ML20116F073
| ML20116F073 | |
| Person / Time | |
|---|---|
| Site: | Braidwood |
| Issue date: | 04/18/1985 |
| From: | Danni Smith COMMONWEALTH EDISON CO. |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| 83-12, 9955N, NUDOCS 8504300553 | |
| Download: ML20116F073 (2) | |
Text
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
b
[O) are First National Plata Chicago, llhnois Commonwealth Edison
"""g
\\ C ' Address Reply to: Post Office Box 767
~/
Chicago. lilinois 60690 April 18, 1985 Mr. James G. Keppler Regional Administrator U. S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137
SUBJECT:
Braidwood Station Units 1 and 2 10 CFR 50.55(e) No. 83-12 Revised Final Report Anaconda Flexible Conduit NRC Docket Nos. 50-456/457 References (a):
E. D. Swartz letter to J. G. Keppler dated October 6, 1983.
Dear Mr. Keppler:
Reference (a) provided information concerning a deficiency reportable pursuant to 10 CFR 50.55(e) regarding the Anaconda flexible conduit at our Byron and Braidwood Stations.
The purpose of this letter is to clarify the description of corrective actions taken to resolve this issue at our Braidwood Station and provide an updated status.
This issue has been closed at our Byron Station.
This letter is considered to be a Final Report.
Status of Corrective Action All Anaconda type NWC and NPW flexible conduit (previously supplied under Specification F/L 2790) installed in Unit 1 containment will be replaced with stainless steel flexible conduit or modified by one of the two " taping" procedures described on the electrical installation drawings.
In addition, all liquid tight flexible metal conduit furnished on safety related and non-safety related local instrument racks located in the Unit 1 and Unit 2 containments will be replaced in the same manner.
The electrical contractor has repaired or replaced approximately 50 percent of the safety related flexible conduit in Unit 1 Containment (this does not include instrumentation racks).
It is expected to take approximately four months to complete this effort.
The electrical contractor is currently in the process of identifying the non-safety related flexible conduits and instrument racks in containment Unit I which need to be reworked.
Identification and completion of this ef fort is expected to take approximately six months for non-safety related conduits and approximately nine months for both the safety and non-safety related instrument racks.
4gg APR 191985 h
e
- . Anaconda flexible conduit has not been installed in Unit 2 containment other than certain instrumentation racks which are currently being identified and will be reworked.
It is anticipated this effort will take approximately nine months to complete.
Please address any questions that you or your staff may have concerning this matter to this office.
Very truly yours, I
I add [5(uk~
David H. Smith Nuclear Licensing Administrator
/klj cc:
NRC Resident Inspector - Braidwood Director of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555 9955N