ML20107E252

From kanterella
Jump to navigation Jump to search
Application for Amend to License NPF-29,prohibiting Performance of 24-h EDG Maint Run While Unit in Either Mode 1/2
ML20107E252
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 04/18/1996
From: Hutchinson C
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20107E255 List:
References
GNRO:96-00038, GNRO:96-38, NUDOCS 9604190259
Download: ML20107E252 (15)


Text

r 5'ENTERGY WMe~"*"*"" '

rbrt Gtson. MS 39150 Td 601437 2800 C. R. .%ichinson Vce Pres: Ant OEeravxs Grarx1 Gulf f+1 tar Swxw April 18, 1996 i

U.S. Nuclear Reguletory Commission Mail Station P1-37 j Washington, D.C. 20555 Attention: Document Control Desk Subjec': Grand Gulf Nuclear Station Docket No. 50-416 ,

License No. NPF-29 24 Hour EDG Technical Specifications Change Droposed Amendment to the Operating License (PCOL- 96/05) i GNRO: 96/00038 Gentlemen:

Entergy Operations, Inc. is submitting by this letter a proposed amendment to the  !

Grand Gulf Nuclear Station (GGNS) Operating License. The proposed change to the Technical Specification modifies Note 2 io Sumillance Requirement 3.8.1.14.

Presently, Note 2 prohibits the performance of the 24-hour emergency diesel generator (EDG) maintenance run while the unit is in e ther Mode 1 or 2. The proposed change would remove this estriction thus allowing the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run to be performed during any mode of operation (i.e., Mode 1,2,3,4 or 5).

l The Staff has previously expressed concern about the performance of the 24-hour EDG load test while paralleled to the offsite power systems. This concern, based on the common-mode vulnerability of the offsite and onsite sources during testing, led to restricting the performance of the test during periods when the reactor was shutdown (i.e., Mode 3,4 or 5). Specifically, the Staff was concerned that if a fault or grid disturbance were to occur while an EDG was connected in parallel with the offsite cystems, the availability of the EDG for subsequent emergency operation could be sdversely affected.

Recently, the Staff has approved several licensees' requests (e.g., Pennsylvania Power & Light and Niagara Mohawk Power) for eliminating the Mode 1 and 2 restrictions when performing the 24-hour EDG run. NRC approval has been based on the existence of unique EDG design features and/or special provisions that ensure that paralleled operation of the EDG with offsite sources will not prevent the EDG from performing its assumed safety functions. Attachment 2 provides similar justification for GGNS.

7g 9604190259 DR 96041e '

l ADOCK 05000416 PDR

l 4

April 18, 1996 GNRO-96/00038 Page 2 of 4 While the performance of these surveillance requirements has in the past not affected outage critical path, continued certainty of no future impact is not assured. As outage schedules continue to be optimized, the likelihood that one or all three of these surveillances could adversely impact future outage critical paths

is ever increasing. In addition, the performance of these surveillances is very L

operator intensive thus placing additional strain on a limited resource during refueling outages. Performance of these tests at times other than during refueling outages lessen both the complexity of the outages and the vying for limited operations' resources. For these reasons, Entergy Operations, Inc. believes the approval of the proposed change will result in expected benefits well in excess of

$100,000 over the remaining life of the plant.

Consequenby, the proposed amendment is being submitted as part of the cost beneficiallicensing action (CBLA) program established within the NRR. EOl request that the Staff complete its review and approval of the subject Technical Specifications change no later than September 15,1996, in time to support GGNS's October 1996 refueling outage.

Attachment 2 provides a detailed description of the proposed changes, justification and the No Significant Hazards Considerations. Attachment 3 is a copy of the marke6Hp TS pages.

Based on the guidelines in 10 CFR 50.92, Entergy Operations has concluded that this proposed amendment involves no significant hazards considerations.

Attachment 2 details the basis for this determination.

In accordance with the provisions of 10 CFR 50.4, the signed original of the requested amendment is enclosed.

l Yours truly,

/

RHWKH/

attachment: 1. Affirmation per 10 CFR 50.30

2. Discussion and Justification i
3. Mark-up of Affected Technical Specifications and Bases cc: (See Next Page)

4 April 18, 1996 GNRO-96/00038 Page 3 of 4 cc: . Mr. J. E. Tedrow (w/a)

Mr. R. B. McGehee (w/a)

Mr. N. S. Reynolds (w/a) ,

Mr. H. L. Thomas (w/o)

Mr. J. W. Yelverton (w/a)  !

Mr. J. N. Donohew, Project Manager (w/2)

Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop 13H3 Washington, D.C. 20555

)

Mr. L. J. Callan (w/a)

Regional Administrator l U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington,TX 76011 Dr. Eddie F. Thompson (w/a)

State Health Officer State Board of Health P.O. Box 1700 Jackson, Mississippi 39205 l

l l

4

- , - - +

, Att: chm:nt 1 to GNRO-96/00038

. Pags 1 of 1 BEFORE THE UNITED STATES NUCLEAR REGULATORY COMMISSION LICENSE NO. NPF-29 DOCKET NO. 50-416 IN THE MATTER OF MISSISSIPPI POWER & LIGHT COMPANY and l

SYSTEM ENERGY RESOURCES, INC. L and SOUTH MISSISSIPPI ELECTRIC POWER ASSOCIATION and

( ENTERGY OPERATIONS, INC.

AFFIRMATION 1, C. R. Hutchinson, being duly sworn, state that I am Vice President, Operations GGNS of Entergy Operations, Inc.; that on behalf of Entergy Operations, Inc., System Energy Resources, Inc., and South Mississipp' ectric Power Association I am authorized by Entergy Operations, Inc. to sign and file with the Nuclear Regulatory Commission, this application; that I signed inis application as Vice President, Operations GGNS of Entergy Operations, Inc.; and that the  ;

statements made and the matters set forth therein are true an orr to the est I knowledge, information and belief. -

7 C. R. Hutchinson l STATE OF MISSISSIPPI y IP COUNTY OF OtWBORME- Arm SUBSCRIBED AND S RN TO bpfpre m.e, a Notary Public, in and for the County and State above named, this / day of C4;dJA0 1996.

0 YU Notary Public

$ 8IlE 919I M E'N @$ 6 m ue JfT _COML!!$SION EXPIRES JUNE 16. 1997 swaus.u anaw a6rA,Au, .wv.xT SE2VlcE

l .

Attachm:nt 2 to GNRO-96/00038 Page 1 of 10 l

l GRAND GULF NUCLEAR STATION l 24 HOUR EMERGENCY DIESEL GENERATOR RUN

! DISCUSSION AND JUSTIFICATION 1

i 1

l l

l l

_ _ _ . _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ __. . _ __ ._m Attachm:nt 2 to GNRO-96/00038 Page 2 of 10 A. AFFECTED TECHNICAL SPECIFICATIONS 1

The following Ter.nnical Specification is affected by the proposed change.

)

Surveillance Requirements (SR) 3.8.1.14 AC Source - Operating The proposed Technical Specification and the associated Technical Specification Bases change to be implemented following NRC approval are detailed in Attachment 3.

B. BACKGROUND At Grand Gulf Nuclear Station (GGNS) the Class 1E AC electrical power distribution systems consist of offsite sources (three incoming lines) and onsite sources (three l emergency diesel generators). As requin>d by 10 CFR 50, Appendix A, GDC 17, the design of the AC electrical power system provides independence and redundancy to ensure an available source of power to the Engineered Safety Feature (ESF) systems.

The Class 1E AC distribution system supplies power to three divisional ESF load groups (i.e., Divisions I,11 and lil), with each division powered by an independent Class 1E 4.16 kv ESF bus. Each ESF bus receives power from either offsite sources or a dedicated onsite emergency diesel generator (EDG). During normal operations, the ESF buses are aligned to their preferred offsite sources. In the event that the preferred offsite source is loss or degrades, the affected ESF bus is automatically transferred to an alternate standby onsite source.

Olfsite power is supplied to the GGNS via either two 500 kv lines or one 115 kv line.

From the switchyard three electrically and physically separated circuits provide AC rower to each 4.16 kv ESF bus. The offsite AC electrical power sources are designed and located so as to minimize to the extent practical the likelihood of their simultaneous l failure under operating and postulated accident conditions. A complete description of l the offsite power system may be found in the GGNS's Updated Final Safety Analysis Report (UFSAR) Section 8.2.

The onsite standby power source for each 4.16 kv ESF bus is a dedicated EDG. These standby EDG's (i.e., Divisions I, ll and Ill) auto start fchowing generation of either a loss of coolant accident (LOCA) signal (i.e., low reactor w ater level or high drywell pressure) or an ESF bus degraded or undervoltage signal (refor to Technical Specification 3.3.8.1

- LOP Instrumentation). The automatic transfer of each ESF bus to its standby EDG is initiated QDIX after generation of a bus degraded or undervoltage signal as measured on the 4.16 kv bus. Transfer is accomplished by first opening ths incoming offsite feeder breakers and subsequently closing the EDG feeder breaker when the generator has reached rated speed and voltage. This arrangement lessens the likelihood that the offsite source (i.e., grid) and the onsite sources remain paralleled during periods of degraded grid conditiens.

Attichm:nt 2 to GNRO-96/00038 Page 3 of 10

~

For Divisions I and II, prior to auto connecting the EDG to the ESF bus (i.e., closing EDG output breaker), the breakers connecting the buses to the offsite sources are opened and all bus loads except ESF 480 voit load center feeders are tripped. The same signal that initiates the tripping of the offsite feeder breakers also causes all loads to be stripped from the 4.16 kv bus. Loads are sequenced back onto the bus following closure of the EDG output breaker to the ESF bus, in a predetermined sequence in order to prevent overloading the standby emergency power source. Load shedding and sequencing for Divisions I and ll is discussed in detail in the GGNS's UFSAR Section L 8.3.1.1.3.

For Division lli (High Pressure Core Spray - HPCS) loads are not shed and thus not required to be sequenced back onto the bus. However, the design of the HPCS system ensures that the offsite and onsite source will not continue to operate in a parallel mode following receipt of either a LOCA or LOP signal. If in parallel operation prior to the occurrence of a LOCA signal, the HPCS EDG output breaker will trip open and not be automatically reclosed unless the preferred offsite source of power is loss similar to the l Division I and ll designs. Following the receipt of a LOP signal, the offsite feeder breakers will trip open.

Currently, the GGNS Technical Specification requires that the operability of each EDG be demonstrated every 18 month by operating each EDG for 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> at specific load conditions. In order to achieve the required load conditions, the selected EDG is operated in parallel with offsite sources. Because of the perceived vulnerability that exists while paralleled to an offsite source, the current Technical Specification prohibits these tests from being performed while the unit is in Mode 1 or 2. The Staff's concem, as expressed in li, formation Notice 84-69, is that a possible fault on the offsite system l

could cause lockout of the ESF bus or trip the EDG itself. In such case the ability of the unit to respond to an emergency could be reduced.1 C. PROPOSED TS CHANGES l The proposed change to the Technical Specification is to modify Note 2 to Surveillance 3.8.1.14. Presently Note 2 prohibits the performance of the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> diesel maintenance i run while the unit is in either Mode 1 or 2. The proposed change would remove this I

restriction thus allowing the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run to be performed during any mode of operation (i.e., Modes 1,2,3,4 or 5).

The second part of Note 2 would remain providing clarification that credit may be taken for unplanned events to satisfy the requirements of 3.8.1.14.

1 The Technical Specification Bases denotes the reason for Note 2 as being a concern for potentially tripping the plant if the surveillance were performed during Modes 1 and 2. While performance of this surveillance could present a potential challenge to the continued operation of the unit, it doesn't present a

greater challenge than many other surveillances performed on a more frequent basis (e.g., SR 3.8.1.3).

l The decision of whether to perform this surveillance during power operation should be made just as with any other surveillance that presents a potential trip of the unit. It is rather EOl's opinion that the more

important concems with SR 3.8.1.14 are as expressed in IN 84-69 and not whether performance of the

[

surveillance represents a challenge to continued steady state operation.

  • \

- )

Attachm:nt 2 to GNRO-96/00038 Page 4 of 10 D. JUSTlFICATION The Staff previously expressed concern about the performance of the 24-hour EDG load test while paralleled to the offsite power system. This concern, which is based on the common-mode vulnerability of the offsite and onsite sources during the test duration, led to restricting the performance of the test during periods when the reactor was shutdown (i.e., Modes 3,4 or 5).

The specific Staff concem was that if a fault or grid disturbance were to occur while an EDG was connected in parallel with the offsite system, the availability of the EDG for subsequent emergency operation could be effected. Specifically, the EDG or its generator breaker could trip and thus require local operator action to restore. In these instances, the response of the ESF systems could be slower than assumed in the supporting accident analyses.

Recently, the Staff has approved several licensees' requests for eliminating the Mode 1 and 2 restrictions when performing the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> EDG runs. This approval has been based on the existence of unique EDG design features and/or special provisions. These features and/or special provisions must ensure that paralleled operation of the EDG with offsite sources will not prevent the EDG from performir.g its assumed safety functions.

Of particuiar interest is the response of a paralleled EDG to a LOCA signal, a loss of i offsite power signal or coincident signais. Each un!que situation is discussed in additional details below.

RESPONSE TO LOCA The first action after generation of a LOCA signal is the shedding of allloads, except l feeders to 480 voit load centers, off the ESF buses (Divisions I and ll only). Loads are i sequenced back onto the ESF bus once appropriate bus voltage and frequency is  !

confirmed. The timing of the sequencing is the same regardless of whether the ESF i buses are energized from offsite er onsite sources. This makes the LOCA sequencing a function solely of when ESF bus voltage becomes available without memory of past conditions or knowledge of pres snt power source. i Regardless of whether the EDG's are in parallel operation or in its normal standby mode, the generation of a LOCA signal is an emergency start signal for all three of the EDG's. In either case (i.e., paralleled or normal standby) an emergency start signal automatically bypasses selected EDG trips. For Divisions I and 11 a LOCA signal retains only three EDG trips active - engine overspeed, generator differential and low lube oil pressure. For Division lli following a LOCA signal two EDG trips remain active - engine overspeed and generator differential. Interlocks to the EDG breakers and parallel circuits cause the EDG to automatically reset to ready-to-load operation if a LOCA signal is received during operation in the test mode. Ready-to-load operation is defined as the EDG running at rated speed and voltage with the EDG output breaker open. If offsite power is available, the EDG will continue to run in the ready-to-load condition.

Of significance is that all three EDG's response to a LOCA signal as an emergency start thus overriding the test start signal and removing selected engine / generator trips from w

l Attnchmsnt 2 to GNRO-96/00038 Page 5 of 10 ,

l the active trip circuitry. Continued operation of the EDG's in parallel with offsite sources j is automatically terminated following receipt of a valid LOCA signal thus preventing l subsequent failure of offsite sources from affecting performance of the EDG's safety i function.

RESPONSE TO LOCA COINCIDENT WITH LOSS OF OFFSITE POWER l

in accordance with the GGNS UFSAR Chapter 15 analysis, the design basis accident l (DBA)is the occurrence of a LOCA coincident with a LOP. Per the assumptions of this analysis, ESF systems are actuated following receipt of the LOCA signal. Thus the event is initiated by the occurrence of the LOCA. The simultaneous LOP is assumed i only to ensure a bounding case for the assumed subsequent single failure (i.e., loss of one ESF division). In other words, the UFSAR makes no attempt to analyze all possible permutation of event sequences but rather assumes a LOCA to be the most credible bounding event.

Consistent with the Chapter 15 analysis any EDG test would be terminated by the  !

! . receipt of the LOCA signal. In this instance, the LOCA signal takes precedence .

resulting in system response as previously described to the receipt of a LOCA signal l l

singularly. However; in this case since offsite power is lost concurrent with the LOCA signal, the EDG will automatically be transferred back onto the ESF bus following the  ;

tripping of offsite feeder breakers. The bus, once isolated from the offsite grid, would be '

(

reenergized by the EDG output breaker reciosing, in this instance, the reenergization of the ESF bus will actually be slightly faster than the assumed UFSAR time since the EDG would already be at rated speed and voltage and thus need only have its output breaker )

reciosed to energize the bus.

It should be noted that a review has been performed that demonstrates that the EDG's will not trip or be rendered inoperable with a concurrent LOP /LOCA signal. The review demonstrates that the EDG's are designed to withstand the stresses generated by any l credible offsite fault. Also, the review demonstrates that paralleled operation of the EDG's will be terminated prior to any credible fault causing the EDG to trip or be locked-out.

RESPONSE TO LOSS OF OFFSITE POWER Each 4.16 kv ESF bus has its own independent loss of power (LOP) instrumentation and associated trip logic. The voltage for Division 1,11 and lit buses is monitored 6.t two

! levels, which may be considered as two different undervoltage functions: loss of voltage and degraded voltage. See Technical Specifications 3.3.8.1 (LOP instrumentation) for actual setpoints.

Actuation of the LOP instrumentation results in an automatic start signal for its associated EDG. For Division 1 and 2, prior to connecting the EDG to its appropriate

bus, allloads are shed except feeders to 480 voit load centers. Provisions are built into

! the automatic sequences to recognize a grid undervoltage condition and to automatically i place the EDG on the bus after tripping the incoming offsite source feeder breaker.

j Should a LOP condition occur while the EDG is being operated in parallel, the incoming l

. l Attichmsnt 2 to GNRO-96/00038 Page 6 of 10 offsite feeder breakers and EDG breakers (Div. I and ll only) would open and the EDG would switch from parallel operation to isochronous mode picking up the loads on the bus.

Unlike Division I and ll, Division lli does not have an automatic load shedding and sequencing. However; as with Division I and il, Division ill does have undervoltage l protection that activates to open incoming feeder breakers thus separating the onsite source from a degraded grid condition.

For all three EDG's, the auto start due to the actuation of LOP instrumentation is not an emergency start and thus all normal EDG protective trips remain active (see sections 8.3.1.1.4.1 and 8.3.1.1.4.2.10 of the GGNS UFSAR). While the presence of a loss of preferred power signal may be indicative of either a failure of the offsite power source (s) or some type of fault on the local ESF bus, it is not indicative of the occurrence of a

design basis event requiring emergency (i.e., minimal protective trips) EDG response.

This design was reviewed and approved by the Staff as documented in their Safety l Evaluation Report dated September 1981, Section 8.3.1.

In accordance with the GGNS system design, it is possible that an EDG started as a l result of a LOP signal could trip due to some engine / generator protective trip ( as previously noted protective trips are not bypassed due to only a LOP signal), it is also possible that this trip could result in the actuation of a generator lockout. In this l instance, local operator action would be required (i.e., resetting lockout) prior to the EDG restarting and/or resequencing onto the bus following a subsequent signal (either emergency or non-emergency). For emergency starts (LOCA or emergency manual),

local operator action would only be required if a generator lockout protective trip had previously actuated.

l

One of the concems expressed by the Staff has been that a possible fault on the offsite system could cause lockout of the ESF bus or trip the EDG itself and as a result delay the unit's response to an emergency condition. While it is possible to postulate that l some type of grid or bus fault could result in the actuation of an EDG protective
trip / lockout, it is EOl's opinion that any delay in EDG response time would be considered i acceptable due to
2 1

! 1. the less critical nature of EDG start / load times for LOP, i f- 2. the low probability of subsequent events occurring following the initial LOP and I

3. procedural requirements that would tend to minimize EDG response times. j 2in proposing the subject Technical Specification change request it was not EOl's intention to do ar l exhaustive review of relay actuation for an almost unlimited number of possible sequence of event s and/or j scenarios. Rather the approach taken was to confirm the possibility that an EDG lockout could occur.  ;

Then assuming as worst case that the lockout actuated determine whether this was an acceptable i condition. Furthermore, EOl did not attempt to quantify the frequency with which such an event could  !

occur (i.e., actuation of lockout relay). However, it is EOl's opinion that the likelihood of such an event i i occurring is low based on our past experience of operating in a similar configuration when performing

( surveillance requirement 3.8.1.3 on at least a monthly basis.

l l

(

1 e

  • Attachmtnt 2 to GNRO-96/00038 Page 7 of 10 I A LOP, unlike a LOCA, does not present an immediate challenge to the fuel cladding i integrity, reactor water level control or to containment parameters as demonstrated by l the bounding 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> Station Blackout coping analysis contained in GGNS's UFSAR 4

Appendix 8-A. Given that the only occurrence has been either the loss of offsite power

, or an individual bus fault, it is not necessary that the EDG respond in the same manner j as for the Chapter 15 DBA. In this scenario, there would exist ample time for the operator to recover the EDG if plant conditions warranted such action.

i In addition, the probability of a subsequent event occurring (e.g., LOCA ) within a i relatively short time period following the initial LOP signal would be extremely low. In

!- fact EOl has determined based on results from the GGNS IPE that the probability of

having a LOP and a LOCA within a given 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> period is 1.6E-8/yr. ANSI /ANS 52.1-l 1983 directs that events of frequency <1E-6/yr, on a best estimate basis, need not be l t

considered for design. It is therefore EOl's opinion that to assume a coincident l LOP /LOCA occurring within the time frame of the test is not a credible event.

4 Finally, any potential delay in EDG response time would be minimized by the way in  !

which the test is performed. Per procedural requirements, prior to beginning the test j suitable communications between the Control Room and the local EDG Room must be i
established. Also during the first two hours of the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run, the EDG must be closely
monitored by collecting local data every half an hour. Following the first two hours of

! operation this local data is collected hourly. These procedural requirements help ensure j timely local operator response to any abnormal EDG conditions and subsequent

recovery from any such event.

l

} The discussion of this possible scenario is included for completeness only, it has in fact i very little relevance to the acceptability of the proposed Technical Specification change.

The testing of an EDG, regardless of the mode of operation in which the test is performed, does not create or increase the possibility of experiencing a fault on the j offsite system. In fact, given the existing EDG design one could postulate a similar

scenario regardless of the Mode during which the test was being performed or even if l the EDG were in its normal standby mode. Of greater importance is the fact that there
exist design features that automatically terminate continued paralleled operation of I offsite and onsite sources if a LOP should occur during performance of the surveillance.  !
These features prevent the testing of an EDG from introducing a new or different type of j failure.

ADDITIONAL CONSIDERATIONS l In addition to the existing system design features, there are other factors that should be j considered when evaluating the acceptability of this proposed Technical Specification

change. In particular, there are other Technical Specification Surveillance j Requirements that are of interest as it relates to the proposed change.

1' Current surveillance testing required by SR 3.8.1.3 results in the EDG's being operated

{ in parallel operation with the grid on at least a monthly basis. Therefore, the requested Technical Specification change will not result in a new or different configuration of any 1

Attachmtnt 2 to GNRO-96/00038 Page 8 of 10 system. The only change will be the time spent in this configuration during Modes 1 or 2 will increase over a given 18 month period.

I I The ability of each EDG to survive a load reject without tripping is verified every 18 l months per Technical Specifications 3.8.1.10. This surveillance would simulate an EDG l operated in parallel with the grid following receipt of either a LOCA or LOP signal and l having its output breaker trip open separating it from paralleled operation with the grid.

I This surveillance will remain and thus continue to confirm the ability of the EDG's to survive a totalload reject.

l The other Technical Specification Surveillance of particular interest is 3.8.1.17. This surveillance requirement demonstrates on an 18 month frequency the capability of the l EDG to revert to the ready-to-load status following a LOCA signal while operating in l parallel test mode. Demonstration of the test mode override ensures that the EDG l availability under accident conditions is not compromised as a result of testing.

l l Finally there are some special administrative provisions that may be taken to l appropriately manage any risk presented by performing the EDG 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test during l Modes 1 and 2:

1. Only one EDG will be tested in parallel to the offsite grid in accordance with SR 3.8.1.14 at a time.

l 2. Appropriate precautions / limitations will be provided that cautions against conducting the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test during periods of severe weather, unstable offsite grid conditions or maintenance and test conditions that have an adverse effect on the test.

l 3. No additional maintenance or testing will be performed or planned to be performed on required safety systems, subsystems, trains, components and devices that depend on the remaining EDG's as sources of emergency power.

Each of the above precautions / limitations will be included in appropriate procedural guidance following approval of this Technical Specification change request by the Staff and prior to performing the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run with the unit in either Mode 1 or 2.

E. CONCLUSION l

In conclusion, the performance of the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> diesel maintena'nce runs while the unit is l In Mode 1 or 2 will not adversely affect the ability of either of the three EDG's to response to design basis events per the UFSAR. In all cases following generation of either a LOCA or LOP signal, occurring individually or coincidentally, the system design will automatically terminate continued paralleled operation with offsite sources thus preventing this mode of operation from introducing a new or different failure from those i previously assumed in the accident analysis. Since the response of an EDG in testing is l essentially identical to that of a EDG in normal standby, the unit will continue to satisfy l the single failure criteria and remains within the assumed design basis during the l performance of the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> EDG test regardless of the unit's mode of operation.

_ _ _ _ _ . . _ _ . . _ _ _ _ _ _ _ _ . . _ _ _ _ _ . ~ . . _ _ _ . _ _ _ - _ . ____ _ __

Att chm:nt 2 to GNRO-96/00038 Page 9 of 10 F. SIGNIFICANT HAZARDS CONSIDERATION Entergy Operations, Inc. proposes to change the current Grand Gulf Nuclear Station Technical Specifications. The specific change is to modify note 2 to Surveillance 3.8.1.14. Presently, this note prohibits the performance of the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> diesel maintenance run while the unit is in either Mode 1 or 2. The proposed change would remove this restriction thus allowing the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> run to be performed during any mode of operation (i.e., modes 1,2,3,4 or 5).

The Commission has provided standards for determining whether a no significant hazards considerations exists as stated in 10 CFR 50.92 (c). A proposed amendment to j

an operating license involves no significant hazards consideration if operation of the facility in accordance with the proposed amendment would not: (1) involve a significant increase in the probability or consequences of an accident previously evaluated; (2) 1 create the possibility of a new or different kind of accident from any accident previously l evaluated; or (3) involve a significant reduction in a margin of safety. I Entergy Operations, Inc. has evaluated the no significant hazards consideration in its request for this license amendment and determined that no significant hazards considerations results from this change. In accordance with 10 CFR 50.91(a), Entergy Operations, Inc. is providing the analysis of the proposed amendment against the three standards in 10 CFR 50.92(c). A description of the no significant hazards consideration determination follows:

1. The proposed change does not significantly increase the probability or consequences of an accident previously evaluated.

The GGNS UFSAR assumes that the AC electrical po'wer sources are designed to provide sufficient capacity, capability, redundancy and reli: ability to ensure that the fuel, reactor coolant system and containment design limits are not exceeded during an assumed design basis event. Specifically, the UFSAR assumes that the onsite EDG's provide emergency power in the event offsite power is loss to either one or all three ESF buses. In the event of a loss of preferred power, the ESF electrical loads are automatically connected to the ,

EDG's in sufficient time to provide for safe reactor shutdown and to mitigate the  !

consequences of a design basis accident such as a LOCA.

The proposed change to permit the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> testing of the EDG's during power operation does not increase the chances or consequences of any previously evaluated accident. The capability of the EDG's to supply power in a timely 1 manner will not be compromised by permitting performance of EDG testing l during periods of power operation. Design features of the EDG's and electrical systems ensures that if a LOCA or LOP signal, either individually or concurrently, should occur during testing that the EDG would be returned to its ready-to-load operation (i.e., EDG running at rated speed and voltage separated from the offsite sources) or separately connected to the ESF bus providing ESF loads. As such, an EDG being tested is considered to be

l Attrchm:nt 2 to GNRO-96/00038 l Page 10 of 10 Operable and fully capable of meeting its intended design function. Additionally, the testing of an EDG is not a precursor to any previously evaluated accidents.

Therefore, the proposed change allowing testing of EDG's during power operation will not significantly increase the probability or consequences of an accident previously evaluated.

II. The proposed change does not create the possibility of a new or different kind of accident from any accident previously evaluated.

j As previously discussed, the proposed change to permit the performance of

' EDG testing during power operation will not affect the operation of any system or alter any system's response to previously evaluated design basis events. The  !

1 EDG's will automatically transfer from the test configuration to the ready-to-load configuration following receipt of a valid signal (i.e., LOCA or LOP). In the ready-i to-load configuration, the EDG will be running at rated speed and vcitage separated from the offsite source capable of automatically supplying powe.r to the ESF buses in the event that preferred power is actually loss.

Surveillance Requirement 3.8.1.17 demonstrates that the EDG will automatically l override the test mode following generation of a LOCA signal. In addition the 4

ability of the EDG's to survive a full load reject is verified by the performance of surveillance requirement 3.8.1.10. These existing surveillance requirements along with system design features ensures that the performance of EDG testing during power operation will not create the possibility of a new or different kind of accident from any previously evaluated.

Ill. The proposed change does not involve a significant reduction in a margin of safety.

The AC electrical power sources are designed to provide sufficient capacity, capabi:ity, redundancy, and reliability to ensure the availability of necessary  ;

power to ESF systems so that the fuel, reactor coolant system and containment design limits are not exceeded. Specifically, the EDG's must be capable of automatically providing power to ESF loads in sufficient time to provide for safe reactor shutdown and to mitigate the consequences of a design basis accident in the event of a loss of preferred power.

Testing of EDG's during power operation will not affect the availability or operation of any offsite source of power. In addition, the EDG being tested remains capable of meeting its intended design functions. Therefore the proposed change to the Technical Specification Surveillance Requirement 3.8.1.14 will not result in a reduction in a margin of safety.

- j Attachm:nt 3 to GNRO-96/00038  ;

l i

l l

1 l

l l

l l

MARK-UP OF AFFECTED  :

I TECHNICAL SPECIFICATIONS AND BASES 1

l GRAND GULF NUCLEAR STATION l

1