r-Q e

TENNESSEE VALLEY AUTHORITY CH ATTANOOG A. TENNESSEE 37401 400 Chestnut Street Tower II 35 m. 27 A 8 : 57 March 25, 1985 BLRD-50-43 8/84 -12 BLRD-50-439/84 -11 U.S. Nuclear Regulatory Ccmmission Region II Attn:

Dr. J. Nelson Grace, Regioral Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323

Dear Dr. Grace:

BELLEFQiTE NUCLEAR PLANT LNITS 1 AND 2 - HALOGENS IN CARBO INE 305 PAINT ON SUPPORTS WHIGI ARS AGAINST STAINLESS STEEL PIPE - BLRD-50-438/84-12, BLRD-50-439/84 FINAL REPORT The subject deficiency was initially reported to NRC-0IE Inspector P. E. Fredrickson cn January 31, 1984 in accordance with 10 TR 50.55(e) as NCR BLN BLP 8401. This we followed by our interim reports dated February 27 and August 21, 1984.

Enclosed is our final report.

1.* you have any questions, please get in touch with R. H. Shell at FTS 858-2474.

O Very truly yours,

TENNESSEE VALLEY AUTHORITY

, &>. ILpk4m J. W. Hufham, Manager Licensing and Regulations Enclosure cc:

Mr. James Taylor, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Cmmission Washington, D.C. 20555 Records Center (Enclosure)

Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 8505010

$$$$$k30 PDR A

PDR S

A hf)

L

)

An Equal Opportunity Employer

/

p ENC 1.03URE BELLEFmTE NUCLEAR PLANT UNITS 1 AND 2 4

~ ~

HALOGE!B IN CARBOLINE 305 PAINT m SUPPORTS WIm ARE AGAINST STAINLESS STEEL PIPE BLRD-50-438/84-12, BLRD-50-439/84-11 Nm BLN BLP 8401 10 GR 50.55(e)

FINAL REPORT Descriotion of Deficiency Carbon ateel pipe supports topooated with carboline 305 paint, a halogen-containing substance, are in contact with stainless steel piping. The deficiency was identified at Bellefonte Nuclear Plant (BLN) per Program Information Notice 83-8, " Stainless Steel Pipe in Contact with Halogenated Protective Coatings." The deficiency resulted f rce the failure to provide guidelines in General Construction Specifi cation G-29M restricting halogen-containing paint from contacting stainlca steel piping.

Safety Irnplications If stainless steel piping comes in contact with substances containing halogens, stress corrosion cracking could result in piping where operating temperatures exceed 1400F. Stress corrosion cracking in safety-related piping systems could be adverse to the safe operation of the plant.

Corrective Action TVA's Office of Construction (OC) is proceeding with the removal of.

carboline 305 paint applied to pipe supports that are in contact with stainless steel piping and are exposed to an operating temperature in excess of 1400F.

Renoval of the paint will be completed by January 15, 1986.

To prevent recurrence of this deficiency, TVA initiated a testing program to determine allowable halogen limits in zinc paints.

Based upon the test program results, purchase specification PF 106710 was issued as part of Construction Specification G-29M.

This purchase specification specifies the allowable halogen content in zinc paints.

Also, TVA drawing 6GWO470-00-01 RT and BLN Construction Specification N4 A-933 (SRN-N4 A-933-1) now prohibit the appliction of carboline 305 paint as a topcoat on pipe supports contacting stainless steel piping.

e

-.m