HOUSTON llGHTING & POWER COMPANY CITY PUBLIC SERVICE BOARD OF SAtLANTONIO CENTRAL POWER AND LIGHT COMPANY CITY OF AUSTIN. TEXAS DQ.CKET NO.50-49Q 10VTH TEXAS PROJrlT,. UNIT 1 AMENDMENT TO FAClllTY OPERATING llCEhSE Amendment No. 41 License No. NPF-76 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for cmendment by Houston Lighting & Power Company *
(HL&P) acting on behalf of itself and for the City Public Service Board of San Antonio (CPS), Certral Power and Light Company (CFL), and City of Austin, Texas (C0A) (the licensees) dated June 12, 1990, as supplemented by letter dated July 17, 1991, complies with the standards and requirements of the Atomic Eneroy Act of 1954, as
. amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, as amer.ded, the provisions of the Act, and the rules and regulations of r
the Commission; k
C.
There is reasonab'.: assurance:
(i) that the activities authorized by this amendmen rs.n n conducted without endangering the health and safety of the public, and (ii) that such activ. ties will be conducted in compliance with the Commission's regulations; D.
The issuance of this license amendment will not be inimical to the common defense and sect.rity or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
- Houston 1.ighting & Pawer Company is autnorized to act for the City Public Service Board of San Antonio, Central Power and Light Company ant'. City of Austin, Texas and has exclusive responsibility and control over the physical construction, operation and maintenance of the facility.
9208260142 920g19 i
DR ADOCK 05000498 FDR
. 2.
Accordingly, the license is amended by changes to the Technical Specifi-cations as indicated in the attachment to this license amendment and Paragraph 2.C.(2) of Facility Operating License No. NPF-76 is hereby amended to read as follows:
2.
Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amenoment No.
41, and the Environmental Protection Plan contained in-Appendix B, are hereby incorporated in the license.
The licensee shall operate the ' facility in accordance with the Technical Specifications and the Environmental Prctection Plan.
3.
The license amendment is effective as of its date of issuance and is to be implemented prior to restart from the fourth refueling outage.
FOR THE NUCLEAR REGULATORY COMMISSION r
,)
s
( V.s e / -
3,4 s r.
Suzanne't. Black, Director Project Directorate IV-2 Division of Reactor Projects III/IV/V Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications
-Date of Issuance:
August 19, 1992
s ATTACHMENT TO LICENSE AMENDMENT NO. 41 FACILITY OPERATING LICENSE NO. NPF-76 DOCKET NO. 50-498 Replace the following pages of the Appendix A Technical Specifications with the attached pages.
The revised pages are identified by Amendment number and contain vertical lines indiciting the areas of change.
REMOVE INSERT 3/4 5-11 3/4 5-11 B 3/4 5-3 8 3/4 5-3
4 1
[t!ERGENCY CORE COOLING SYSTEMS' 3/4.5.6 RESIDUAL HEAT REMOVAL (RHR) SYSTEM LIMITING CONDITION FOR OPERATION 3.5.6 Three independent Residual Heat Removal (RHR) loops shall be OPERABLE with each loop comprised of:
a.
One OPERABLE RHR heat exchanger, and c.
One OPERABLE flowpath caoable of taking suction from its associated RCS hot leg and disch&rging to its associated RCS cold leg.*
APPLICABILITY: MODES 1, 2 and 3.
ACTION:
a, With one RHR loop inoperable, restore the required loop to OPERABLE status witnin 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6-hours and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, b.
With two RHR loops incperable, restore at least two RHR loops to OPERABLE status within 24 hnuts or be in at least HOT STANDBY within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.
c.
With three RHR loops inoperable, immediately-initiate corrective action to restore at least one RHR loop to OPERABLE status as soon as possible.
fURVEILLANCEREQUTREMENTS 4.5.6.1 Each RHR loop shall be demonstrated OPERABLE pursuant to the requirements of Specification 4.0.5.
4.5.6.2 At least once per 18 months by verifying automatic interlock action of the RHR system from the React - Coolant System to ensure that:
a.
With a simulated or actual Reactor Coolant System pressure signal greater than or equal to 350 psig, the interlocks prevent the valves from being opened, g
]
- Valves MOV-0060 A, B, and C and M0V-0061, A, B, and C may have power removed to support the FHAR (Fire Hazard Analysis Report) assumptions.
I SOUTH TEXAS - UNITS 1 & 2 3/4 5-11 Unit 1 Amendment No. 4, 41 Unit 2 - Amendment No. 18
a -,
4 p -
+-
m:
m,4.-.
+
s..
ae.
M a-A a
EMERGENCY CORE ~ COOLING SYSTEMS gd,SES 1/4.5.6 -RESIDVAL HEAT REMOVAL (RHR) SYSTEM The OPERABILITY of the RHR system ensures adequate heat removal capabilities for long-Te m Core Cooling in the event of a small-break loss-of-coolant accident (LOCA), an isolatable LOCA, or a secondary break in MODES 1, 2, and 3.
The limits on the OPERABILITY of the RHR system ensure that at least one RHR loop is available for cooling including single active failure criteria.
I SOUTH TEXAS - UNITS 1 & 2 B 3/4 5-3 Unit 1 - Amendment No. 41 Unit 2 - Amendment No. 18
-~.
.