ML20106H280

From kanterella
Jump to navigation Jump to search
Provides Info to Address SER Requirement,Section 9.1.3,for Tech Spec for Fuel Pool Cooling & Cleanup Sys,Consisting of Encl Page 9-6.SER Change to Delete Requirements for Tech Specs for Fuel Pool Cooling & Cleanup Sys Requested
ML20106H280
Person / Time
Site: Perry  
Issue date: 02/13/1985
From: Edelman M
CLEVELAND ELECTRIC ILLUMINATING CO.
To: Youngblood B
Office of Nuclear Reactor Regulation
References
NUDOCS 8502150241
Download: ML20106H280 (3)


Text

.

.s fIs,it

.<,n 1

4 4

<u e n c.

LLLpgiLLAqq

. g c p l !- l b t: J a i' ! s -

!1

.e U a l', il '

ni.-

a

,y b Le tuta w

P.O. box 5000 - CLEVELAND. oHlo 44101 - TELEPHONE (216) 622-9800 - lLLUMINATING BLDG.

- 55 PUBLicSQUARE Serving The Best Location in the Nation MURRAY R. EDELMAN VICE PRESIDENT NUCLEAR February 13, 1985 PY-CEI/NRR-0181 L Mr. B. J. Youngblood, Chief Licensing Branch No. 1 Division of Licensing U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Perry Nuclear Power Plant, Units 1 & 2 Dockets Nos. 50-440; 50-441 Spent Fuel Pool Cooling and Cleanup System

Dear Mr. Youngblood:

This letter provides information to andress the SER requirement, Section 9.1.3 (p.9-6, attached), for a Technical Specification for the Fuel Pool Cooling and Cleanup System.

The SER states that "the spare pump will be operated periodically in accordance with plant Technical Specifications." This testing is performed as required by Technical Specification 4.0.5 which provides for inservice inspection and testing of ASME Code Class I, II, and III components in accordance with ASME Section XI.

In addition, Perry administrative procedure OAP-0206, Rotation of Operating Equipment, requires the fuel pool cooling and cleanup pumps to be rotated into service on a monthly basis. This procedure provides assurance that both pumps will be available at all times.

The SER also states that we have committed to running the RilR system of the shutdown reactor in the Fuel Pool Cooling mode until the normal system can maintain the temperature limit. Since all fuel has to be unloaded from the vessel to get into this condition, there are no Technical Specifications requirements for ECCS systems. Thus, two loops of RilR system can be used to remove all of the decay heat from the pool. Technical Specifications currently require all ECCS to be operable in Operational Condition 1, 2, & 3.

This prevents reactor start-up while the RilR system is in the Fuel Pool Cooling mode, as mentioned in paragraph 5.

l\\

8502150241 850213 i

PDR ADOCK 05000440

\\

E PDR u

__m o

Mr. B. J. Youngblood PY-CEI/NRR-0188L February 13, 1985 The requirement for a Technical Specification related to the fuel pool cooling and cleanup system does not presently exist in the Standard Technical Specifications. We feel that a specific Technical Specification for the Fuel

. Pool Cooling and Cleanup System is not required, since the SER requirements are addressed elsewhere in the Perry Technical Specifications.

'We believe that this information is responsive to staff concerns, and request the SEE be changed to delete these requirements for Technical Specifications for the Fuel Pool Cooling and Cleanup Systems.

Very truly yours,

.Edelm%

Murray an Vice President Nuclear Group MREtnje Attachment cc: Jay Silberg, Esq.

J. Stefano J. Grobe S. Brown k

  • ~

ATTACHMENT l

i

)

The various components of the system are located in shielded cubicles or are i

separated from other moderate-and high-energy piping systems. Thus, the requirements of GDC 4 and the guidelines of Regulatory Guide 1.13, Position C.2,

)

are satisfied.

j i

The system serves the shared fuel storage facility with sufficient redundancy of equipment and conservative design that the requirements of GDC 5 are met.

The system is accessible for routine visual inspection of the system components.

One fuel pool cooling pump is in operatian at all times. The spare pump will be operated periodically in accordance with plant Techr.ical Specifications.

Thus, the requirements of GDC 45, " Inspection of Cooling Water Systems," and GDC 46, " Testing of Cooling Water Systems" are satisfied.

The spent fuel pool cooling system will maintain the fuel pool water tempera-ture.at 127*F with a heat load based on decay heat generation from 4020 fuel assemblies (maximum storage) and both cooling trains in operation. This is the normal discharge from 9 years of operation of Units 1 and 2.

If one pump and heat exchanger were lost under these conditions, the temperature would rise to 160*F maximum for a short period. The applicant has committed to running the residual heat removal (RHR) system of a shutdown reactor to maintain tempera-

. tures below.150*F until the normal system could maintain the temperature below 150*F.

I In the case of an abnormal heat load when the full core of one unit must be-unloaded, the RHR system of the affected unit would be used to maintain the

)

temperature of the fuel pool below 150*F. Under these conditions, the RHR system could maintain a fuel pool temperature of 106*F. Again, the RHR system t

would be used until the normal system could maintain the temperature below 150*F. The reactor of the unit whose RHR system is providing pool cooling, will not be started up.. The Perry Technical Specifications will prevent reactor startup when the RHR system is providing fuel pool cooling. Heat loads for the above storage modes are based on BTP AS8 9-2, " Residual Decay Energy for Light Water Reactors for Long-Term Cooling."

~

No connections are provided to the spent fuel pool that may cause the pool

. ater to be drained below a safe shielding level. All lines that connect to w

the pool and extend below the safe level of the pool water are equipped with syphon breakers, check valves, or other means to prevent inadvertent pool drainage. The nonsafety-related nuclear closed cooling water system provides cooling water to the fuel pool heat exchanger under normal conditions. Backup cooling is available in emergency conditions from the emergency (seismic Cate-gory I) closed cooling water system which transfers spent fuel pool heat loads to the ultimate heat sink (refer to Sections 9.2.1, 9.2.2, and 9.2.5). In addi-tion, the residual heat removal system can be utilized to supplement the fuel poolcoolingsystembyprovidingadditionalcoolingduringshutdownasdescribed above. Thus, the requirements of GDC.44, " Cooling Water, are met.

Normal makeup to the pool is provided by the nonsafety-related condensate and

", ' )i refueling water storage and transfer system to replace losses from leakage through the liner and evaporation. Emergency makeup is supplied by the redun-

~'.

dant loops of the seismic Category I emergency service water system! Thus, t requirements of GOC 61, and the guidelines 'of Regulatory Guide 1.13, Position i

C-6, concerning fuel pool design are satisfied..

Pprry SER 9-6

-