ML20112E613

From kanterella
Jump to navigation Jump to search
Forwards Revised Pages to Emergency Response Data System (ERDS) at San Onofre Nuclear Generating Station (SONGS) Units 2 & 3
ML20112E613
Person / Time
Site: San Onofre  
Issue date: 06/04/1996
From: Marsh W
SOUTHERN CALIFORNIA EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9606070009
Download: ML20112E613 (10)


Text

..

/

Southem Califomia Edison Company P. O. BOX 128 SAN CLEMENTE, CALIFORNIA 92674-0128 AAANAGER O LE F EQ Y AFFAIRS (714 368 1

U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C.

20555 i

Gentlemen:

Subject:

Docket Nos. 50-361 and 50-362 Emergency Response Data System.

San Onofre Nuclear Generating Station Units 2 and 3 This letter is to inform the NRC of changes that have been made to the Emergency Response Data System (ERDS) at San Onofre Nuclear Generating Station (SONGS) Units 2 and 3.

These changes were discussed with Mr. John Joliceour of the NRC staff on March 21, 1996. As required by 10CFR50 Appendix E.

Section VI.3.a. any hardware and software changes that affect the transmitted

-data points identified in the ERDS Data Point Library must be submitted to the NRC within 30 days after the changes are completed. Accordingly, the revised pages to the ERDS Data Point Library are provided in the' Enclosures to this letter.

Data points for the Letdown Line Radiation Monitor R202 and Containment Purge Vent Stack Radiation Monitors RT7828 A and B have been removed from the ERDS Data Point Library.

These three monitors for each unit are not currently in service.

Monitor R202 which has been removed from service, provided information for the reactor coolant system (RCS) letdown ERDS parameter. The information for this parameter can be obtained by a grab sample through the Post-Accident Sampling System (PASS) and provided to the NRC over the Emergency Notification System (ENS).

Monitors RT7828 A and B, which were never in service, were intended to provide information for the Effluent Gas ERDS by the wide range gas monitor (RT7865) parameter. This information is provided

, which also provides input to the ERDS system.

The above described changes were implemented on the ERDS SONGS 2 and 3 data bases on May 9, 1996.

This letter is the formal 10CFR50 Appendix E Section VI.3.a notification of'the changes to the EROS data base for both SONGS Unit 2 and Unit 3.

nno018 9606070009 960604 PDR ADOCK 05000361 A

F-PDR

() \\\\

Document Control Desk If you have any questions regarding this matter please let me know.

Very truly yours, 1

Mb Enclosure cc:

L. J. Callan, Regional Administrator,.NRC Region IV J. Dyer, Director, Division of Reactor Projects, Region IV K. E. Perkins, Jr., Director, Walnut Creek Field Office, NRC Region IV J. A.-Sloan, NRC Senior Resident Inspector, San Onofre Units 2 & 3 H. B. Fields, NRC Project Manager, San Onofre Units 2 and 3 1

)

I i

h.

I 4

e e

ENCLOSURE 1 EMERGENCY RESPONSE DATA SYSTEM CHANGES FOR i

SAN ON0FRE NUCLEAR GENERATING STATION UNIT 2

)

i 2

l j

DWG kO.' 90052 PWR DATA POINT LIBRARY REFERENCE FILE I

DATE:

May 9, 1996 REACTOR UNIT:

$02 DATA FEEDER:

$021 NRC ERDS PARAMETER:

NOT LISTED l

Po!NT ID:

R202 PLANT SPEC POINT DESC.: TOTAL ACTIVITY LETDOWN GENERIC /COND DESC.:

LETDOWN LINE RAD MON-ANALOG / DIGITAL:

A

' ENGR UNITS / DIG STATES: CPM ENGR UNITS CONVER$10N N/A MINIMUM INSTR RANGE:

10 i

MAXIMUM INSTR RANGE:

P t c: E+e eted from Database ZERO' POINT

REFERENCE:

REFERENCE POINT NOTES: N/A 1

PROC OR SENS:

NUM8ER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATIONS:

RADWASTE BLDG ELEV 24 FT ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER

. SUPPLY CUT-OFF POWER LEVEL:

N/A N1 DETECTOR POWER SUPPLT TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

DISPLAYS LAST GOOD READING TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE DESC.:

N/A UNIQUE SYSTEM DESC.:

4.7E-9UC/CC/ CPM 55

"DbKi NO 90052 PWR DATA PO!NT LIBRARY REFERENCE FILE DATE:

May 9, 1996 REACTOR UNIT:

SO2 DATA FEEDER:

$021 NRC ERDS PARAMETER:

EFF GAS RAD j

PolNT ID:

RT7828A PLANT SPEC POINT DESC.: CONTAINMENT PURGE VENT STACK IODINE GENERIC /COND DESC.:

EFF GAS RAD ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

CPM j

ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

1E+1 MAXIMUM INSTR RANGE:

lE+l l

ZERO PolNT REFERENCE,Pojpt ce eted f. rom Database REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

CX SENSOR LOCATIONS:

'IS0 KINETIC N0ZZLE EL 133 CTMNT PURGE STK ALARM / TRIP SET PolNTS:

N/A NI DETECTOR POWER SUPPLY CUT OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

DISPLAYS LAST GOOD READING TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE DESC.:

N/A UNIQUE SYSTEM DESC.:

FLO=40KCFM 63

I-I

' DWG N0'. 90052 l

l PWR DATA POINT LIBRARY REFERENCE FILE DATE:

May 9, 1996 REACTOR UNIT:

$02 DATA FEEDER:

S021 i

NRC ERDS PARAMETER:

EFF GAS RAD POINT ID:

RT78288 PLANT SPEC POINT DESC.: CONTAINMENT PURGE VENT STACK PARTIC ACT GENERIC /COND DESC.:

EFF GAS RAD ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

CPM ENGR UNITS CONVERSION:

N/A MINIMUM INSTR RANGE:

1E+1

E+l MAXIMUM INSTR RANGE:

ZERO POINT REFERENCE,Poj,pt ce eted from Database REFERENCE POINT NOTES: N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

CX SENSOR LOCATIONS:

IS0 KINETIC N0ZZLE EL 133 CTMNT PURGE STK ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN ON POWER LEVEL:

N/A INSTRUMENT FAILURE MUDE:

DISPLAYS LAST GOOD READING TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE DESC.:

N/A UNIQUE SYSTEM DESC.:

1.23 X 10 E-7 UCI/ COUNTS 64

ENCLOSURE 2 1

EMERGENCY RESPONSE DATA SYSTEM CHANGES l

FOR SAN ON0FRE NUCLEAR GENERATING STATION UNIT 3 i

i l

e

)

'DWG fiO 90052 i

1 PWR DATA POINT LIBRARY REFERENCE FILE 1

l DATE:

May 9, 1996

']

1 REACTOR UNIT:

$03 DATA FEEDER:

S031 l

NRC ERDS PARAMETER:

NOT LISTED i

POINT ID:

R202 PLANT SPEC POINT DESC.: TOTAL ACTIVITY LETDOWN GENERIC /COND DESC.:

LETDOWN LINE RAD MON ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: CPM i

ENGR UNITS CONVER$10N: N/A MINIMUM INSTR RANGE:

10 OillKe e ec

'r0111 Ja a 3ase MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

N/A REFERENCE PolNT NOTES: N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATIONS:

RADWASTE BLDG ELEV 24 FT ALARM / TRIP SET P0lNTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

DISPLAYS LAST GOOD READING TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE DESC.:

N/A UNIQUE SYSTEM DESC.:

4.7E-9UC/CC/ CPM 121

'DWGh5.90052 PWR DATA POINT LIBRARY REFERENCE FILE DATE:

May 9, 1996 REACTOR UNIT:

S03 DATA FEEDER:

5031 NRC ERDS PARAMETER:

EFF GAS RAD PolNT ID:

RT7828A PLANT SPEC POINT DESC.: CONIAINMENT PURGE VENT STACK IODINE GENERIC /COND DESC.:

EFF GAS RAD ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES: CPri ENGR UNITS CONVER$10N: W/A MINIMUM INSTR RANGE:

1E+1 OiIl!r+Cerec yom Jr2 aue MAXIMUM INSTR RANGE:

ZERO' POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUM8ER OF SENSOR $

2 HOW PROCESSED:

CX SENSOR LOCATIONS:

IS0 KINETIC N0ZZLE EL 133 CTMNT PURGE STK ALARM / TRIP SET POINTS: N/A NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:

N/A-NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

N/A INSTRUMENT FAILURE MODE:

DISPLAYS LAST GOOD READING TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

LEVEL REFERENCE DESC.:

N/A UN!QUE SYSTEM DESC.:

FLO=40KCFM 129 i

.m

~m I

1 DWG NO. 90052 l

r i

l PWR DATA POINT LIBRARY REFERENCE FILE-l '

DATE:

May 9,1996 REACTOR UNIT:

S03 DATA FEEDER:

S031 NRC EROS PARAMETER:

EFF GAS RAD POINT ID:

RT78288 PLANT SPEC POINT DESC.: CONTAINMENT PURGE VENT STACK PARTIC ACT GENERIC /COND DESC.:

EFF LAS RAD l

1 ANALOG / DIGITAL:

A ENGR UNITS / DIG STATES:

CPM ENGR UNITS CONVERS10N:

N/A MINIMUM INSTR RANGE:

1E+1 OilD.c e e e<

r0111 Ja a 3ase MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

P NUMBER OF SENSORS:

2 HOW PROCESSED:

CX SENSOR LOCATIONS:

ISOKINETIC N0ZZLE EL 133 CTMNT PURGE STK ALARM / TRIP SET PolNTS:

N/A NI DETECTOR POWER SUPPLY CUT *0FF POWER LEVEL:

N/A NI DETECTOR POWER SUPPLY TURN-ON POWER 1

LEVEL:

N/A INSTRUMENT FAILURE MODE:

DISPLAYS LAST GOOD READING TEMPERATURE COMPENSATION FOR DP TRANSMITTERS.

i LEVEL REFERENCE DESC.:

N/A UNIQUE SYSTEM DESC.:

1.23 X 10 E-7 UCI/ COUNTS i

l l

l l

130

,