Clarifies Two Points in Util Re Components Being Relocated from skid-mounted Control Panels & Location of One Instrument Stand.Upon Completion of Mods,License Condition 2.C.19 Will Be Satisfied
ML20108A556
Person / Time
Site: Summer 
Issue date: 11/08/1984
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
References
NUDOCS 8411150057
Download: ML20108A556 (2)


Text

p&V

,y

~

y cm.

, png

~+:

~

, g" -

f SOUTH CAROLINA ELECTRIC 4k' gas COMPANY-

~

1

. POST OppaCE 784

,1 V,

' Cos.uustA. south CAn0UNA SSSIS

~

L O' W. Dix 0N. JR. '

~

I

' = ' ' * * * " ' * " '

November;8, 1984:

3 5 NucLaAm OpsstATeosse -

1Mr..--Harold R. Denton,'DirectorE LOfficeiof Nuclear Reactor Regulation

?U.S.~ Nuclear Regulatory Commission Washington, D.C. 120555

Subject:

Virgil C. Summer Nucl' ear Station

. Docket ik). 50/395

. Operating License No. NPF-12:

Licensing Condition 2.C.19-Diesel Generator Vibration

Dear'Mr. Denton:

In a letter from O.'W. Dixon, Jr. to H. R. Dentonidated June 6, 1984, South Carolina Electric and Gas Company (SCE&G) outlined the~ modifications being made to the Emergency Diesel Engine Auxiliary' Support System-to meet Operating License = Condition 2.C.19 for the Virgil'C.. Summer Nuclear Station.- This letter is

-provided to clarify two'(2) points-in the June 6, 1984 letter

-concerning the components being relocated from the skid-mounted control' panels and :the location of one of the instrument stands.

' The active components in the control relay panel located on -the diesel' skid have been relocated to a new wall-mounted control' panel as outlined in our June 6, 1984 letter.

These active components

  • include all relays, fuses, speed switches, and heaters.

.The existing control panel has been lef t mounted on the diesel skid and contains only passive components such as terminal blocks and' indicating lights.

Therefore,-this panel now serves only as a termination cabinet.

The pressure switches originally located on'an engine gauge board have been removed from the diesel skid-mounted location and installed on a floor-mounted instrument stand separate from~ the skid.

In addition, the air-start and shutdown solenoids have been moved to a second floor mounted stand separate from the skid.

The. connections from the floor stands to the diesel skid are made via flexible hoses and flexible conduits to reduce transfer of' i

, vibration (due to diesel vibration).

The diesel generator skid is supported by its own ' foundation that transfers load directly from elevation 436 to elevation 427 (basement floor).

This load bearing foundation directly below the skid consists of solid reinforced : concrete which extends from the 436 elevation floor down to,.and becomes a part of, the 427 elevation (basement floor). 'The basement floor itself~ rests on caissons embedded in bedrock.

Thus the ' diesel skid vibration transfer is through the foundation below the skid to the caissons.

The new instrument stands are located on elevation 436 floor adjacent to, but not a partiof, the diesel' generator skid.

5411150057 6

PDR ADOCK O db P.

u r.

i

~.

?ou

.M) ' 't --

s.

T

Mr.1 Harold cR. Denton

' Diesel; Generator? Vibration-November.8,;1984 a.

Page #2-The ' equipment that is now being movedL but'which previously.was

' located on the diesel skid, has never experienced any adverse performance effects c.s'a result of' diesel l vibration. ~ However,; by ilocating instrument standsioff the-skid u and? utilizing flexible -

connections' to 'the : stands, the potential L for any equipment -

failure due to operational stress 1vibrationJis1further reduced.

-These modifications are currently-being made=during:the present

~

refueling outage.-. Upon' completion l of these modifications, SCEEG

- will consider that License Condition 2.C.19:for the Virgil C.

Summer Nuclear Station has been satisfied.

If you-have any questions, please advise.-

Very truly yours, 4

/

1 O. W.-Dixon, Jr.

AMM/OWD/gj cc:

V. C.

Summer C. A.

Price T.

C. Nichols, Jr./O. W. Dixon, Jr.

C.

L.

Ligon (NSRC)

E.

H.' Crews,:Jr.

K.

E. Nodland E.

C. Roberts R. A.

Stough W. A. Williams, Jr.

G.

Percival D. A. Nauman C. W. Hehl J.

P..O'Reilly J.

B.

Knotts, Jr.

Group Managers

- H.

G.

Shealy-

- O. S. Bradham NPCF File

.m i

1

\\

(

y"

'-a+

--ew,t 9

y-

>w" y

Me der T%

ge,ee-g g-gp<y myy 9-y gemy-svmpcp-ggb-gywgg,eg + g

,ya-g=4y mg,p

++g=g-gpp ev---

g e y -m-gmy 9 % ** W ye-p y wyg m m9r---W+N9TN