duct No.
Dia Manufact Product Tension Shear Coeff Coeff Fact Fact Fact 1
1-1/4 Other Cast in Place 41720.00 20860.00 1.00 0.30 1.00 1.0 1.00 (A-307)
Concrete :
Ultimate Stress : 4000.00 psi.
Reduction Factor : 0.85 Weld :
Allowable Stress : 30600 psi.
Surfaces :
Number of Surfaces : 1 Surface Orientation 9608260176 960819 PDR ADOCK 05000295 p
PDR Anchor 4.0 analysis AC-10A Page 1 of 5
r
~
l Direction Direction Direction Comp Comp Comp No Nx Ny Nz 1
0.00E+000 0.00E+000 1.00E+000 Anchor Pattern for Surface # 1 (g}
2:XDil
- na
- :gg
)DO i$ dim
- .n
)
- 1 Q
]1 lL A
r n
q
,,08 i; i J
]
M m
mi n%=x%;j X
Legend for Anchor Patterns Anchors:
Concrete Lines:
Q [fjj Concrete Points:
Weld Lines:
GADmetry :
Anchor :
Number of Anchors : 4 Anch X
Y Z
Surf No.
Id Coord Coord Coord Id 1
1 2.00E+000 2.00E+000 0.00E+000 1
2 1
3.40E+001 2.00E+000 0.00E+000 1
3 1
3.40E+001 3.40E+001 0.00E+000 1
4 1
2.00E+000 3.40E+001 0.00E+000 1
l Concrete Lines :
- of elements perline : 5 Number of Concrete Lines : 8 Anchor 4.0 analysis AC-10A Page 2 of 5
Start Start Start End End End Sf Line No X-Coord Y-Coord Z-Coord X-Coord Y-Coord Z-Coord Id Width 1
0.00E+000 3.50E+000 0.00E+000 7.00E+000 3.50E+000 0.00E+000 1
7.00E+000 2
7.00E+000 1.00E+000 0.00E+000 2.90E+001 1.00E+000 0.00E+000 1
2.00E+000 3
2.90E+001 3.50E+000 0.00E+000 3.60E+001 3.50E+000 0.00E+000 1
7.00E+000 4
0.00E+000 3.25E+001 0.00E+000 7.00E+000 3.25E+001 0.00E+000 1
7.00E+000 5
7.00E+000 3.50E+001 0.00E+000 2.90E+001 3.50E+001 0.00E+000 1
2.00E+000 6
2.90E+001 3.25'i+001 0.00E+000 3.60E+001 3.25E+001 0.00E+000 1
7.00E+000 7
1.00E+000 7.0CE+000 0 00E+000 1.00E+000 2.90E+001 0.00E+000 1
2.00E+000 8
3.50E+001 7.00E+000 0.00E+000 3.50E+001 2.90E+001 0.00E+000 1
2.00E+000 j
Concrete Points :
Number of Concrete Points : 0 Weld Lines :
- of elements per line : 5 Number of Weld Lines : 0 Determination of Reduction Factors :
Reduction Factor input for Anchor # 1 Adequately installed : Yes Embedment Length : 13.50, Min:=12.50 in.
Gap at Threaded Anchor : 0.00 in.
Edge Distance - Edge 1 : 6.60 in.
Crack Size : 0.000 in.
Essential Relays in Cabinet : No Base Strength and Load Path : Ok Embedment Steel and Pads Adequately installed : Yes Reduction Factor input for Anchor # 2 Adequately Installed : Yes Embedment Length : 13.50, Min:=12.50 in.
Gap at Threaded Anchor : 0.00 in.
Edge Distance - Edge 1 ; 6.60 in.
Crack Size : 0.000 in.
3 Essential Relays in Cabinet : No Base Strength and Load Path : Ok Embedment Steel and Pads Adequately installed : Yes i
l Reduction Factor input for Anchor # 3 Adequately installed : Yes Embedment Length : 13.50, Min:=12.50 in.
Gap at Threaded Anchor : 0.00 in.
Edge Distance - Edge 1 6.60 in.
Crack Size : 0.000 in.
Essential Relays in Cabinet : No i
Base Strength and Load Path : Ok l
Embedment Steel and Pads Adequately Installed : Yes i
Anchor 4.0 analysis AC-10A Page 3 of 5
l Reduction Factor input for Anchor # 4 Adequately Installed : Yes Embedment Length : 13.50, Min:=12.50 in.
Gap atThreaded Anchor: 0.00in.
Edge Distance - Edge 1 ; 6.60 in.
Crack Size : 0.000 in.
Essential Relays in Cabinet : No Base Strength and Load Path : Ok Embedment Steel and Pads Adequately Installed : Yes Reduction Factors Data Current : Yes Anc Pall /
Pa!!r/
No ld Vall Valir RT RN RL RG RS RE RF RC RR RP RB RM i
1 1
35030 57 N/A 1.00 1.00 1.00 1.00 1.00 0.84 1.00 1.00 1.00 1.00 1.00 1.00
)
7618.22 N/A 1.00 1.00 1.00 1.00 1.00 0.37 1.00 1.00 1.00 1.00 1.00 1.00 2
1 35030.57 N/A 1.00 1.00 1.00 1.00 1.00 0.84 1.00 1.00 1.00 1.00 1.00 1.00 7618.22 N/A 1.00 1.00 1.00 1.00 1.00 0.37 1.00 1.00 1.00 1.00 1.00 1.00 3
1 35030.57 N/A 1.00 1.00 1.00 1.00 1.00 0.84 1.00 1.00 1.00 1.00 1.00 1.00 j
7618.22 N/A 1.00 1.00 1.00 1.00 1.00 0.37 1.00 1.00 1.00 1.00 1.00 1.00 4
1 35030.57 N/A 1.00 1.00 1.00 1.00 1.00 0.84 1.00 1.00 1.00 1.00 1.00 1.00 7618.22 N/A 1.00 1.00 1.00 1.00 1.00 0.37 1.00 1.00 1.00 1.00 1.00 1.00 N/A
= Not Applicable Pall
= Allowable Pull without Reduced Inspection Vall
= Allowable Shear without Reduced Inspection Palir
= Allowable Pull with Reduced Inspection Va!!r
= Allowable Shear with Reduced Inspection
= Outlier X
= Reduction Factor Not Used RT
= Reduction Factor for Type of Anchorage RN
= Reduction Factor for Installation Adequacy RL
= Reduction Factor for Embedment RG
= Reduction Factor for Gap at Anchors RS
= Reduction Factor for Spacing RE
= Reduction Factor for Edge Distance RF
= Reduction Factor for Concrete Strength RC
= Reduction Factor for Concrete Cracks RR
= Reduction Factor for Essential Relays RP
= Reduction Factor for Base Stiffness and Prying Action RB
= Reduction Factor for Base Strength and Load Path RM
= Reduction Factor for Embed. Steel and Pads Analysis Results :
Analysis Performed : Yes Type of Analysis : Regular Spectral Accelerations (G's)
No N-S E-W Vertical Safety Factor 1
2.40E+000 9.61 E-001 2.28E-001 0.955 Anchor 4.0 analysis AC-10A Page 4 of 5
2
-2.40E+000
-9.61 E-001
-2.28E-001 0.965 3
-2.40E+000 9.61 E-001 2.28E-001 0.955 4
2.40E+000
-9.61 E-001
-2.28E-001 0.965 5
2.40E+000
-9.61 E-001 2.28E-001 0.955 6
-2.40E+000 9.61 E-001
-2.28E-001 0.965 7
2.40E+000 9.61 E-001
-2.28E-001 0.965 l
8
-2.40E+000
-9.61 E-001 2.28E-001 0.955
)
9 9.59E-001 2.40E+000 2.28E-001 0.952 10
. -9.59E-001
-2.40E+000
-2.28E-001 0.962 11 9.59E-001
-2.40E+000 2.28E-001 0.952 12
-9.59E-001 2.40E+000 2.28E-001 0.962 13
-9.59E-001 2.40E+000 2.28E-001 0.952 14 9.59E-001
-2.40E+000
-2.28E-001 0.962 15 9.59E-001 2.40E+000
-2.28E-001 0.962 16
-9.59E-001
-2.40E+000 2.28E-001 0.952 17 9.59E-001 9.61E-001 5.70E-001 1.962 18
-9.59E-001
-9.61 E-001
-5.70E-001 2.068 19 9.59E-001 9.61 E-001
-5.70E-001 2.068 20
-9.59E-001
-9.61 E-001 5.70E-001 1.962 21
-9.59E-001 9.61E-001 5.70E-001 1.962 22 9.59E-001
-9.61 E-001
-5.70E-001 2.068 23 9.59E-001
-9.61 E-001 5.70E-001 1.962 24
-9.59E-001 9.61 E-001
-5.70E-001 2.068 Minimum Safety Factor : 9.52E-001 I
HCLPF = (Minimum Safety Factor) * (RLE = 0.3g) = (9.52E-001) * (0.3g) = 0.2856g I
i l
l i
Anchor 4.0 analysis AC-10A Page 5 of 5
i 1
Omiha Public Pow:r District - Fcrt Crlh:un Statisn GIP R*.,v 2, Correct:d,2/14/92 SCREENING EVALUATION WORK SHEET (SEWS)
Status: No Sheet 1 of 1 ID : FW-19 (Rev. 0) l Class : 21 - Tanks and Heat Exchangers Desenption : EMERGENCY FEEDWATER STORAGE TANK Building : AUX Floor El. : 1045.00 Room, Row / Col: AB081,12WC-3N'3A.
Manufacturer, Model. Etc. :
i BASIS : External analysis l
- 1. The buckling capacity of the shell of a large, flat-bottom, vertical tank is equal to or greater N/A than the demand.
l
- 2. The capacity of the anchor bolts and their embedments is equal to or greater than the No*
demand.
- 3. The capacity of connections between the anchor bolts and the tank shell is equal to or N/A greater than the demand.
- 4. Attached piping has adequate flexibility to accommodate the motion of a large, flat-bottom, Yes vertical tank.
- 5. A ring-type foundation is not used to support a large, flat-bottom, vertical tank.
N/A IS EQUIPMENT SEISMICALLY ADEQUATE 7 No COMMENTS T
SRTs are W. Djordjevic and A. Al-Dabbagh - 8/16/93.
REF: Dwgs.11405-S-69 and Eaton Metal Products Corp. Dwgs.70-272 4 1 (02139) & 80048 (02377).
Anchorage:
The tank is supported on 4 - saddles and the saddles are anchored the the concrete by 2" J-bolts.
The tank length = 60' and diameter = 13'-6". Therefore the volume = 60 x Pl x (13.5/2)^2 = 8588 ft^3 Since the weight of the tank plus fluid = 109,840# + 486,673# = 596,513#. The total tank weight density =
596,513# / 8588 ft^3 = 69.5 #/ft^3 However, the tank overhang = (60 - 3 x 14) / 2 = 9' > S/2 = 14/2 = 7', therefore this tank requires an external manual analysis, and will be initially clasified as an outlier.