19 6 7 ;

e

.:cgr

('~

TABLE 3.6-1 (Continued)

CCNTAINMENT ISOLATION VALVES MAXIMUM PENETRATION VALVE NO.

FUNCTION ISOLATION TIME (SEC) 6.

Main Steam Isolation (Continued) 85 1M5101S" Main Steam 10.0

-7 86 IMS101C"'

Main Steam 10.0

( 7 t

7.

Feecwater Isolation g

P

(

76 1FWOO90" Main Feecwater 5.0 76 1FWO430" Main Feecwater 6.0 79 LFWOO9A" Main Feecwater 5.0 79 IFWO43A" Main Feedwater 6.0 84 1FWOO98*

Main Feecwater 5.0

.84 1FWO438" Main Feecwater 6.0 87 1FW009C" Main Feecwater 5.0 87 1FWO43C" Main Feedwater 6.0 99 1FWO350" Main Feecwater 6.0 99 1FWO390*

Main Feecwater 6.0 100 IFWO35A" Main Feecwater 6.0 100 LFWO"9A" Main Feecwater 6.0 101 1FWO358" Main Feecwater 6.0 101 IFWO398*

Main Feecwater 6.0 102 LFWO35C" Main Feedwater 6.0 102 IFWO39C" Main Feecwatar 6.0 8.

Remote Manual 58 1RH8701A"8b RH Suction N/A 58 1RH87013*1@'

kH Suction N/A 75 1RH8702A"3$

RH Suction N/A l

75 1RH87023";#

RH Suction N/A 59 15I8881" Hot Leg Safety Injection N/A 73 15I8824" Hot Leg Safety Injection N/A 66 1SI8825" Hot Leg RH-Injection N/A 60 15I8823" Cold leg Safety Injection N/A l

50 ISIS 890A" Cold Leg RH Injection N/A 51 15I88908" Cold Leg RH Injection N/A l

26 15I8843" Cold Leg Safety Injection N/A 33 1CV8355A" RCP Seal Injection N/A 33 1CV83550" RCP Seal Injection N/A 53 1CV83558" RCP Seal" Injection N/A 53 1CV8355C" RCP Sea 1 Injection N/A B501290513 850118 PDR ADOCK 05000 DR k_

P

. SYRON - UNIT L 3/4 6-21.

s 4

5

.l

e e

F TABLE'3.5-1 (Continued)

CONTAINMENT ISOLATION VALVES MAXIMUM PENETRAT!ON VALVE NO.

FUNCTTON ISOLATICN TIME (SEC) 8.

Remote Manual (Continued) 59 ISIS 802A" Hot Leg Safety Injection N/A 73 ISI8802S" Hot Leg Safety Injection N/A

/

60 15I88358~

Hot Leg Safety Injection N/A

[,

50 ISI8809A" RH Cold leg Injection N/A

(

51 ISIS 8098" RH Cold Lag Injection N/A 66 ISIS 840" Hot. Leg Safety Injection N/A 100 1AF013A" Feedwater N/A 100 1AF013E" Feecwater N/A 101 1AF0138" Feecwater N/A 101 1AF013F" Feecwater N/A 102 1AF013C' Feecwater N/A 102 1AF013G" Feecwater N/A 99 1AF0130" Feecwater N/A 99 1AF013H" Feecwater N/A 9.

Manual 37 1CV8346*

RCS Loco Fill N/A I3 IVQOl6 Instrument Penetration N/A I3 IVQO17 Instrument Penetration N/A I3 IVQO18 Instrument Penetration N/A I3 IVQ019 Instrument Penetration N/A

  • 15 1RYO75 Instrument Penetration N/A 30 l'nM190 Make-Up Oomin N/A 57 1FC009 Scent Fuel Pool Cleaning N/A 57

.1FC010 Spent Fuel Pool Cleaning N/A 32 1FC011 Scent Fuel Pool Cleaning N/A l

32 1FC012 Spent Fuel Pool Cleaning N/A 77 1M5021D" Y Main Staam N/A 78 1M5021A" Y Main Steam N/A SS IM50213"pF Main Steam N/A 86 1M5021C'alf Main Steam N/A

~AL IPR 002E Process Radiation N/A AL.

1PR033A Process Radiation N/A AL

~1PR0338 Process Radiation N/A ~

AL' 1PR002F Process Radiation N/A I

J.

AL-1PR033C Process Radiation N/A l

-(

AL IPR 0330

- Procass Radiation N/A l

3

' BYRON - UNIT 1

  • 3/4-6-2r 4

f A

4 e

.y

$ ~

v' f

TABLE 3.5-1 (Continued)

CCNTAINMENT ISOLATION VALVES MAXINUM-PENETRATION VALVE NO.

FUNCTION ISCLATION TIME (SEC) 9.

Manual (Continued) 99 1FWO150" Y Fee &ater N/A 100 1FWO15A" #

FetWater N/A 101 IFWOISB"7F Fet Water N/A j

102 IFWOISC* $

FeeWater N/A

10. Check 28 1CV8113 RCP Seal 'Jater Return N/A 37 1CV8348" RCS Loop Fill N/A

(

7 i

6 IWOO7A Chilled Water N/A

/

10 IWOO78 Chi 11ed Water-N/A p

21 1CC9534 RCP Mtr Srng Return N/A I

24 1CC3518 RCP Thermal Barrier Return N/A 25 1CC3486 RCP Cooling Wtr Supply N/A 1

1CS008A Containment Spray N/A 16 1C30088 Containment Spray N/A 39 LIA091 Instrument Air N/A 30 1W191 Make-Up Domin N/A 52 1PR032 Process Radiation N/A AL IPR 002G Process Radiation N/A AL IPR 002H Process Radiation N/A I

12 1PS231A Hydrogen Monitor N/A 12

,1PS2313 Hydrogen Monitor N/A l

27 1RY8047 PRT Nitrogen N/A i

44-1RY8046 PRT Make-Ua N/A 25 ISI8815" Safety Infection

.N/A 50 ISIS 818A" Safety Injection N/A 50 15I88180" Safety Injection N/A j

51 ISI88188" Safety Injection N/A 51

1SI8818C' Safety Iirjection N/A N/A 59 ISI8905A" Safety Injec. tion

~

N/A 59 1SI88050" Safety Injection

' 60 ISIS 819A" Safety Injection-N/A-50-ISIS 8198"'

Safety Injection N/A

.k 3YRON - UNIT 1 3/4 6-23'

.,f O

e

r 4

Brr -

wws 4g C

TABLE 3.5-1 (Continued)

CONTAINMENT ISOLATION VALVEi MAXIMUM' PENETRATION VALVE NO.

FUNCTION ISOLATION TIME (SEC)

10. Check (Continued) j; 60 ISI8819C*

Safet/ Injection N/A 60 15188190" Safety Injection N/A 66 ISI8841A" Safety Injection N/A 66 ISIS 8413" Safety Injection N/A 73 ISI8905B" Safety Injection N/A 73 ISIS 905C*

. Safety Injection N/A 55 15I8968" Safety Injection N/A 34 1FP345" Fire Protection N/A b

33 1CV8368A" RCP Seal Injection N/A 33 1CV83680" RCP Seal Injection N/A 53 1CV83688" RCP Seal Injection N/A 53 1CV8368C'~

RCP Seal Injection N/A I

11. S/G Safeties /DORVs 77 LM50130" Main Staam N/A 77 1M50140*

Main Staam N/A 77 LMS0150" Main Staam N/A -

77 LM501E0" Main Steam N/A 77 1MS0170" Main Steam N/A 78 LMS013A" Main Steam N/A 78 1MS014A" Main Steam N/A 78 LM5015A" Main Steam N/A 78 LM5016A*

Main Steam N/A 78 LMS017A" Main Staam N/A 85 LM50138" Main Steam N/A i

85 L450148" Main Steam N/A I

85 L95015B" Main Staam N/A 85 1M5016B"-

Main Steam N/A 85 LMS017B" Main Steam N/A 86 LM5013C*

Main Steam N/A 86 1MS014C' Main Steam N/A 86 LMS015C' Main Steam N/A-i 86 IM5016C' Main Steam M/A 86 1M5017C*

Main Steam N/A 77 LM50180" Main Staam 20 78 1MS018A" Main 5, team 20 i

85 1MS0188" Main Steam 20 86 LM5018C" Main 5taim' 20 i

i "Not suoject to Type.C leakage tests.

"" Proper valve coeration will be demonstrated by.verifyingL that the valve strokes to its required cosition.

~

~

M OAy be, o 'hed OA qw ~i A,h V M $ b d b & k TSi.(A h M,

. TodC Ahtr

c. d ol...

. f' L.

- - BYRON - UNIT 1.

3/4 6-24 e

0

..