Rev 4 to Pump & Valve Program Re Insp of Jacket & Air Cooler Coolant Sys
ML20102B892
Person / Time
Site: Crystal River 
Issue date: 02/27/1985
From:
FLORIDA POWER CORP.
To:
Shared Package
ML20102B891 List:
References
PROC-850227, NUDOCS 8503040491
Download: ML20102B892 (4)


Text

l TABLE 2 - VALVES FOR WHICH RELIEF IS REQUESTED SYSTEM NAME: DIESEL,3ACKET COOLANT DRAWING No. FD-302-283 Page 1ofI DATE: 02/27/85 REVISION 4 Valve Asme Dwg.

Asme Valve Cat.

Size In Valve Act. Norm. Test Test Sury.

Leak Rate Relief Number Class Co-Ord. ABCDE Inches Type Type Pos.

Freq.

Method Proc.

(SCC / Min) Table 2A REMARKS DJV-1 3

N/A X

CK SA 605 1

DJV-2 3

N/A X

CK SA 605 1

DJV-17 3

N/A X

CK SA 605 1

DJV-18 3

N/A X

CK SA 605 1

DJV-27 3

N/A X

CK SA 605 1

DJV-28 3

N/A X

CK SA 605 1

DJV-29 3

N/A X

CK SA 605 1

DJV-30 3

N/A X

CK SA 605 1

DJV-31 3

N/A X

CK SA 605 1

DJV-32 3

N/A X

CK SA 605 I

c 8503040491 850227 PDR ADOCK 05000302 O

pm

Page 1ofI DATE: 02/27/85 REVISION 4 TABLE 2A VALVE RELIEF REQUEST BASIS System: Diesel,3acket Coolant (DJ) 1.

Valves:

D3V-1, D3V-2, D3V-17, D3V-18, D3V-27, D3V-28, D3V-29, D3V-30, D3V-31, D3V-32 Function:

These are the essential valves comprising the coolant water flow path of the Emergency Diesel and its associated lube oil system.

Test Requirement:

EF-lF Basis for Relief:

The emergency diesels are required to be tested monthly in accordance with the facility technical specifications.

The starting and operation of the emergency diesels requires use of this system.

Alternate Testing:

Each diesel will be tested in accordance with plant technical specifications. Current technical specifications require each diesel be tested monthly. The successful completion of this test shall denote the subject valves are allowing coolant flow.

The valves are disassembled for a visual inspection of the disk and seating surface at 5,000 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> of diesel operation or 5 years, whichever comes first.

l

TABLE 2 - VALVES FOR WHICH RELIEF IS REQUESTED SYSTEM NAME: DIESEL, AIR COOLER COOLANT DRAWING No. FD-302-284 Page 1ofI DATE: 02/27/85 REVISION 4 Valve Asme Dwg.

Asme Valve Cat.

Size In Valve Act. Norm. Test Test Sury.

Leak Rate Relief Number Class Co-Ord. ABCDE Inches Type Type Pos.

Freq.

Method Proc.

(SCC / Min) Table 2A REMARKS DJV-38 3

N/A X

CK SA 605 1

D3V-39 3

N/A X

CK SA 605 1

Page1of1 DATE: 02/27/85 REVISION 4 TABLE 2A VALVE RELIEF REQUEST BASIS System: Diesel, Air Cooler Coolant (DJ) 1.

Valves:

DJV-38, D3V-39 Function:

Provide coolant water for the combustion air coolers in the emergency diesels.

Test Requirement:

EF-lF Basis for Relief:

The emergency diesels are required to be tested monthly in accordance with the facility technical specifications.

The starting and operation of the emergency diesels requires use of this system.

Alternate Testing:

Each diesel will be tested in accordance with plant technical specifications. Current technical specifications require each diesel be tested monthly. The successful completion of this test shall denote the subject valves are allowing coolant flow.

The valves are disassembled for a visual inspection of the disk and seating surface at 5,000 hours0 days <br />0 hours <br />0 weeks <br />0 months <br /> of diesel operation or 5 years, whichever comes first.