OPERATING DATA REPORT DOCKET NO. 050-237-o DATE February 1, 1985

~

COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920 0PERATING STATUS NOTES 1.

Unit Name:

Dresden II 2.

Reporting Period:

January, 1985 3

Licensed Thermal Power (MWt):

2 527 4.

Nameplate Rating (Gross MWe):

828 5

Design Electrical Rating (Net MWe): 794 6.

Maximum Dependable Capacity (Gross MWe):

812

~ ~ ~ ~ ~ 8. ~ Maximum Dependable Capacity (Net MWe):

772 7.

If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:

N/A fLf*%p?K~l:.?ys.:,pn m.t A w +;-a.* :.et.v v.wa+-n::w <:a::s

.H 1.ne:!.-~a

,~

s n:

9 Power Level to Which Resi;ricted, if 'Any (Net MWe): N/A 10.

Reasons For Restrictions, if Any: N/A v

This Month Yr-to-Date Cumul.ative.

11. Hours in Reporting Period 74A 744 136.048
12. Number of Hours Reactor Was Critical 0

0 98.735.9

~ ~ ~ "13.

Reactor Reserve Shutdown Hours 0

0 0

~ ~~ ~ ~ 14. Hours Generator On-Line 0

0 97,309.8

~ ~ 15 E Unit Reserve Shutdown Hours 0

0 0

16.

Gross Thermal Energy Generated (MWH) 0 0

191,338,058 17 Gross Electrical Energy Generated (MWH) 0 0

61,221,341 18.

Net Electrical Energy Generated.(MWH)

-2.477

-2.477 57.846.149

~~ ~19 Unit Service Factor 0

0 71.5 20.

Unit Availability Factor 0

0 71.5 21.

Unit Capacity Factor -(Using MDC Net) 0 0

55.I 22.

Unit Capacity Factor (Using DER Net) 0 0

53.6 23 Unit Forced Outage Rate 0

0 11.2

~ ~ 2 4.'

Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

l

, Mid-May for snubber inspections.

~_

25.

If Shut Down At End of Report Period, Estimated Date of Startup: March 13, 1985, -

.y ;.., s,l *.,.. '.:.*.:r....

.r-u

    • .:..l

"..'*s'

'~

e~....'...':s...'.*

.:s uo9 9

.D s e Ift

OPERATING DATA REPORT DOCKET NO. 050-249 DATE February 1, 1985 COMPLETED By D. C. M:txwell TELEPHONE 815/942-2920 OPERATING STATUS NOTES 1.

Unit Name: Dresden III 2.

Reporting Period:

January. 1985 3

Licensed Thermal Power (MWt):

2.527 4.

Nameplate Rating (Gross MWe):

82R 5.

Design Electrical Rating (Net MWe): 794 6.

Maximum Dependable Capacity (Gross MWe): 812 7.

Maximum Dependable Capacity (Net NWe):

773 8.

If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:

N/A

}.Qd$tf%'5rNi~:S %.':?'w n;O a v.@:*Y.'?~.*:.~Y 'n'*M-

'
:t ! ^

'o W

s' 9.

Power Level to Which Restricted, if Any (Net MWe): N/A 10.

Reasons For Restrictions, if Any: N/A This Month Yr-to-Date Cumulativo 11.

Hours in Reporting Period 744 744 118,633 12.

Number of Hours Reactor Was Critical 675.6 675.

90,553.6

'- - ~13 Reactor Reserve Shutdown Hours 0

0 0

14.

Hours Generator On-Line 645.3 645.

83,817.4 15.

Unit Reserve Shutdown Hours 0

0 0

16.

Gross Thurmal Energy Generated (MWH)

I,510,336 1,510,336 168,567,359 17.

Gross Electrical Energy Generated (MWH) 487.545 487.545 54,694,874 18.

Net Electrical Energy Generated.(HWH) 469.814 469,874 51,806,104 19 Unit Service Factor 86.7 86.7 70.7 20.

Unit Availability Factor 86.7 86.7 70.7

~

21.

Unit Capacity Factor (Using MDC Net) 81.7 81.7 56.5 22.

Unit Capacity Factor (Using DER Net) 79.5 81.7 56.5 23.

Unit Forced Outage Rate I3.3 13.3 12.7 t

- ^ 2 4.~

Shutdowns Scheduled Over Next 6 Months (Type. Date, and Duration of Each):

r If Shut Down At End Of Report Period, Estimated Date of Startup:

25.

..** *s',

'"d

- :.s

.... ;. g. :.

.... s

....e.,

og

'o 8

e

~

r.

c AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-237

~ UNIT II DATE February 1, 1985 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920, Ext. 489 MONTH January. 1985 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net).

(MWe-Net)

I O

17 0

2 0

18 0

3 0

19 0

4 0

20 0

Q

'5 0

21 0

6 0

22 0'

7 0

23 0

-8 0

24 0

0 9

0

-25 10 0

26 0

11 0

27 0

12

'o 28 0-13 O

29 0

-14' O

30 0

15 0

.31 0

L 16 0

l-o I

l.

l.

t h ~.

AVERAGE DAILY UNIT' POWER LEVEL

~?

DOCKET NO. 050-249 UNIT III DATE ' February 1,1985 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920, Ext. 489 MONTH 3.nnorv. 1985 DAY

-AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(MWe-Net) 1 788 17 54 5 2

786 18 653

.3 790 19 735

.4 794 20 711

, ]-

5 785 21 727 6

753 22 689 7

780 23 714 8

788 24 715 9

793 25 705

)

- 10 789 26 736 11 775 27 626 12 16 28 703 13 0-29 727

~

14 0

30-759 0

15 31 774 16-331 B

C0FDf0NWEALTH EDISON COMPANY I DA 0

MONTH OF JANUARY. 1985 HOUR MAXIMUM DAILY LOAD DAY ENDING KW 1

1000 824.800 2

1100 822,300 3

1000-823,400 4

1500 823,200 5

2000 823,800 6

1600 817,000 7

1500 817,700 8

1600 824,500 9

1000 825,200 10 0500 825,400 11 0600 825,700 "O

12 0100 722,200 13 0

0 14 15 O

t 16 2400 492,400 17 1900 621,600 18 2400 764.300 19 1000 793,100 20 2200 751,000 i

21 1600

'769,300 22 2l00 759,700 0100 757,200 23 24 2400 742,900 l

25 1500

-743,900 26 2100 780,900 27 0100 727,800~

28 1600 760,800 29 2400 760,400 30 1300 800,900 31 0600 820,300 c

3 DOCKET NO. 050-237 UNIT NAME Dresden II UNIT SHUTDOWNS.AND POWER REDUCTIONS DATE February 1,.1985 COMPLETED BY D. C. Maxwell TELEPHONE (815) 942-2920 REPORT MONTH JANUARY. 1985 IETHOD OF LICENSEE CAUSE & CORRECTIVE NO.

DATE' TYPEI DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS)

DOWN REACTOR 3 REPORT F CODE 4 CODE 5 PREVENT RECURRENCE 5

84-10-05 S

744 C

1 Refueling outage.

1 2

3

.F:

Forced Reason:

4 Method:

Exhibit G-Instructions for 8: Scheduled A-Equipment Failure.(Explain) 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3--Automatic Scram Event Report (

) File D-Regulatory Restriction 4-Other (Explain)

(NUREC-0161)

E-Operator Training &-License Examination F-Administrative i

-GM)perational Error j

H-Other (Explain)

DOCKET NO. 050-249

- UNIT NAME Dresdan III UNIT SHUTDOWNS AND POWER REDUCTIONS DATE February 1, 1985 m

COMPLETED BY D. C. Maxwell TELEPHONE (815) 942-2920 REPORT HDNTH JANUARY, 1985 METHOD OF LICENSEE CAUSE & CORRECTIVE 10 0 DATE' TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS)

DOWN REACTOR 3 REPORT-F CODE 4 CODES PREVENT RECURRENCE I

85-01-12 F

98.7 A

3 85-001-0 Replaced defective turbine oil trip solenoid valve.

1.

2 3

4 F: Forced Reason:

Method:

Exhibit G-Instructions for S: Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3 -Automatic Scram Event Report (

) File D-Regulatory Restriction 4-Other (Explain)

(NUREC-0161)

E-Operator Training & License Examination F-Administrative 3

G-Operational Error H-Other-(Explain) e

...... q

_-u.-

^'

DRESDEN UNIT !

~

SAFETY RELATED HAINTENANCE-~- JANUARY, 1985-

^

NATURE OF LER OR OUTAGE ELFUNGION

-EQUIPMENT MAINTENANCE.

NUMBER CAUSE RESULT CORRECTIVE ACTION R2fual Grapple Preventive W.R. #37424~

N/A N/A Reset breaker and tested grapple.

'"A".Rx Recire.

Preventive W.R. #38901 N/A N/A Temporarily plugged drains on ID recire.

.PP. Bowl Drain pp. bowl drain.

t v

I

W 5-EE DRESDEN UNIT 2

SAFETY RELATED MAINTENANCE - JANUARY, 1985 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Refuel Plat-Preventive W.R. #38325 N/A N/A Inspected, checked oil levels, and f rm greased refuel platform.

Mottr Operated Modification W.R.

N/A N/A Relamped local control station with Vc.lve #MO #38494 230 volt light bulbs.

2301-10 local Mot 1r Operated Valve Sta.

24/48V Battery Preventive W.R. #38725 N/A N/A Adjusted float and equalizer on charger.

Refueling Preventive W.R. #39365 N/A N/A Adjusted hoist loading limit.

Int::rlocks ECCS Jockey PP Corrective W.R. #35454 N/A N/A Repacked coupling.

C1ttla Chute Preventive W.R. #35465 N/A N/A Removed and replaced cattle chute.

Turbine Bldg.

Corrective W.R. #38579 N/A N/A Found broken wire at lower magnet.

to Rx Bldg.

Reconnected wire.

Intnrlock A Rx Bldg.

Corrective W.R. #39146 N/A N/A Replaced sensor converter and calibrated.

Vint M:nitor, EPN #2-1705-21 Refuel Plat-Corrective W.R. #36960 N/A N/A Found cable splices. Removed old connec-fzrm tors and replaced with new ones.

U2 250 VDC Corrective W.R. #39060 N/A N/A Adjusted voltage to proper setting which Batt ry cleared up alarm problem.

Charg;r

(

DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - JANUARY, 1985 MALFUNCTION NATURE OF LER OR OUTAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORhECTIVE ACTION HFA Relay Preventive W.R. #37415 N/A N/A Rebuilt relay.

590-101A Inst. Line Preventive W.R. #39122 N/A N/A Bench tested instrument line flow check Flow Check valve #2-263-2-19B.

Valve, EPN

  1. 2-263 19B SRM 21 Corrective W.R. #38179 N/A N/A Reconnected SRM 21 monitor leads.

2B Main Steam Corrective W.R. #38370 N/A N/A Replaced relays on 2B main steam line rad.

Line Rad.

monitor.

Monitcr

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - JANUARY, 1985 NATURE OF LER OR OUTAGE M'

NCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U3 CRD's Preventive & Corrective N/A N/A Rebuilt CRD's recoved from Unit 3 during v_1u=e I and 2 W.R. #30240 its refueling outage.

Loc: 1 Operator Corrective W.R. #35629 N/A N/A Relamped local control station with Indic:. tion for 230 volt bulbs.

MO-3-2301-35 HFA Relay 590-Corrective W.R. #37587 N/A N/A Replaced coil and adjusted relay.

IL7G HFA Relay 595-Corrective W.R. #38205 N/A N/A Replaced coil and adjusted relay.

103C HFA Relay 590-Corrective W.R. #37505 N/A N/A Replaced coil and adjusted relay.

106C HPCI Room Preventive W.R. #38697 N/A N/A Replaced belts.

Cool'r LPCI Full Flow Corrective W.R. #38900 N/A N/A Tightened bolts of cover on operator.

T it Vclve "A" ATWS Preventive W.R. #34966 N/A N/A Replaced ATWS inverter cooling fan.

Invert':: r Electro =atic Corrective W.R. #38662 N/A N/A Replaced limit switch 3-203-3C.

VElve 3-203-3C Accus. 50-23, Corrective W.R. #33620 N/A N/A Replaced i13 valve, cut out old one and EPN #3-0305-welded in new one.

113 D3 Fissel Modification W.R.

N/A N/A Replaced LWS 3-6600 switch to a ACW 5548.

Generator Low

  1. 36468 Calibrated and tested.

Water Pres-surt EPN

  1. LWS 3-6600

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - JANUARY, 1985 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NLMBER CAUSE RESJLT CORRECTIVE ACTION LPRM 08-33A Preventive W.R. #37588 N/A N/A Changed LPRM circuit board.

Reland Wire Corrective W.R. #38993 N/A N/A Relanded wire BJ-l for fuse 590-709A.

for Fuse 590-709A Local Operator Corrective W.R. #38630 N/A N/A Relamped local control station with 230 RMt Indication volt bulbs.

far MO-3-230l-6 cr 9 Head Spray Corrective W.R. #34985 N/A N/A Replaced one light socket and 2 bulbs.

Locol valve Indicator for MO-3-205-2-4 Accu =ulator Corrective W.R. #39321 N/A N/A Replaced accumulator.

N-13 (50-51)

MO-3-202-7A Corrective W.R. #29171 N/A N/A Installed and wired new limitorque operator.

Scoop Tube Corrective W.R. #38581 N/A N/A Reset stops on the recirculation pp.

Mechanical run out limits.

Stop Setting IRM #12. EPN Corrective W.R. #37902 N/A N/A Recalibrated IRM # 12 per procedure.

  1. RM3-950-7C 3B LPCI Heat Corrective W.R. #38903 N/A N/A Replaced micro switch and recalibrated Exchanger Low 3B LPCI heat exchanger Dp alarm.

DP A1: r:::

UNIQUE REPORTING REQUIREMENTS MAIN STEAM RELIEF VALVE OPERATIONS Relief valve operations during the reporting period are summarized in the following table. The table includes information as to which relief valve was actuated, how it was actuated, and the circumstances resulting in its actuation.

Valves Description Unit Reporting Period Actuated Actuations Conditions of Events 2

01-01-85 to 01-31-85 None (4 safety / relief valves were replaced during the refueling outage and will be tested in February of 1985.)

3 01-01-85 to 01-31-85 None

SUMHARY OF OPERATING EXPERIENCE UNIT TWO JANUARY, 1985 01-01 to 01-31 Refueling outage activities continued throughout the entire period. The unit is presently scheduled to start-up in mid-March, 1985. Major work includes:

- Local Leak Rate Tests

- ISI Inspections

- ILRT Preparation

- Normal Pump (s) and Valve (s) Maintenance

- Snubber Replacements

- Clean-up Pipe Replacement

e SUMHARY OF OPERATING EXPERIENCE UNIT THREE JANUARY, 1985 01-01 to 01-14 Unit 3 entered the month operating at a level of 815 MWe and operated until January 12th, at 0101 when a Rx scram and turbine trip occurted because of the malfunction of the o'.1 trip solenoid valve during turbine weekly testing whirn caused a turbine trip on a false overspeed trip signal and a Rx scram.

01-14 to 01-31 The Rx was brought critical ou January 14th at 2125 and the turbine was placed on system January 16th at 0345.

The unit operated continuously during the remainder of the month (with notaal power reductions for weekend surveillances) reaching a power level of 819 MWe with a capacity factor of 78.65% and an availability of 86.73%.

1

F f'N Commonwealth Edison

/

) Dresden Nucle r Power St tion RA#1 k

] Morris, tilinois 60450

'As/

Telephone 815/942-2920

)

l February 1, 1985 DJS LTR: 85-148 Director, Office of Inspection and Enforcement United States Nuclear Regulatory Commission Washington, DC 20555 Attention: Document Control Desk

Dear Sir:

Enclosed, please find Dresden Station's operating data for last month. This information is supplied to your office per the instruc-tions set forth in Regulatory Guide 1.16.

Sincerely, b

M N D. J. Scott i

Station Superintendent Dresden Nuclear Power Station DJS:DCM:hjb Enclosure cc: Region III, Regulatory Operations, U.S. NRC Chief, Division Nuclear Safety, State of IL U.S. NRC, Document Management Branch Nuclear Licensing Administrator Nuc. Sta. Div. Vice Pres.

Manager, Tech. Serv. Nuc. Sta.

Tech. Staff AE On-Site NRC Inspector Sta. Nuc. Eng. Dept.

Comptroller's Office PIP Coordinator INP0 Records Center File /NRC Op. Data File / Numerical V