Special Rept 92-06:on 920807,fire Diesel Pump 1 Declared Inoperable for More than 7 Days to Perform Preventive Maint.On 920811,diesel Engine Overheated.Solenoid Valve Replaced & New Cooling Water Strainers Installed
ML20105A512
Person / Time
Site: Oyster Creek
Issue date: 09/10/1992
From: J. J. Barton
GENERAL PUBLIC UTILITIES CORP.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
92-06, 92-6, C321-92-2253, NUDOCS 9209170047
Download: ML20105A512 (2)


Text

-

ib e

t OPU Nuclear Corporadon Nuclear

=sur **

Forked River, New Jersey 08731-0388 609 971-4000

%ter's D: rect Dial Number:

September 10, 1992 C321-92-2253 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C.

20555 Gentlemen:

Subject:

Oyster. Creek Nuclear Generating Station Dacket No. 50-219 Special Report No. 92-06 Enclosed is Special Report No. 92-06 which is submitted in accordance with technical specification 3.12.B.2.

If there are any questions, please call Mr. Michael Heller, Licensing

Engineer, at (609) 971-4680.
interely, g7

/

h)I M

i J. J.'B on Vi c President and Director 0) cr Creek Enclosure cc:

.NRC Region 1 Administrator NRC Resident Inspector i

[.

Oyster Creek NRC Project Manager l

l L

9TOOGI 9209170047 920910 PDR ADOCK 0500021"'

/ h' I S

PDR y

g ceuNeee,c.,_ sesees

- O_ oescumesc-,s-

7 1, n.

4 i

Qyster Creek fhtglear Generatinglation

.Special Reoprt 92-06 Rgoort Datei September 10, 1992 Occurrence Datei August 7, 1992 Identification of Occurreaqs1 The #1. fire diesel pump was inoperable for greater than 7 days which requires a special report per technical specification 3.12.B.2.

D ncrip_ tion of Oclyrren.c_qi c

The #1 fire diesel pump was removed form service on August 7,1992 to perform routine quarterly; preventive maintenance tasks. When the pump was being returned to service on August 11, 1992, the diesel engine overheated during the operability surveillance.

Corrective action was taken to replace the cooling water solenoid valve (V-9-52) and install new cooling water strainers.

The #1 fire diesel pump again tested and declared operable on August 15, 1992.

During this entire period, the #2 fire diesel pump and the backup suppression

-water system were operable.