Proposed Tech Spec,Changing Table 3.8-1 Re Containment Penetration Conductor Overcurrent Protective Devices
ML20112B780
Person / Time
Site: Arkansas Nuclear 
Issue date: 03/13/1985
From:
ARKANSAS POWER & LIGHT CO.
To:
Shared Package
ML20112B753 List:
References
NUDOCS 8503190311
Download: ML20112B780 (12)


Text

_ _ _ _ _ _ _ _ _ _

\\

TABLE 378-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES 6

Primary Backup Location Device Device of System Number Number Devices Powered A. 6900 VAC 152-11 152-13, or Switchgear 2H1 RCP 2P32A 152-14, or 152-15 152-12 152-13, or Switchgear 2H1 RCP 2P32D 152-14, or 152-15 152-21 152-23, or Switchgear 2H2 RCP 2P32B 152-24, or 152-25 152-22 152-23, or Switchgear 2H2 RCP 2P32C 152-24, or 152-25 B. 480 VAC 52-131 None, circuit 281 Containment shall not be Building energized Crane 2LM2 unless plant is shutdown 52-523 52-512 285 Pressurizer Proportional Heater Bank 1 52-533 52-512 285 Hydrogen Recombiner 1 52-623 52-612 286 Pressurizer Proportional Heater Bank 2 ARKANSAS - UNIT 2 3/4 8-13 Amendment No. 35 8503190311 850313 PDR ADOCK 05000368 p

PDR b

r TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES e

Primary Backup Location Device Device of System Number Number Devices Powered 52-623 52-612 286 Hydrogen Recombiner 2 52-731 52-732 287 MCC 2871 52-824 52-823 2B8 MCC 2B81 1

52-922 52-912 2B9 Pressurizer Backup Heater Bank 3 52-923 52-912 289 Pressurizer Backup Heater Bank 5 Pressurizer 52-1022 52-1012 2B10 i

Backup Heater Bank 4 l

52-1023 52-1012 2B10 Pressurizer Backup Heater Bank 6 C. 480 VAC MCC 52-51A4 52-51H2 MCC 2851 Reactor Cavity Cooling Fan 2VSF34A-1 52-5182 52-51H3 MCC 2B51 Containment Sump Isolation-MOV2CV-2060-1 52-5103 52-51H4 MCC 2B51 Containment Recirculating Fan 2VSF31A-1 ARKANSAS - UNIT 2 3/4 8-14 Amendment No. 35

TABLE'3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-51D4 52-51H5 MCC 2B51 Containment Recirculating Fan 2VSF31C-1 52-51E2 52-51H6 MCC 2B51 Reactor Drain Tank Drain Iso.

Valve 2CV-2201c 52-51E4 52-51C1 MCC 2851 Pressurizer Relief Valve Isolation 2CV-4730-1 52-51F1 52-51H7 MCC 2851 RCP Controlled Bleedoff Iso.

Valve 2CV-4846-1 52-51F2 52-51H8 MCC 2851 Safety InjectiG Tank 2T2A Discharge MOV 2CV-5003-1 i

52-51G2 52-51L2 MCC 2B51 Shutdown Cooling Return Header Iso.

Valve 2CV-5084-1 52-51G3 52-51H9 MCC 2851 Check Valve Leakage Drain Valve 2CV-5105-1 52-51H1 52-51L3 MCC 2B51 Safety Injection Tank 2T28 Discharge MOV 2CV-5023-1 ARKANSAS - UNIT 2 3/4 8-15 Amendment No. 35 m -

e TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System

' Number Number Devices Powered 52-51K1 52-51L4 MCC 2851.

Containment Sump Isola-tion MOV 2CV-5647-1 52-51K2 52-51J4 MCC 2851 Pressurizer Relief Iso.

Viv. 2CV-4741-[

ARKANSAS - UNIT 2 3/4 8-15a Amendment No. 35 m-.

,i TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-51K3 52-51L5 MCC 2B51 Containment Air Purge Isolation Valve 2CV-8289-1 52-51K4 52-51L6 MCC 2851 Containment Air Purge Isolation Valve 2CV-8291-1 52-51L1 52-51L7 MCC 2B51 Containment Vent Header Isolation Valve 2CV-2401-1 52-51M1 52-51L8 MCC 2B51 Regenerative Heat Exchanger:

Inlet Valve 2CV-4821-1 52-51N3 52-51L9 MCC 2B51 Reactor Cavity.

Cooling Fan Bypass Damper 2HCD8243-1 52-53G1 52-53AS MCC 2B53 Containment Cooling Fan Bypass Damper.

Motor 2UCDM8203-1 52-53G2 52-53A6 MCC 2B53 Containment Cooling Fan Bypass Damper

  • Motor 2UCDM8209-1 52-53H3 52-53H2 MCC 2B53 Pressurizer l

Spray Valve 2CV-4652 ARKANSAS - UNIT 2 3/4 8-16 Amendment No. 35

s..

{

b i

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 7

t 52-53L1 52-53K5 MCC 2853 Containment Cooling Fan I

2VSF1A 52-53L2 52-53K6 MCC 2B53 Containment Cooling Fan i

2VSFIB l

l

[

f I

i l

i ARKANSAS - UNIT 2 3/4 8-16a Amendment No. 35 l

r.

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup.

Location Device Device of System Number Number Devices Powered 52-54G2 52-54C5 MCC 2B54 H Purge 2

Containment Iso. Valve 2CV-8233-1 52-54G3

.52-54B4 MCC 2854 H Purge 2

Containment Iso. Valve 2CV 8259-2 52-54J2 52-54J3 MCC 2B54 Containment Elevator Motor 2MM6

'52-54K2 52-54J4 MCC 2854 Containment Building Lighting Panel 27 LA 52-54K3 52-54J8 MCC 2854 RCP 2P3A 011 Lift Pumps 2P63Al & A2 52-54K4 52-54F3 MCC 2854 RCP 2P32B Oil Lift Pumps 2P63B1 & B2 52-61A4 52-61H3 MCC 2B61 Reactor Cavity Cooling Fan 2VSF34B-2

!52-61D3 52-61H4 MCC 2861 Containment Recirculating.

Fan 2VSF318-2 52-61D4 52-61H5 MCC 2861 Containment Recirculating Fan 2VSF31D-2 ARKANSAS - UNIT 2-3/4 8-17 Amendment No. 35

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device.

of System Number Number Devices Powered 52-61F2 52-61H6 MCC 2861 Safety Inject.

Tank 2T2C Discharge MOV 2CV-5043-2 52-61G2 52-61K8 MCC 2861 Check Valve Leakage Drain Valve 2CV-5106-2 ARKANSAS'- UNIT 2 3/4 8-17a Amendment No. 35

[

t TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-61G3 52-61H7 MCC 2861 Reactor Coolant System Charging Line MOV 2CV-4831-2 52-61G4 52-61H8 MCC 2B61 Reactor Coolant System Charging Line MOV 2CV-4827-2 52-61H1 52-61K3 MCC 2B61 Safety Inj.

Tank 2T20 Dis.

MOV 2CV-5063-2 52-61H2 52-61K7 MCC 2B61 Containment Sump Iso.

MOV 2CV-5648-2 52-61L2 52-6102 MCC 2B61 Pressurizer Relief Iso.

Viv. 2CV-4731, 1

52-61L3 61K4 MCC 2B61 Letdown Line Stop Valve 2CV-4820-2 52-61L4 52-61L1 MCC 2B61 Pressurizer Spray Viv.

2CV-4651 52-61N2 52-61K6 MCC 2B61 Reactor Cavitg Cooling Fan Damper 2HCD 8244-2 52-62E5 52-62C2 MCC 2B62 Shutdown Cooling Return Header Iso. Valve 2CV-5086-2 ARKANSAS - UNIT 2 3/4 8-18 Amendment No. 35 L

TABLE 3.8-1 CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-63F2 52-63E1 MCC 2B63 Containment Chilled Water Isol. Valve 2CV-3850-2 ARKANSAS - UNIT 2 3/4 8-18a Amendment No. 35 L-

..r-f..

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR OVERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered 52-63G4 52-63E2 MCC 2863 RCP Cooler Iso. Valve 2CV-5254-2 52-63L1 v2-63J1 NCC 2B63 Containment Cooling Fan 2VSFIC 52-63L2 52-63J2 MCC 2863 Containment Cooling Fan 2VSF10 64D4 52-64B3 MCC 2B64 Containment Cooling Fan Bypass Damper Motor 2VCDM 8216-2 52-64E3 52-6484 MCC 2B64 Pressurizer Auxiliary Spray MOV 2CV-4824-2 52-64E4 52-64C2 MCC 2B64 Containment Cooling Fan Bypass Damper Motor 2VCDM 8222-2 52-64J1 52-64B1 MCC 2864 RCP 2P32C 011 Lift Pumps 2P63C1

& C2 52-64K1 52-64H2 MCC 2864 RCP 2P320 011 Lift Pumps 2P63D1

& D2 j

ARKANSAS - UNIT 2 3/4 8-19 Amendment No. 35 l

L

C~ L l*

TABLE 3.8-1 (Continued)

CONTAINMENT PENETRATION CONDUCTOR 0VERCURRENT PROTECTIVE DEVICES Primary Backup Location Device Device of System Number Number Devices Powered D.

480/277 21PA-19 52-15C1 Primary -21PA Space Heater Backup -2B15 for RCP 2P32A 21PA-25 52-15C1 Primary -21PA Space Heater Backup -2B15 for RCP 2P32B 21PA-31 52-15C1 Primary -21PA Space Heater Backup -2B15 for RCP 2P32C 21PA-20 52-15C1 Primary -21PA Space Heater Backup -2B15 for RCP 2P32D

{

E. 125 VDC 72-0318 72-0320 DC Control Containment Center Bldg 125 VDC 2003 Lighting Panel 220A 72-26A3 72-26A2 DC MCC Pressurizer 2026 Vent Valve 2CV-4740-2 72-27A3 72-27A2 DC MCC Pressurizer 2D27 Vent Valve 2CV-4698-1 F.

240 VAC CEA 1 CB3021 2C72 CEA 1 C0101 CB3022 ARKANSAS - UNIT 2 3/4 8-20 Amendment No. 35 L