g NUCLEAR REGULATORY COMMISSION UNITED STATES

j WASHINGTON, D. C. 20556 f.

~'

DUKE POWER COMPANY

. DOCKET NO. 50-369 I

McGUIRE NUCtEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 38 License No. NPF-9

1. _ The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendment to the McGuire Nuclear Station, Unit 1 (the facility) Facility O Power Company (licensee) perating License No. NPF-9 filed by the Duke dated August 31, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the C'ommission's regulations as set forth in 10 CFR

. Chapter I; B.

The facility will operate in conformity with the application, as amended, the provisions of the A~t, and the regulations of the c

Commission; C."

There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and l

safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations set forth in 10 CFR i

Chapter I; D.

The issuance of this license amendment will not be inimical to the common defense and security or to the health and safety of the public; E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachments to this license amendment and paragraph 2~.C.(2) of Facility Operating License No. NPF-9 is hereby amended to read as follows:

i (2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 38, are hereby incorporated into this license.

l 8502200421 850201 PDR ADOCK 05000369 p

PDR a

v,3y..,

._,,.,_.,..-w.r,-,y

,.,g,

,,.,,.m..,.,.~,

yew,

,_.m,,e r w e e,_

,cm_,,_,_r,,w,

,.n.

mm.,,,,%,,,

,e,m,-

-, -,,..,.,, -.e,e----e

The. licensee shall operate the facility in accordance with the Tech-nical Specifications and the Environmental Protection Plan.

3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COMISSION NW ne Elino'r G. Adensam, Chief

~/, y Licensing Branch No. 4 Division of Licensing

Attachment:

Technical Specification Changes Date of Issuance:

February 1, 1985 6g e e

a 0

e i

[m2 Etc 6

o

-UNITED STATES g

8 NUCLEAR REGULATORY COMMISSION o

h WASHINGTON. D. C. 20555

/

DUKE POWER COMPANY

. DOCKET NO. 50-370 McGUIRE NUCCEAR STATION, UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE.

Amendment No. 19 License No. NPF-17 1.

The Nuclear Regulatory Comission (the Commission) has found that:

A.

The application for amendment to the McGuire Nuclear Station, Unit 2 (the facility) Facility Operating License No. NPF-17 filed by the Duke Power Conipany (licensee) dated August 31, 1984, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's regulations as set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, as amended, the provisions of the Act, and the regulations of the Comission; C.'

There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this license amendment will not be inimical to the l

comon defense and security or to the health and safety of the public; i

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 l

of the Commission's regulations and all applicable requirements have j

been satisfied.

l 2.

Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachments to this license amendment and paragraph 2.C.(2) of Facility Operating License No. NPF-17 is hereby amended l

to read as follows:

(2) Technical Specifications l

The Technical Specifications contained in Appendix A, as revised through Amendment No.19, are hereby incorporated into this license.

i I

l l

l t

~

1 9

The licensee shall operate the facility in accordance with the Tech-nical Specifications and the Environmental Protection Plan.

L 3.

This licen,se amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGULATORY COPMISSION t

h in.$0 S Elinor G. Adensam, Chief Licensing Branch No. 4' Division of Licensing

Attachment:

Technical Specification Changes a

Date of Issuance: February 1, 1985

. 4

/

W O

O r-w-

aw--

-e--m,.

m w nm w,

ATTACHMENT TO LICENSE AMENDMENT NO. 38 FACILITY OPERATING LICENSE NO. NPF-9 DOCK T NO. 50-369 AND TO LICENSE AMENDMENT NO. 19 FACILITY OPERATING LICENSE NO. NPF-17 DOCKET NO. 50-370 Replace the following page of the Appendix "A" Technical Specifications with the enclosed page. The revised page is identified by Amendment number and contains a vertical line indicating the area of change. The corresponding overleaf page is also provided to maintain document completeness.

Amended Overleaf Page Page 3/4 8-5 3/4 8-6 i

e-I

d ELECTRICAL' POWER SYSTEMS I

SURVEILL NCE REQUIREMENTS (Continued) 5)

Verifying that on an ESF actuation test signal, without loss-of-

'offsite power, the diesel generator starts on the auto-start

' signal and operates on standby for greater than or equal to 5 minutes.

The generator voltage and frequency shall be at least 4160 volts and 57 Hz within.11 seconds after the auto-start signal; the steady-state generator voltage and frequency shall be maintained within 4160 t 420 volts and 60 1.1.2 Hz during this test; 6)

Verifying that on a simulated loss of the diesel generator, with offsite power not available, the loads are shed from the emergency busses and that subsequent loading of the diesel generator is in accordance with design requirements; 7)

Simulating a loss-of-offsite power in conjunction with an ESF actuation test signal, and a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses; b)

Verifying the diesel starts on'the auto-start signal, energizes the emergency busses with permanently connected loads within 11 seconds, energizes the auto-connected emergency (accident) loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the emergency loads. After energization, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 +

420 volts'and 60 + 1.2 Hz during this test; and

- c)

Verifying that all automatic diesel generator trips, except engine.overspeed, lube oil pressure, and generator differential, and all diesel generator breaker trips, except generator time overcurrent, are automatically.

bypassed upon loss of voltage on the emergency bus con-current with a Safety Injection Actuation signal.

8)

Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During the_first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator shall be loaded to greater than or equal to 4400 kW and during.

the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to greater than or equal to 4000 kW.

The generator voltage and frequency shall be at least 4160 volts and 57 Hz.

'within'11 seconds after the: start signal.

The steady-state

~

generator voltage and~ frequency shall be maintained within 4160 1.420 volts and 60'i 1.2 Hz during ^.his test. Within 5 minutes aftr.r completing this 24-hour test, perform Specifj-cation 4.8.1.1.2d.7)b);

McGUIRE - UNITS 1 and 2 3/4 8-5 Amendment No.19 (Unit 2)

Arendment No.38 (Unit 1) t

ELECTRICAL POWER SYSTEMS ~

[

SURVEILLANCE REQUIREMENTS (Continued) 9)-

Verifying that the auto-connected loads to each diesel

~

generator do not exceed the 2-hour rating of 44QO kW;

10) Verifying the df esel' generator's capability to:

a)

Synchronize with the offsite power source while the generator is~ loaded with its emergency loads upon a simulated restoration of offsite power, b)

Transfer its loads to the offsite power source, and c)

Be restored to its standby status.

II) Verifying that with the diesel generator operating in a test mode, connected to its bus, a simulated Safety Injection signal

~ overrides the test mode by:

(1) returning tha diasel generator to standby operation, and (2) automatically energizing the emergency loads with offsite power;

12) Verifying that the fuel transfer pump transfers fuel from each fuel storage tank to the day tank of each diesel via the installed cross-connection lines;
13) Verifying that the automatic load sequence timer is OPERABLE with the. interval between each load block are within the

. tolerances shown in Table 4.8-2;

14) Verifying that the following diesel generator lockout features prevent diesel generator starting only when required:

a)

Turning gear engaged, and

[

b)

Emergency stop.

15) Verifying that with all diesel generator air start receivers pressurized to less than or equal to 220 psig a,nd the compres-l sors secured, the diesel generator starts at least 2 times from ambient conditions and accelerates to at least 438 rpm in less than or equal to 11 seconds.

i f.

At least once per 10 years or after any modifications which could affect diesel generator interdependence by starting both diesel generators simultaneously, during shutdown, and verifying that both diesel generators ' accelerate to at least 488 rpm in less than or i

equal to 11 seconds; and

-g.

At least once per 10 years by:

,(

l L

f McGUIRE - UNITS 1 and 2 '

3/4 8-6 knendment No.14 (Unit 2)

Amendment No. 33 (Unit 1)