ML20101M877

From kanterella
Jump to navigation Jump to search
Amend 8 to Environ Rept
ML20101M877
Person / Time
Site: Millstone 
Issue date: 12/31/1984
From:
NORTHEAST NUCLEAR ENERGY CO.
To:
Shared Package
ML20101M870 List:
References
ENVR-841231, NUDOCS 8501030285
Download: ML20101M877 (90)


Text

_ _ _ _

MNPS-3 EROLS INSERTION INSTRUCTIONS FOR AMENDNINT 8

]

i Remove old pages and insert Amenhent 8 pages as instructed below (amenhent pages bear the amendment number and date at the foot of the page).

I i

Vertical bars (change bars) have been placed in the outside margins of 4

revised text pages and tables to show the location of any technical changes originating with this amendment. A few unrevised pages have-l

, been reprinted because they fall within a run of closely spaced revised pages. No change bars are used on figures.

Transmittal letters along with these insertion instructions should

-l '

either be filed or entered in Volume I in front of any existing letters, i

instructions, distribution lists, etc.

f i

LEGEND l

Remove / Insert Columns I

5 Intries beginning with "T"

or "F" designate table or figure numbers, respectively. All other entries are page numbers:

T2.3-14 = Table 2.3-14 F2.3-14 = Figure 2.3-14 I

2.1-9 = Page 2.1-9 EP2-1 = Page EP2-1 vil = Page vil i

Pages printed back to back are indicated by a "/"

i f

1.2 5/6 = Page 1.2-5 backed by Page 1.2-6

[

t T2.3-14(5 of 5)/15(1 of 3) = Table 2.3-14, sheet 5 of 5, backed by Table 2.3-15, sheet 1 of 3 i

Location Column I

Ch = Chapter, S = Section, Ap = Appendix i

i i

l-i l

i Oh i o Amenhent 8 1 of 3 December 1984 l

L

., - -.. ~ _ _ - _, _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ - - _ _ - - - - - - - - _ _

MNPS-3 EROLS INSERTION INSTRUCTIONS FOR AMENDMENT 8 (Cont)

Remove Insert Location VOLUME 1 EP2-1 thru EP2-9 EP2-1 thru EP2-9 After Ch. 2 Tab T2.1-22 (1 of 1)/T2.1-23 T2.1-22 (1 of 1)/T2.1-23 After S2.1 Tab (1 of 1)

(1 of 1) 2.2-7 thru 2.2-10 2.2-7 thru 2.2-10 Af ter S2.2 Tab VOLUME 2 T2.3-38 (1 of 1) thru T2.3-38 (1 of 1) thru After S2.3 Tab T2.3-39 (3 of 3)

T2.3-39 (3 of 3)

T2.3-44 (1 of 1)/T2.3-45 T2.3-44 (1 of 1)/T2.3-45 (1 of 1)

(1 of 1)

T2.3-50 (1 of 1)/T2.3-51 T2.3-50 (1 of 1)/T2.3-51 (1 of 1)

(1 of 1)

T2.3-56 (1 of 1) thru T2.3-56 (1 of 1) thru T2.3-63 (1 of 1)

T2.3-63 (1 of 1)

EP3-1/EP3-2 EP3-1/EP3-2 After Ch. 3 Tab T3.3-1 (1 of 1)/ Blank T3.3-1 (1 of 1)/ Blank After S3.3 Tab F3.3-1 F3.3-1 3.4-1/3.4-2 3.4-1/3.4-2 After 53.4 Tab 3.4-5/3.4-6 3.4-5/3.4-6 T3.4-1 (1 of 1)/ Blank T3.4-1 (1 of 1)/ Blank 3.6-1 thru 3.6-4 3.6-1 thru 3.6-4 Af ter S3.6 Tab T3.6-1 (1/2 of 3)

T3.6-1 (1/2 of 3) 3.7-1/3.7-2 3.7-1/3.7-2 After S3.7 Tab T3.7-1 (1 of 1)/T3.7-2 T3.7-1 (1 of 1)/T3.7-2 (1 of 1)

(1 of 1)

EP5-1 thru EP5-3 EP5-1 thru EP5-3 After Ch. 5 Tab 5.3-1 thru 5.3-4 5.3-1 thru 5.3 4 After S5.3 Tab T5.3-3 (1 of 1)/ Blank T5.3-3 (1 of 1)/Dlank O

Amendment 8 2 of 3 December 1984

)

4

MNPS-3 EROLS i

t INSERTION INSTRUCTIONS FOR AMENDMENT 8 (Cont)

O l

Remove Insert Location VOLUME 3 EP6-1/ Blank EP6-1/ Blank After Ch. 6 Tab 6.2-1/6.2-2 6.2-1/6.2-2 After 56.2 Tab

{

EP-E-1/ Blank EP-E-1/ Blank After Ap E Tab F E-3 F E-3

-i VOLUME 4 EPQ-1/EPQ-2 EPQ-1/EPQ-2 After January 31, 1983 Tab T QE311.5-1 (1 of 1) thru T QE311.5-1 (1 of 1) thru After QE311.5 T QE311.5-14 (1 of 1)

T QE311.5-14 (1 of 1) 4 i

~

i s

i I

i i

i

(

Amendment 8 3 of 3 December 1964 1

?.

MNPS-3 EROLS 7-~g LIST OF EFFECTIVE PAGES Page. Table-(T). or Amendment Figure (F)

Mumber 2-i 5

2-ii thru 2-viii 0

2-ix 5

2-x thru 2-xii 0

2-xiii 5

'2-xiv 0

2-xv 5

2-xvi 0

2-xvii 5

2.1-1 thru 2.1-2 0

2.1-3 thru 2.1-5 5

2.1-6 0

2.1-7 1

2.1-8 4

2.1-9 thru 2.1-10 0

2.1-11 4

2.1-12 thru 2.1-30 0

T2.1-1 (1 of 1) 0 T2.1-2 (1 of 1) 0 T2.1-3 (1 of 1) 0 T2.1-4 (1 of 1) 0 T2.1-5 (1 of 1) 0 T2.1-6 (1 of 1) 0 4

T2.1-7 (1 of 1) 0 T2.1-8 (1 of 1) 0 T2.1-9 (1 of 1) 0 T2.1-10 (1 of 1) 0

/.

72.1-11 (1 of 1) 0 T2.1-12 (1 of 1) 0 T2.1-13 (1 of 1) 0 T2.1-14 (1 of 1) 0 T2.1-15 (1 of 1) 0 T2.1-16 (1 of 1) 0 T2.1-17 (1 of 1) 0 T2.1-18 (1 of 1) 0 T2.1-19 (1 of 1) 0 T2.1-20 (1 of 1) 0 T2.1-21 (1 thru 2 of 2) 0 T2.1-22 (1 of 1) 8 T2.1-23 (1 of 1) 0 T2.1-24 (1 thru 2 of 2) 0 T2.1-25 (1 of 3) 4 O

T2.1-25 (2 thru 3 of 3) 0 T2.1-26 (1 of 1) 0 Amendment 8 EP2-1 December 1984

MNPS-3 EROLS LIST OF EFFECTIVE PAGES (Cont)

Page, Table (T), or Amendment Figure (F)

Number T2.1-27 (1 thru 3 of 3) 0 T2.1-28 (1 of 1) 0 T2.1-29 (1 of 1) 0 T2.1-30 (1 of 1) 0 T2.1-31 (1 of 1) 0 T2.1-32 (1 thru 3 of 3) 0 T2.1-33 (1 of 1) 0 T2.1-34 (1 thru 3 of 3) 0 T2.1-35 (1 thru 4 of 4) 0 T2.1-36 (1 thru 2 of 2) 0 T2.1-37 (1 of 1) 0 T2.1-38 (1 thru 2 of 2) 0 T2.1-39 (1 of 1) 0 T2.1-40 (1 thru 2 of 2) 0 T2.1-41 (1 thru 2 of 2) 0 T2.1-42 (1 of 1) 0 T2.1-43 (1 of 1) 0 T2.1-44 (1 of 1) 0 T2.1-45 (1 of 1) 0 T2.1-46 (1 of 1) 0 T2.1-47 (1 thru 2 of 2) 0 T2.1-48 (1 thru 2 of 2) 0 T2.1-49 (1 of 1) 0 F2.1-1 0

F2.1-2 0

F2.1-3 5

F2.1-4 5

F2.1-5 7

F2.1-6 0

F2.1-7 0

F2.1-8 0

F2.1-9 0

F2.1-10 0

F2.1-11 0

F2.1-12 0

F2.1-13 0

F2.1-14 0

F2.1-15 0

F2.1-16 0

F2.1-17 0

F2.1-18 0

F2.1-19 0

F2.1-20 0

F2.1-21 0

Amendment 8 EF2-2 December 1984 L_

MNPS-3 EROLS LIST OF EFFECTIVE PAGES (Cont)

O Page, Table (T), or Amendment Figure (F)

Number F2.1-22 0-F2.1-23 0

F2.1-24 1

F2.1-25 0

F2.1-26 0

F2.1-27 0

F2.1-28 0

F2.1-29 0

F2.1-30 0

F2.1-31 0

F2.1-32 0

F2.1-33 0

F2.1-34 4

F2.1-35 0

F2.1-36 0

F2.1-37 0

F2.1-38 0

O F2.1-39 0

2.2-1 thru 2.2-7 0

2.2-8 thru 2.2-9 8

2.2-10 thru 2.2-19 0

2.2-20 5

2.2-21 thru 2.2-22 0

2.2-23 5

2.2-24 thru 2.2-33 0

2.2-34 5

2.2-35 thru 2.2-63 0

2.2-64 5

2.2-65 thru 2.2-104 0

T2.2-1 (1 thru 10 of 10) 0 T2.2-2 (1 thru 2 of 2) 0 T2.2-3 (1 of 1) 0 T2.2-4 (1 thru 3 of 3) 0 T2.2-5 (1 of 1) 5 T2.2-6 (1 of 1) 0 T2.2-7 (1 thru 2 of 2) 0 T2.2-8 (1 of 1) 5 T2.2-9 (1 thru 2 of 2) 0 T2.2-10 (1 of 2) 5 T2.2-10 (2 of 2) 0 T2.2-11 (1 of 1) 0 T2.2-12 (1 of 1) 0 T2.2-13 (1 of 1) 0 Amendment 8 EP2-3 December 1984

MNPS-3 EROLS LIST OF EFFECTIVE PAGES (Cont)

Page, Table (T), or Amendment Figure (F)

Number T2.2-14 (1 of 1) 5 T2.2-15 (1 of 1) 0 T2.2-16 (1 thru 6 of 7) 0 T2.2-16 (7 of 7) 5 T2.2-17 (1 thru 3 of 3) 0 T2.2-18 (1 of 1) 0 T2.2-19 (1 of 1) 0 T2.2-20 (1 of 1) 0 T2.2-21 (1 of 1) 0 T2.2-22 (1 thru 4 of 4) 0 T2.2-23 (1 thru 2 of 2) 0 T2.2-24 (1 of 1) 0 T2.2-25 (1 thru 4 of 4) 0 T2.2-26 (1 thru 2 of 2) 0 T2.2-27 (1 of 1) 0 T2.2-28 (1 of 1) 0 T2.2-29 (1 thru 2 of 2) 0 T2.2-30 (1 thru 10 of 10) 0 T2.2-31 (1 thru 3 of 3) 0 T2.2-32 (1 of 1) 0 T2.2-33 (1 of 1) 0 T2.2-34 (1 of 3) 5 T2.2-34 (2 thru 3 of 3 0

T2.2-35 (1 of 1) 0 T2.2-36 (1 of 1) 0 T2.2-37 (1 of 1) 0 T2.2-38 (1 of 1) 5 T2.2-39 (1 of 1) 0 T2.2-40 (1 of 1) 0 T2.2-41 (1 thru 2 of 2) 0 T2.2-42 (1 of 1) 5 T2.2-43 (1 of 1) 0 T2.2-44 (1 of 1) 0 T2.2-45 (1 of 1) 0 T2.2-46 (1 thru 3 of 3) 0 T2.2-47 (1 of 1) 0 T2.2-48 (1 thru 2 of 2) 0 T2.2-49 (1 of 1) 0 T2.2-50 (1 of 1) 0 T2.2-51 (1 of 1) 0 T2.2-52 (1 thru 2 of 2) 0 T2.2-53 (1 of 1) 0 T2.2-54 (1 of 1) 0 T2.2-55 (1 of 1) 0 Amendment 8 EP2-4 December 1984

~

3\\

h

,c.

a

?.,

MNPS-3 EROLS

.. L s,

'. LIST _OF EFFECTIVE PAGES (Cont) y t

Page, Table (T), or Amendment s

/j Figure (F)

Number

.T2.2-56 (1 of 1) 0 P2.2-1 s

0 F2.2-2 0

F2.2-3 0

F2.2-4 0

N F2.2-5 0

.i F2.2-6.

0 F2.2-7 0

'}

'F2.2-8 0

F2.2-9 0

F2.2-10 0

F2.2-11 0

F2.2-12 (3 ' sheets) 0 F2.2-13 0

F2.2-14 O

t l

~

.-F2.2-15 0

0 l

F2.2-16 (3 sheets)

F2.2-17 0

,\\

F2.2-18 O

s

.F2.2-19 0

+

r

l..

r2.2-20 0

F2.2-21 0

a F2.2-22 0

F2.2-23 O

F2.~2-24.(3 sheets)

.0

-F2.2-25 0

F2.2-26 0

F2.2-27

-0 F2.2-28-(2 sheets)

O l

F2.2-29 O

l'?

F2.2-30 O

F2.2-31 O

l F2.2-32

.0 l

F2.2-33 0'

F2.2-34 0

F2.2-351 0

l F2.2-36 0

i.

F2.2-37 0,

i F2.2-38 0-I,.

F2.2-39 0

l F2.2-40 0

F2.2-41 0

F2.2-42 0

F2.2-43 0

(w

' Amendment-8 EP2-5 December 1984 i

.a k

MNPS-3 EROLS LIST OF EFFECTIVE PAGES (Cont)

O Page, Table (T), or Amendment Figure (F)

Number F2.2-44 0

F2.2-45 0

F2.2-46 0

F2.2-47 0

F2.2-48 0

F2.2-49 0

F2.2-50 0

F2.2-51 0

Summary TC 1 thru ii 0

2.3-1 0

2.3-2 4

2.3-3 thru 2.3-6 0

2.3-7 1

2.3-8 1

2.3-9 1

2.3-10 1

2.3-11 1

2.3-12 1

2.3-13 thru 2.3-15 5

2.3-16 thru 2.3-17 0

2.4-18 thru 2.3-19 5

2.4-20 thru 2.3-24 0

T2.3-1 (1 of 1) 0 T2.3-2 (1 of 1) 0 T2.3-3 (1 of 1) 1 T2.3-4 (1 of 1) 0 T2.3-5 (1 of 1) 0 T2.3-6 (1 of 1) 1 T2.3-7 (1 of 1) 0 T2.3-8 (1 of 1) 1 T2.3-9 (1 of 1) 0 T2.3-10 (1 of 1) 0 T2.3-11 (1 of 1) 1 T2.3-12 (1 of 1) 0 T2.3-13 (1 of 1) 0 T2.3-14 (1 thru 13 of 13) 1 T2.3-15 (1 thru 13 of 13) 0 T2.3-16 (1 of 1) 0 T2.3-17 (1 of 1) 0 T2.3-18 (1 of 1) 1 T2.3-19 (1 thru 2 of 2) 1 T2.3-20 (1 of 1) 1 Amendment 8 EP2-6 December 1984

MNPS-3 EROLS

~

LIST OF EFFECTIVE PAGES (Cont)

Page, Table (T), or Amendment Figure (F)

Number

-T2.3-21 (1 of 1) 1 T2.3-22 (1 of 1) 1 T2.3-23 (1 thru 8 of 8) 0 T2.3-24 (1 thru 3 of 3) 0 T2.3-25 (1.of 1) 0 T2.3-26 (1 of 1) 0 T2.3-27 (1 of 1) 0

'T2.3-28 (1 of 1) 1 T2.3-29 (1 thru 12 of 12) 0 T2.3-30 (1 of 1) 0 T2.3-31 (1 of 1) 2 T2.3-32 (1 of 1) 2 T2.3-33 (1 of 1) 2 T2.3-34 (1 of 1) 2 T2.3-35 (1 of 1) 2 T2.3-36 (1 of 1) 2

-~s

~ T2.3-37 (1 of 1) 2 T2.3-38 (1 of 1) 2 T2.3-39 (1 thru 3 of 3) 8 T2.3-40 (1 of 1) 1 T2.3-41 (1 of 1) 0 T2.3-42 (1 of 1) 1 T2.3-43 (1 of 1) 1 T2.3-44 (1 of 1) 8 T2.3-45 (1 of 1) 8 T2.3-46 (1 off1)-

0

'T2.3-47 (1 of 1) 1 4

T2.3-48 (1 of 1) 1 T2.3-49-(1 of 1) 0 T2.3-50 (1 of 1) 8 T2.3-51 (1 of 1).

8 T2.3-52c(1.of 1) 0 T2.3-53 (1 of 1) 1 T2.3-54 (1 of 1)-

0 T2.3-55 (1 of 1) 0 T2.3-56 (1 of.1) 8 T2.3-57 (1 of 1) 8 T2.3-58 (1 of 1) 8 T2.3-59 (1 of 1) 8 T2.3-60'(1 of 1) 8

=

T2.3-61~(1 of 1)1 8

~

T2.3-62 (1 of 1) 8

,T2.3-63 (1 of 1) 8 O

.T2.3-64 (1 of 1) 0 c.

Amendment 8 EP2-7 December 1984

MNPS-3 EROLS LIST OF EFFECTIVE PAGES (Cont)

Page, Table (T), or Amendment Figure (F)

Number T2.3-65 (1 of 1) 0 T2.3-66 (1 of 1) 1 T2.3-67 (1 of 1) 0 T2.3-68 (1 of 1) 0 T2.3-69 (1 of 1) 0 F2.3-1 0

F2.3-2 0

F2.3-3 0

F2.3-4 (2 sheets) 0 F2.3-5 (2 sheets) 0 F2.3-6 (2 sheets) 0 F2.3-7 0

2.4-1 5

2.4-2 thru 2.4-10 0

2.4-11 5

2.4-12 0

2.4-13 2

2.4-14 thru 2.4-17 0

T2.4-1 (1 thru 3 of 3) 0 T2.4-2 (1 of 1) 0 T2.4-3 (1 of 1) 0 h

T2.4-4 (1 of 1) 0 T2.4-5 (1 of'1) 0 F2.4-1 0

F2.4-2 0

F2.4-3 0'

o F2.4-4 0

F2.4-5 0

F2.4-6 0

F2.4-7 0

F2.4-8 0

F2.4-9 0

F2.4-10 0

F2.4-11 0

F2.4-12 0

F2.4-13 0

2.5-1 thru 2.5-2 2

F2.5-1 0

F2.5-2 0

2.6-1 thru 2.6-3 0

T2.6-1 (1 thru 2 of 2) 0 Amendment 8 EP2-8 December 1984

t.s-

- o 3~

r 1

_MNPS-3 EROLS.

1-

-(

' LIST OF EFFECTIVE PAGES'(Cont) e y

c.

i Page, Table'(T), or Amendment Figure (F)

Number 4

i

~

T2.6-2 (1 of 1) 0.6A (Cover) - 1 page 0

i.6A.- 1 page 0

- Attachment 2.6A-(letter) - 3 pages 0

4

,.6A (list) - 15 pages O

L.

~ Attachment 2.6B (cover) - 1 page 0

l.68 - 1 page 0.6B (letter) - 2 pages-0 2.7-1 5

2.7-2 thru 2.7-3 0

T2.7-1 (1 of 1) 0 T2.7-2 (1 of 1)-

0 l

f T2.7-3 (1 thru 2 of 2) 0 F2.7-1~

0 F2.7 2

- +

A f

I.

~.

p.

.?

5 I

i.

't a

r l

,c y:

^

li L

L l-l-

t

-Amendment 8-EP2-9'

' December 1984 i

t 4

y

'T I 4-7-O M raw b

b h==

d e+t gp

-pe w --up,eg.g'W,ge-yr.W sr 'W ws't We 9

_ 13 -w%- w F *=r'-M-e y yg *M s -wg Pg yq=' us'em-' w-pMW p %-4-r4e-'MFr'Ww-'ppywe e WW= $ 7 M1*g g T@Wy$"**'T-WF T

..~ _ -_.

h

%Y

%/

y,/.

NNPS-3 EROLS b

TABLE 2.1-22' RADIOLOGICAL PATHWAY ANALYSES PARAMETERS

( 1981 ) '" '

(Distances are 'f rom' containment and turbine but iding vents) "*

8

(

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW Nearest milk cow 9.6 Nearest meat animal '"

Nearest milk Doat 3.2 2.9 3.2 4.0 4.8.

8 Nearest residanco 0.92 1.55 0.84 0.81 1.30 1.69 33.0 22.2 16.1 18.3 3.38 3.05 2.70 2.31 0.68 0.69

' Nearest vegetable garden '**

O.92 1.55 0.84 0.81 1.30 1.69 33.0 22.2 16.1 18.3 3.38 3.05 2.70 2.31 0.68 0.69 8

Nearest si te boundary "'

O.92 1.55 0.84 0.60

0. 60 '" O.60 0.60 0.63 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.69 4

@_I.E S :

1.

Table updated to reflect information available as of April 1984 g

2.

All distances in kilometers.

I 3.

There are no commercial facilities.

4.

For conservatism. It is assumed that there is a vegetable garden at the nearest residence.

5.

For water sectors, '". is used where greater than the distance to the shoreline, g

G.

Shortest site boundary. distance in any landward sector.

4 l

e 1

i 1

i A:sseidmen t 8 1 of 1 December 1984 l

TABLE 2.1-23 AVERAGE DAILY TRAFFIC COUNTS IN THE VICINITY OF MILLSTONE 3 Location of Average Daily Traffic Count Number of vehicles Route 52, north of Interstate 95 (I-95) 7,400 I-95, east of junction of Route 52 30,100 I-95, between Interchanges 72 and 73 29,100 Route 156, at Niantic River Bridge 9,900 Route 156, east of Gardner's Wood Road 8,200 Route 213, south of Route 156 8,400 Route 213, near Goshen Road 2,300 U.S. Highway 1 at Cross Road 8,900 Route 161, south of I-95 17,900 Source: Connecticut Depar it of Transportation,

Hartford, Connecticut, Average saily Traffic Counts, 1980 (Telecon, C.S. Ellis (SWEC) to A. Zevin, November 5, 1981)

O 1 of 1

m i

MNPS-3 EROLS I

2.2.1.3 Millstone Point Fauna Faunistic studies of Millstone Point were conducted concurrently with floral-investigations in 1973-74 (Figure 2.2-1).

The objectives of the program were:

.1. -

To identify migrant and/or resident population of mammals, ll

birds, reptiles and amphibians, and terrestrial

}

invertebrates in the vicinity of the site 2.

To determine the general distribution and interrelationships of existing wildlife populations t

3.

To assess the utilization of existing wildlife habitats by i

birds and mammal populations 4.

To determine existing effects cf natural arid man-induced factors on communities in the area i

Results of the-faunal investigations are preanted.in detail in the Summary Report, 1974 (NUSCo. 1974). Thus, only < brief summary of the data is presented herein.

2.2.1.3.1 Mammals Eight small mammal species totaling 454 specimens were captured from

-May to October 1973 (Table 2.2-2).

The white-footed mouse

.(Peromyscus leucopus) was the.most abundant and widespread small

(

mammal collected during the sampling period.

This species was l

collected in each community sampled and accounted for 61.0 percent of the total mammal catch (NUSCo.

1974; Industrial Bio-Test l

Laboratories, Inc. 1974b).

Meadow voles (Microtus pennsylvanicus)

L

. ere most abundant in October and constituted. 29.7 percent of the w

total mammal catch.

Less abundant species included the shortail shrew (Blarina brevicauda),-meadow jumping mouse

(_Zapus hudsonius),

Norway rat (Rattus. norvegicus)', masked shrew (Sorex cinereus),

i eastern chipmunk (Tamias striatus) and pine vole (Pitymys pinetorum).

L

' Data on sex,- weight and selected body measurements of individual l

species were.also collected (NUSCo. 1974).

Habitat Utilization, defined -as the proportion of animals ' captured l-

-within each habitat type, was highest in the beach community and

' lowest in the xeric hardwood forest (Community 6).

The, relative

. abundance of small mammals increased significantly (p <0.05) from May to July. Increases were greatest in the beach and managed recreation area,- beach community, and.the transmission line corridor (NUSCo.-1974).

Observations and/or sign of seven larger mammals were recorded during j

the 1973-74 field survey

-(Table 2.2-3).

Cottontail rabbits-l (Sylvilagus spp.), eastern gray squirrels (Sciurus carolinensis) and L

woodchucks (Marmota monax) were common. Visual observations or signs L

of cottontail rabbits were recorded in all habitats, with the exception of the coastal marsh (Community 4).

Cottontails were the s

-2.2-7 1

Is

~

_... _. - _. -. - ~,. - ~ -. _

MNPS-3 EROLS most frequently observed larger mammal, accounting for 47 percent of the sightings (NUSCo. 1974; Industrial Bio-Test Laboratories, Inc. 1974b).

The eastern gray squirrel was recorded in three communities but observations were largely restricted to the mesic hardwood stand (Community 2) and xeric hardwood stand (Community 6).

Woodchucks were also abundant onsite, occurring in the riparian hardwood stand (Community 3),

the transmission corridor (Community 5), the abandoned nursery (Community 7) and the beach (Community 9).

Other species recorded from the Millstone Point site included raccoon (Procyon lotor), starnose mole (Condylura ciristata),

muskrat (ondatra zibethicus) and white-tailed deer (Odocoileus virginianus).

Only one white-tailed deer was recorded from the site; however, suitable habit for deer is present, particularly along the forest borders.

2.2.1.3.2 Birds Observations of 3,692 birds comprising 106 species were recorded along nine transect routes during the 1973-74 survey (NUSCo. 1974; Industrial Bio-Test Laboratories, Inc. 1974b). Resident status of these species included 39 permanent residents, 42 summer residents, 10 winter residents and 11 migrants (Table 2.2-4).

During the spring and fall migration periods, 63 and 55 species, respectively, were sighted.

Sixty-two species were recorded during the summer survey and 35 were observed during the winter census.

Predominant birds sighted during the May migration period included red-winged blackbirds (Agelaius phoeniceus),

common grackles (Quiscalus quiscula), barn swallows (Hirundo rustica) and starlings (Strunus vulgaris). Common nesting species observed during July included black ducks (Anas rubripes), blue jay (Cyanocitta cristata),

American robin (Turdus migratorius),

and song sparrow (Melospiza melodia).

In October, double-crested cormorants (Phalacrocorax auritus), Canada geese (Branta canadenses), herring gulls (Larus argentatus),

starlings and American goldfinches (Spinus tristis) were most frequently sighted.

Red-breasted merganser (Mergus serrator),

herring gulls, ring-billed gulls (Larus delawarensis), and song sparrows were most prevalent durring the January census.

Raptorial birds observed in the Millstone Point area included Cooper's hawk (Accipiter cooperii),

red-tailed hawk (Beuteo jamaicensis), broadwinged hawk (B.

platypterus), osprey (Pandion haliaetus), and American kestrel (Falco sparverius).

The osprey is the most conspicuous raptor on Millstone Point.

NUSCo.,

in cooperation with the Connecticut Department of Environmental Protection, has maintained nesting platforms onsite 8

since 1969. As of the end of 1984, five artificial nesting platforms had been established. Young osprey were successfully produced every year during 1974-1980 and in 1981 osprey in two nests successfully Amendment 8 2.2-8 December 1984 Eju

[

MNPS-3 EROLS produced' a total of four fledglings.

In the period of 1969-1980, 8

osprey produced 32 offspring using the nests onsite (NUSCo 1981a).

The. quarry nest was investigated in 1976, 1977, and 1978 by adult ospreys but remained unoccupied. The highly successful wildlife area l 8

nest, however, continues to assist in sustaining the Osprey population of Connecticut.

During the 1977 reconnaissance of the Millstone Point site, bird observations were made in the vicinity of the wildlife management pond.. Most noteworthy was the presence of great blue herons -(Ardea herodius), black-crowned night herons (Nycticorax nycticorax),

two

--adult whistling swans (Olor columbianus) and five juveniles, belted kingfisher (Megaceryle alceyon), and pied-billed grebe (Podilymbus podiceps). A number of ducks and a.large number of passerine species were also noted, suggesting that the wildlife management area a

continues to be ' a highly productive area with respect to avian species.

2.2.1.3.3 Reptiles and Amphibians During the 1973-74 field survey, five species of amphibians and one species of reptile were observed in the Millstone Point area (Table 2.2-6).

One northern two-lined salamander-(Eurycea bislineata) was captured m

at the edge' of the stream in the riparian hardwood stand (Community 3).

One American toad (Bufo americanus) was recorded from

~

the xeric hardwood stand (Community 6).

Green frogs-(Rana clamitans) were the most abundant amphibian onsite, observed most frequently in the riparian hardwocds stand, coastal marsh (Community 4),

and the abandoned nursery -(Community 7).

Leopard frogs (Rana pipiens) were recorded from the transmission line corridor (Community 5) and the abandoned nursery, while wood frogs (Rana sylvatica) were observed in the old field (Community 1) and the two hardwood stands (Communities 2 and 6).

With respect ~ to -reptiles, the eastern garter snake (Thamnophis sirtalis) was recorded' from the riparian hardwood stand and transmission line corridor. This species occurs in a wide. variety of habitats.

Terrestrial Invertebrates r.

Two hundred thirty-seven specimens representing 2 classes, 11 orders, and 40 families of terrestrial invertcbrates were collected from the old field (Community.1)- and riparian hardwood stand (Community 3) during the 1973-74 field survey. Plant bugs, dance flies, midges and spiders -were the species most commonly collected. The relative abundance.and diversity of invertebrates were greater in the old field than in the riparian hardwood stand.

AV

' Amendment 8 2.2-9 December 1984

MNPS-3 EROLS 2.2.1.4 Environmental Stresses During the 1972-1974 terrestrial field studies, ground surveys were made to determine the major environmental stresses (both natural and man-induced) on native plant communities of the Millstone Point site.

The most common stresses were caused by lumbering, insect infestations,

flooding, fires, hurricanes, gales, and by the conversion of native communities to farm land, residences, commercial and industrial developments, and transportation networks.

(NUSCo.

1974). Natural stresses caused by several topographic, edaphic, and physical factors associated with the coastal environment were also present (NUSCo. 1974).

The 1977 reconnaissance of the site revealed very little change in community structure since the 1973-1974 survey. No evidence of major natural environmental stresses was observed. However, man-induced perturbations, associated with the construction of Millstone 3, were noted which may have affected the quality of the terrestrial communities adjacent to the construction site.

Inadequate sediment

barriers, in conjunction with -heavy precipitation in October, resulted in a small deposition of silt in the marsh west of the construction site and in the mixed hardwood stand west of the batch plant. Several small areas of unchecked erosion due to heavy rainfall and imprcper stabilization of sicpes vcre also noted on site.

In addition, storage of fill material in the storage area west of the craft parking lot had led to a depositing of fill in the marsh and woods immediately west of the storage bins.

Subsequent to an Environmental Site Audit, these construction-related problems were rectified. New sediment barriers were installed and slopes were stabilized by seeding (section 4.1.4).

2.2.1.5 Endangered Species No rare or endangered species of flora or fauna listed by the U.S.

Department of Interior, Fish, and Wildlife Service as endangered (U.S.

Department of Interior 1979) were observed during the field investigations or are likely to permanently inhabit the Millstone Point site.

With respect to mammals, the Indiana bat (Myotis sodalis) is the only potentially occurring endangered species.

The geographic range of this bat extends into connecticut (Burt and Grossenheider 1964; Hall and Kelson 1959).

It is known that the Indiana bat requires roosting caves in winter; however, little is known about its habitat requeaements in the summer. Hollow trees and man-made structures are thought to provide suitable summer habitat (Burt and Grossenheider 1964). Thus, it is conceivable that if the Indiana bat is present in Connecticut during summer months, it may find a suitable habitat at Millstone Point.

However, the lack of limestone caves on the Millstone site suggests that favorable winter roosting habitat is not available.

With respect to avian species, two species, the bald eagle (Haliaeetus leucocephalus) and Artic peregrine falcon (Falco peregrinus tundrius) may be found in Connecticut. The bald eagle may 2.2-10

HNPS-3 EROLS TABLE 2.3-38 MEDIAN (50 PERCENT) FUMIGATION X/Q VALUES (x10-s sec/m3) l2 AT THE LOW POPULATION ZONE

' ~

FOR ELEVATED RELEASE DOSE CALCULATIONS (Millstone 1 Stack) l2 f

Downwind Distance Sector (meters)

X/Q N

.3862 5.25 NNE 3862 5.61 NE.

3862 3.77 ENE 3862 3.80 E

3862 3.52.

ESE 3862 3.01 SW 3862 2.93 I

WSW 3862 3.20 W

3862 3.10

_ NW 3862 4.94 W

NW 3862 5.96 NNW 3862 6.47 NOTE:

1 X/Q'_ values -in this table are not used for any dose calculations-but are presented for information only.

V Amendment 1 1 of l' February 1983

MNPS-3 ERILS TABLE 2.3-39 RA080 LOGICAL PATHWAY ANALYSES DISTANCES (to 8 km - 5 miles) (a) FOR MILLSTONE 3 VENTILATION VENT AND MILLSTONE 1 114-METER ( 375-F00T) STACK ( IN PARENTHESES) (g)

Nearest Nea rest Nea re s t Nea res t Nea rest Heat M i l k Coa t Nearest Residence Vegetable Ga rden Site Bounda ry Hea re s t Land Milk Cow Animal (b) km (mile) km (mi!el km (mile) (c) km (mile) (d.e) km (mile) (f) 0.92 (0.58) 0.92 (0.58) 0.92 (0.58) 0.92 (0.58) 3.2 (2.0)

(NNW-1.19 (0.74))

(NNW-1.19 (0.74))

(NNW-1.19 (0.74))

(NNW-1.19 (0.74))

N 1.55 (0.97) 1.55 (0.97) 1.55 (0.97) 1.55 (0.97)

NNE 2.9 (1.8)

(N-1.73 (1.08))

(N-1.73 (1.08))

(N-1.73 (1.08))

(N-1.73 (1,08))

l8 0.84 (0.53) 0.84 (0.53) 0.84 (0.53) 0.84 (0.53)

(NNE-0.81 (0.51)

(NNE-0.81 (0.51)

(NNE-0.81 (0.51)

(NNE-0.81 (0.51)

NE 0.81 (0.51) 0.81 (0.51) 0.60 (0.38) 0.60 (0.38)

ENE 3.2 (2.0)

(NE-0.78 go.49))

(NE-0.78 (0.49))

(NE-0.50 (0.31))

(NE-0.50 (0.31))

1.30 (0.81) 1.30 (0.81) 0.60 (0.38) 1.30 (0.81)

E (ENE-1.10 (0.69))

(ENE-1.10 (0.69))

(ENE-0.35 (0.22))

(ENE-1.10 (0.69) 1.69 (1.06) 1.69 (1.06) 0.60 (0.38) 1.69 (1.06)

ESE (E-1.40 (0.88))

(E-1.40 (0.88))

(ESE-0.28 (0.18))

(E-1.40 (0.88))

33.0 (20.6) 33.0 (20.6) 0.60 (0.38) 33.0 (20.6)

( SE-33.0 ( 20.6))

(SE-33.0 (20.6))

(SE-0.28 (0.18))

(SE-33.0 (20.6))

SE 22.2 (13.9) 22.2 (13.9) 0.63 (0.39) 22.2 (13.9)

(SSE-22.2 (13.9))

(SSE-22.2 (13.9))

(SSW-0.44 (0.28)

(SSE-22.2 (13.9))

SSE 16.1 (10.1) 16.1 (10.1) 0.60 (0.38) 16.1 (10.1)

S (S-16.1 (10.1))

(S-16.1 (10.1))

(SSW-0.42 (0.26))

(S-16.1 (10.1))

18.3 (11.4) 18.3 (11.4) 0.60 (0.38) 18.3 (11.4)

(SSW-18.3 (11.4))

(SSW-18.3 (11.4))

(SW-0.48 (0.30))

(SSW-18.3 (11.4))

SSW 3.38 (2.11) 3.38 (2.11) 0.60 (0.38 3.38 (2.11)

(WSW-3.48 (2.18))

(WSW-3.48 (2.18))

(WSW-0.66 (0.41))

(W6W-3.48 (2.18))

SW 3.05 (1.91) 3.05 (1.91) 0.60 (0.38) 3.05 (1.91)

(W-3,08 (1.93))

(W-3.08 (1.93))

(W-0.77 (0.48))

(W-3.08 (1.93))

WSW Amendment 8 1 of 3 December 1984 O

O O

' ?l 3

MNPS-3 EROLS

~ TABLE 2.3-39 (Cont)

Nea rest Nea re s t -

Nea rest Nea rest Nea rest -

Meat.

Milk Goat Nearest Residence Vegetable Garden Site Bounda ry Nea rest Land -

i 1

' Milk Cow Anic?* l'ul km fallet km fallet-km failel fc) km failel (d.el km f ailel fil r

i 2.70 (1.69) 2.70 (1.69) 0.60 (0.38)

. (NNW-2.66 (1.66))

2.70 (1.69)

.W 4.0 (2.5)

(NNW-2.66 (1.66))

(NNW-2.66 (1.66))

(W-0.85 (0.53))

f 1

2.31-(1.44) 2.31-(1.44) 0.60 (0.38)~

2.31 (1.44) a

}

WNW (NNW-2.56 (1.6))

(NNW-2.56 (1.6))

(WNW-0.90 (0.56))

(NNW-2.56 (1.6))

l8 i

j 0.68 (0.43) 0.68 (0.43) 0.60 (0.38) 0.68 (0.43) i NW 4.8 (3.0)

( NW-1.00 (0.63 ) )

( NW-1. 00 ( 0. 63 ) )

( NW-0. 92 ( 0. 58 ) )

(NW-1.00 (0.63))

-[

0.69 (0.43) 0.69 (0.43) 0.69 (0.43) 0.69'(0.43)

NNW (NNW-1.01 (0.63))

(NNW-1.01 (0.63))

(NNW-1.01 (0.63))

(NNW-1.01 (0.63))

I Radiological Pathway Analyses Distance (to 8 km - 5 miles) l for Millstone. 3 Turbine Building Vent j

r 4

i N

3.2 (2.0) 0.92 (0.58) 0.92 (0.58) 0.92 (0.58 0.92 (0.58) f-NNE 2.9 (1.8) 1.58 (0.99) 1.58 (0.99) 1.58 (0.99) 1.58 (0.99) 0 j

NE

'O.87 (0.54) 0.87 (0.54) 0.87 (0.54) 0.87 (0.54) f.

L ENE 3.2 (2.0) 0.83 (0.52) 0.82 (0.52) 0.62(d) (0.39) 0.62 (0.39) 1 b

j E

1.32 (0.83) 1.32 (0.83) 0.62.(0.39) 1.32 (0.83)

{

ESE 1.70 (1.06) 1.70 (1.06)-

0.62 (0.39) 1.70 (1.06)

I i

l SE

-~

33.0 (20.6) 33.0 (20.6) 0.62 (0.39) 33.0 (20.6) 4-t i

SSE 22.2 (13.9) 22.2 (13.9) 0.62 (0.39) 22.2 (13.9) i A

1 N

j S

16.1 (10.1) 16.1 (10.1) 0.62 (0.39) 1.6.1 (10.1) 7 SsW 18.3 (11.4) 18.3 (11.4) 0.62 (0.39) 18.3 (11.4) l sW 3.36 (2.10) 3.36 (2.10) 0.62 (0.39) 3.36 (2.10)

}

WSW 3.03.(1.89) 3.03 (1.89) 0.62 (0.39) 3.03 (1.89) 1 I

i I

i' Amendment 8 2 or 3 ~

December 1984 1

1

-~~-

MNPS-3 ECOLS TABLE 2.3-39 (Cont)

Nea re st Nea res t Nea re s t Nea rest Nea rest Heat Milk Goat Nea rest Residence Vegetable Ca rden Si te Bounda ry Nearest Land Milk Cow Animal (b) km faitel km imilen km (milel fcl km (mitel (d.el km (milel fri 4.0 (2.5) 2.69 (1.68) 2.69 (1.68) 0.62 (0.39) 2.69 (1.68)

W 2.31 (1.44) 2.31 ( 1. 4 '4 )

0.62 (0.39) 2.31 (1.44) 8 WNW 4.8 (3.0) 1.01 (0.63) 1.01 (0.63) 0.62 (0.39) 1.01 (0.63)

NW 0.69 (0.43) 0.69 (0.43) 0.65 (0.41) 0.69 (0.43)

NNW NOTES:

(a) All distances are in kilometers (miles)

( b ) The re a re no comme rc ia l racilities within 8 km (5 niles)

(c) for conse rva t i sm, it is assumed that there is a vegetable garden greater than 500m (5,380 ft') in a rea at the nea rest 8

re s idence (d) Shortest site boundary distance in any landward sector (e) For water sectors, (d) is used where greater than the distance to the shoreline (r) For waterfront sectors, the distance to the land across the body or water is applied (g) EX.

Location f rom the MP-1 stack co rrespond i ng to the nea re st residence 0.92 km (0.58 miles) north or the HP-3 ventilation vent i s NNW-1.19 km (0.74 mi les). For no rma l ope ra t iona l effluent releases. the MP-3 vent will be the prima ry dose contributor. Howeve r, for calculation or maximum individual doses, the additional inc rementa l dose f rom the corresponding MP-1 stack location is added to the MP-3 vent doses.

Amendment 8 3 or 3 December 1984 O

O O

MNPS-3 EROLS l'-_

TABLE 2.3-44 D)

ANNUAL AVERAGE X/Q VALUES (sec/m3) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR MILLSTONE 1 STACK RELEASE Vegetable Sector Resident Garden Milk Cow Hilk Goat N

3.48E-8*

3.48E-8 2.09E-8 NNE 3.62E-8 3.62E-8 5.50F-8 NE 5.90E-8 5.90E-8 ENE 5.60E-8 5.60E-8 3.80E-8 E

4.05E-8 4.05E-8 ESE 3.41E-8 3.41E-8 SE 3.98E-9 3.98E-9 SSE 4.56E-9 4.56E-9 S

3.50E-9 3.50E-9 SSW 3.67E-9 3.67E-9 SW 1.17E-8 1.17E-8

  • WSW 1.45E-8 1.45E-8 W

3.48E-8 3.48E-8 1.00E-8 WNW 3.48E-8 3.48E-8 NW 3.35E-8 3.35E-8 2.31E-8 l

NNW 3.48E-8 3.48E-8 NOTES:

[

  • E-8 = 10-s
    • No receptor within this sector l

' O Amendment 8 1 of 1 December 1984 L

HNPS-3 ER0LS TABLE 2.3-45 ANNUAL AVERAGE D/Q VALUES (m-2) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR MILLSTONE 1 STACK RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

7.05E-10*

7.05E-10 2.19E-10 NNE 5.82E-10 5.82E-10 6.23E-10 NE 1.28E-9 1.28E-9 ENE 2.00E-9 2.00E-9 7.39E-10 E

3.12E-9 3.12E-9 ESE 3.34E-9 3.34E-9 SE 3.01E-11

'3.01E-11 SSE 3.53E-11 3.53E-11 S

2.76E-11 2.76E-11 SSW 2.78E-11 2.78E-11 SW 3.34E-10 3.34E-10 WSW 4.22E-10 4.22E-10 W

2.55E-10 2.55E-10 2.76E-10 WNW 2.71E-10 2.71E-10 NW 1.13E-9 1.13E-9 1.38E-10 NNW 6.86E-10 6.86E-10 NOTES:

  • E-10 = 10-18
    • No receptor within this sector O

Amendment 8 1 of 1 December 1984

MNPS-3 EROLS

. TABLE 2.3-50

,g g

s.

's -,

ANNUAL AVERAGE X/Q VALUES (sec/m3) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR CONTAINMENT VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

1.22E-6*

1.22E-6 2.25E-7 NNE 6.82E-7 6.82E-7 6.59E-7 NE 1.95E-6 1.95E-6 ENE 2.61E-6 2.61E-6 4.37E-7 E

8.98E-7 8.98E-7 ESE 5.10E-7 5.10E-7 SE 8.77E-9 8.77E-9

.SSE, 1.22E-8 1.22E-8 S

1.23E-8 1.23E-8 SSW 1.14E-8 1.14E-8 SW

-1.13E-7 1.13E-7 WSW 1.12E-7 1.12E-7 W

1.36E-7 1.36E-7 7.22E-8 8

WNW 2.26E-7 2.26E-7 NW 7.55E-7 7.555-7 1.13E-7

'NNW 8.06E-7 8.06E-7 NOTES:

  • E-6 = 10-8
    • No_ receptor within this sector Amendment 8 1 of 1 December 1984

HNPS-3 EROLS TABLE 2.3-51 ANNUAL AVERAGE D/Q VALUES (m-2) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR CONTAINMENT VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

1.02E-8*

1.02E-8 6.39E-10 NNE 5.26E-9 5.26E-9 3.20E-9 NE 2.07E-8 2.07E-8 ENE 3.21E-8 3.21E-8 1.89E-9 E

1.23E-8 1.23E-8 ESE 7.35E-9 7.35E-9 SE 3.51E-11

'3.51E-11 SSE 4.04E-11 4.04E-11 S

3.75E-11 3.75E-11 SSW 3.11E-11 3.11E-11 SW 7.95E-10 7.95E-10 WSW 7.00E-10 7.00E-10 W

1.16E-9 1.16E-9 4.80E-10 8

WNW 1.40E-9 1.40E-9 NW 9.84E-9 9.84E-9 4.25E-10 NNW 8.76E-9 8.76E-9 NOTES:

  • E-8 = 10-8
    • No receptor within this sector Amendment 8 1 of 1 December 1984

MNPS-3 EROLS TABLE 2.3-56 ANNUAL AVERAGE X/Q VALUES (sec/m3) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATION FOR TURBINE BUILDING VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

2.79E-6*

2.79E-6 3.15E-7 NNE 1.34E-6 1.34E-6 8.43E-7 NE 5.53E-6 5.53E-6 ENE 6.51E-6 6.51E-6 6.09E-7 E

2.09E-6 2.09E-6 ESE 1.02E-6 1.02E-6 SE 1.01E-8 1.01E-8 SSE 1.58E-8 1.58E-8

\\~~

S 1.65E-8 1.65E-8

-SSW 1.50E-8 1.50E-8 SW 1.57E-7 1.57E-7 WSW 1.68E-7 1.68E-7 W

2.21E-7 2.21E-7 1.05E-7

%#Gf 3.81E-7 3.81E-7 NW 1.42E-6 1.42E-6 1.32E-7

- }DGi 2.43E-6 2.43E-6 NOTES:

  • E-6 = 10-s
    • No receptor within this sector O

Amendment 8 1 of 1 December 1984

MNPS-3 EROLS TABLE 2.3-57 ANNUAL AVERAGE D/Q VALUES (m-2) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR TURBINE BUILDING VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

1.74E-8*

1.74E-8 1.01E-9 NNE 8.32E-9 8.32E-9 3.86E-9 NE 4.35E-8 4.35E-8 ENE 5.87E-8 5.87E-8 2.81E-9 E

2.00E-8 2.00E-8 ESE 1.02E-8 1.02E-8 SE 3.78E-11

'3.78E-11 SSE 5.21E-11 5.21E-11 S

4.48E-11 4.48E-11 SSW 4.27E-11 4.27E-11 SW 8.42E-10 8.42E-10 WSW 8.70E-10 8.70E-10 W

1.64E-9 1.64E-9 6.48E-10 8 WNW 2.14E-9 2.14E-9 NW 1.15E-8 1.15E-8 4.59E-10 NNW 1.82E-8 1.82E-8 NOTES:

  • E-8 = 10-s
    • No receptor within this sector Amendment 8 1 of 1 December 1984

MNPS-3 EROLS TABLE 2.3-58 (V

GROWING SEASON X/Q VALUES (sec/m ) AT a

THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR MILLSTONE 1 STACK RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

4.55E-8*

4.55E-8 2.66E-8 NNE 4.77E-8 4.77E-8 6.71E-8 NE 7.58E-8 7.58E-8 ENE 3.97E-8 3.97E-8 3.53E-8 E

3.54E-8 3.54E-8 ESE 1.69E-8 1.69E-8 SE 3.36E-9 3.36E-9 SSE 3.86E-9 3.86E-9 O

S 2.98E-9 2.98E-9 SSW 3.47E-9 3.47E-9 SW 1.07E-8 1.07E-8 WSW 1.74E-8 1.74E-8 W

4.55E-8 4.55E-8 1.21E-8 ~

8 WNW 4.55E-8 4.55E-8 NW 4.27E-8 4.27E-8 3.01E-8 NNW 4.55E-8 4.55E-8 NOTES:

  • E-8 = 10-e

()

    • No receptor within this sector Amendment 8 1 of 1 December 1984

MNPS-3 EROLS TABLE 2.3-59 GROWING SEASON D/Q VALUES (m-2) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATION FOR MILLSTONE 1 STACK RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

9.06E-10*

9.06E-10 2.61E-10 NNE 7.14E-10 7.14E-10 6.77E-10 NE 1.45E-9 1.45E-9 ENE 1.72E-9 1.72E-9 5.44E-10 E

2.07E-9 2.07E-9 ESE 1.24E-9 1.24E-9 SE 1.90E-11

'1.90E-11 SSE 2.71E-11 2.71E-11 S

2.30E-11 2.30E-11 SSW 2.58E-11 2.58E-11 SW 2.99E-10 2.99E-10 WSW 5.06E-10 5.06E-10 W

3.20E-10 3.20E-10 3.28E-10 0

WNy 3.41E-10 3.41E-10 NW 1.54E-9 1.54E-9 1.67E-10 NNW 8.85E-10 8.85E-10 NOTES:

  • E-10 = 10-se
    • No receptor within this sector O

Amendment 8 1 of 1 December 1984

.~

l MNPS-3 EROLS TABLE 2.3-60 pV 3

GROWING SEASON X/Q VALUES (sec/m ) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS j

FOR CONTAINMENT VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

1.54E-6*

1.54E-6 2.97E-7 4

NNE 8.59E-7 8.59E-7 8.77E-7 NE 2.42E-6 2.42E-6 ENE 3.06E-6 3.06E-6 5.47E-7 E

7.26E-7 7.26E-7 ESE 3.59E-7 3.59E-7 SE 8.99E-9

'8.99E-9 SSE 1.20E-8 1.20E-8 S

1.21E-8 1.21E-8 i -

SSW 1.16E-8 1.16E-8 SW 1.10E-7 1.10E-7 WSW 1.12E-7 1.12E-7 W

1.67E-7 1.67E-7 8.87E-8 WNW 2.86E-7 2.86E-7 NW 9.08E-7 9.08E-7 1.50E-7 NNW 9.20E-7 9.20E-7 NOTES:

  • E-6 = 10-s
    • No receptor within this sector 3(d Amen &nent 8 1 of 1 December 1984 t

. _, ~.

MNPS-3 EROLS TABLE 2.3-61 GROWING SEASON D/Q VALUES (m-2) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATIONS FOR CONTAINMENT VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

1.13E-8*

1.13E-8 7.15E-10 NNE 5.78E-9 5.78E-9 3.86E-9 NE 2.21E-8 2.21E-8 ENE 3.06E-8 3.06E-8 1.77E-9 E

6.33E-9 6.33E-9 ESE 3.81E-9 3.81E-9 SE 2.71E-11 2.71E-11 SSE 3.01E-11 3.01E-11 O

S 3.02E-11 3.02E-11 SSW 2.88E-11 2.88E-11 SW 7.82E-10 7.82E-10 WSW 6.16E-10 6.16E-10 W

1.34E-9 1.34E-9 5.59E-10 WNW 1.65E-9 1.65E-9 NW 1.16E-8 1.16E-8 5.55E-10 NNW 9.31E-9 9.31E-9 NOTES:

  • E-8 = 10-s
    • No receptor within this sector O

Amendtrent 8 1 of 1 December 1984

NNPS-3 EROLS TABLE 2.3-62

-~

GROWING SEASON X/Q VALUES (sec/m3) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATION FOR TURBINE BUILDING VENTILATION VENT RELEASE Vegetable Sector Resident Garden

. Milk Cow Milk Goat N

3.75E-6*

3.75E-6 4.24E-7 NNE 1.75E-6 1.75E-6 1.13E-6 NE 7.33E-6 7.33E-6 ENE 7.86E-6 7.86E-6 7.62E-7 E

1.95E-6 1.95E-6 ESE 8.45E-7

-8.45E-7 SE

'1.07E-8 1.07E-8 SSE 1.61E-8 1.61E-8 S

1.72E-8 1.72E-8 SSW 1.54E-8 1.54E-8 i

l SW 1.56E-7 1.56E-7 WSW 1.76E-7 1.76E-7 I

W 2.67E-7 2.67E-7 1.27E-7 WNW 4.92E-7 4.92E-7

-NW 1.91E-6 1.91E-6 1.78E-7 NNW 3.19E-6 3.19E-6 i

i i

NOTES:

  • E-6 = 10-s i

i

    • No receptor within this sector l

fO I

Amendment 8 1 of 1 December 1984 f

I L_

HNPS-3 EROLS TABLE 2.3-63 GROWING SEASON D/Q VALUES (m-2) AT THE NEAREST SIGNIFICANT RECEPTOR LOCATION FOR TURBINE BUILDING VENTILATION VENT RELEASE Vegetable Sector Resident Garden Milk Cow Milk Goat N

2.14E-8*

2.14E-8 1.24E-9 bnG 9.77E-9 9.77E-9 4.75E-9 NE 5.22E-8 5.22E-8 ENE 6.06E-8 6.06E-8 2.88E-9 E

1.21E-8 1.21E-8 dSE 5.98E-9 5.98E-9 SE 3.01E-11 3.01E-8 SSE 4.21E-11 4.21E-11 5

3.86E-11 3.86E-11 SSW 4.10E-11 4.10E-11 SW 8.14E-10 8.14E-10 WSW 7.96E-10 7.96E-10 W

1.92E-9 1.92E-9 7.59E-10 0

WNW 2.66E-9 2.66E-9 NW 1.47E-8 1.47E-8 6.10E-10 Inni 2.21E-8 2.21E-8 NOTES:

  • E-8 = 10-s
    • No receptor within this sector O

Amendment 8 1 of 1 December 1984

MNPS-3.EROLS LIST OF EFFECTIVE PAGES fw]

L Page, Table (T), or Amendment Figure (F)

Number 3-1 thru 3-ii 0

3-iii 5

4 3-iv thru 3-v 0

3.1-1 0

F3.1-1 0

1 3.2-1.thru 3.2-3 0

j F3.2-1 0

F3.2-2 0

+

F3.2-3 0

3.3-1 2

-3.3-2 0

T3.3-1 (1 of 1) 8 F3.3-1 8

3.4-1 8

i 3.4-2 thru 3.4-2a 2

3.4-3 thru 3.4-5 0

3.4-6 8-T3.4-1 (1 of 1) 8 F3.4-1 0

F3.4-2 0

F3.4-3 0

F3.4-4~(2 sheets) 0 3.5-1 thru 3.5-5 0

3.5-6 4 7

3.5-7 0

3.5-8 7

3.5-9 thru 3.5-10 0

3.5-11.

7 3.5-12 0

T3.5-1 (1 of 1) 0

.T3.5-2 (1 thru 2 of-2) 0 T3.5-3 (1 thru 3 of 3) 0 T3.5-4 (1 of 1) 0

'T3.5-5 (1 of 1) 0 T3.5-6 (1 thru 2 of 2) 0 T3.5-7 (1 thru 2 of 2) 0 T3.5-8 (1 thru 3 of 3) 0 T3.5-9 (1 of 1) 0 T3.5-10 (1 of 1) 0 0

T3.5-11 (1 thru 2 of 2) 0 T3.5-12 (1 thru 3 of 3) 0 Amendment 8 EP3-1 December 1984

.= --- e---

..p r MNPS-3 EROLS LIST OF EFFECTIVE PAGES-(Cont)

. 'i Page, Table (T), or Amendment Figure (F)

Number

\\

T3.5-13 (1 thru 2 of 2) 0 i t.

T3.5-14 (1 thru 3 of 3) 0 T3.5-15 (1 of 1) 0 T3.5-16 (l'of 1) 0 T3.5-17 (1 of 1) 0 F3.5-1 0

g F3.5-2 0

F3.5-3 0

F3.5-4 0

3.6-1 7

3.6-2 thru 3.6-4 8

3.6-5 7

T3.6-1 (1 of 3) 8 T3.6-1 (2 thru 3 of 3) 7 T3.6-2 (1 of 1) 0 T3.6-3 (1 of 1)'

0 5

F3.641 3.7-1 8

3.7-2 thru 3.7-3 0

+

T3.7-L (1 of 1) 8 i

T3.7-2 il of 1) 0 T3.7-3 (1 of l~!

\\

0 f

s i

i U,

T3.7-4 (1 of i}(

i 0

4'S T3.7-5 (1 of 1) 0 k.: ' T3.7-6 (1 of 1) 0 4

4 3.8-It[.

0

w 3.9-1 thru 3.9-3 0

l s

F3.9-1 0

F3.9-2 0

5:

i A

)

i

)

s v,

' 'f

?

S Ii

.s N

g Amendment 8 EP3-2 December 1984 tic s

.S

=

MNPS-3 EROLS A

'd' TABLE 3.3-1' STATION WATER USE Maximum **

Average Minimum **

Item *

(gpm)

(gpm)

(gpm) 4 1.

Circulating water withdrawn 912,000 912,000 0

from Niantic Bay 2.

Service water withdrawn 29,385 29,385 10,883***

from Niantic Bay 8

3.

Total cooling water 941,385 941,385

-10,883***

4.

Total city water withdrawal 500 100' 0

1 5.

Water treating system 265 58 0

6.-

Domestic water system 235 42

-0 8

7.

Water treating waste 200 12 0

8.

Condensate polisher waste 200 14 0

Q 9.

Floor and equipment drain 100 40 0

[- (/

and miscellaneous waste g

10. Sanitary waste 9.7 -

2.4 -

0

11. Discharge'from radioactive 50 0.5 0

liquid waste treatment j

12J Total circulating water.

941,935 941,452 10,883 discharge NOTES:

  • Item numbers correspond to the numbers on Figure 3.3-1.
    • Neither maximum extremes nor are minimum extremes expected to occur

. simultaneously.

. *** Flows occur during a temporary shutdown.

i i

1-i i

Amendment 8 1 of 1 December 1984 i

,vr e-e-~ e r m --.--.- -

--..4.

+.- < - -, ~

.-~~,w,,.,-..~w.

---m.- -

-.e

4 8

9 1

3V N

O R

I E

M T

B ME A

M E

1 R T T

C S

S E

O Y D

T R

S S

E N

E DI W

TG RA M

O RA A R E

K YD T

E P OT N

SY SR PS A

N S

T O

D UA E E I

R E E

RS IN T

OG R L L N L A A

F A E C A E RN RW E R Z

EO E

TU TC D

IL T I A S AN N I E

V T

I T

E E A

A A W L L

3.W E MG E

L T R

WR 8

/ A FA S

T W

N N

T P

A U

P O

I 3N N I N

O L

O LW E

I E C

N OS E OT OT E

NI 3

WN S

RA M

I OU R T L TI R D

TM U

N

^

ALI VE G

E E

N I

TI NNP M

T I

FSMUEO A

OA AE E

S RT T

S W

DS A

A T

W E

R W

N T

E ES D

S H

MU I

A S

U W

I PO Q

L I E I

L G

O UN E

I P

QA N

E L T

E LV A

T D

L E

EI E

A N

T C

V R

S A S C

E T

N I

(U I

E D

O

)

A L O R

E R M WD T

N OD OA A

O LN LR W

C FA TE NG AA LS PU E

S OH i

T O

l l

T D

M N

R E

O E

T P

S S

T Y

E A

S R

R W

R E

R G

E N

T O

G T

I A

C1 N

A T

W A

S 3 I

W E

T C

R R

L M M

I E 3.

A E

T TM B

C SE U E I

E R

ME C T VT E

ET UL R S RS T

MS NB I Y EY A

OY A

CS SS W

DS M T E

O_

TN II E

TO

_zI R

N rC

/

E TAW Y

Y A

T B

I C

l j

1 1

e-

?-

.NNPS-3 EROLS 3.4 HEAT DISSIPATION SYSTEM sll

' 3.4' 1 ' Circulating Water System The Millstone 3 circulating water system (Figure 3.4-1) pumps salt water from Niantic Bay through a single-pass, triple shell condenser y

^ at ' a rate Jof. approximately 57' cubic meters /sec (2,000 cfs) to condense the' steam rejected by the main turbine.

The expected temperature. range of inlet water is between 0.6*C (33*F) and 24'C (75*F)..During its passage through the condenser, the circulating

'~

water > is heated approximately ~ 9.4*C (17'F) above its inlet.

temperature. The heated circulating water is then discharged into the quarry, located on the southeast extremity of Millstone Point,

- where it is combined with the_ discharge of Millstone 1 and 2.

The total combined flow-from the circulating water systems of all three Millstone units is approximately 118 cubic meters /sec (4,160 cfs),

t with. a maximum temperature rise at full load of about 11.7'c (21*F).

Figure 3.4-2 shows the overall plan for Millstone 3.

The circulating and service water pumphouse (Figure 3.4-3) is divided 4

into six bays which supply water to six circulating water pumps, four service; water -pumps, and two screenwash pumps. Flow to each bay leaves Niantic Bay-and passes through a trash rack and a traveling

- water screen in each bay. The average velocity within the pumphouse bays during normal operation at low water elevation is about 0.24' meters /sec (0.8 fps).

The trash racks are 4.9 meters (16 feet - 1 inch) wide and consist of-1.3-cm (1/2-inch) thick by 8.9 cm (3-1/2 inch) deep vertical steel bars installed 6.4 cm (2-1/2 inches) apart on centers at a slope of 5 on 1.

Two traversing trash rakes remove debris from the six trash-racks-by means of' motor operated cable hoists mounted on a steel superstructure (located at elevation 4.4 meters [14.5 feet] and deposit'the debris into trash carts for removal.

The traveling water screens are located upstream of the circulating water pumps and consist-of an : endless band of screening panels 4.3 meters 1(14 feet) wide by,0.61 meters (2 feet) high constructed of-

-No. 17 W&M gage 4.76 mm (3/16-inch) mesh copper cloth, which has a

.60-percent clear opening. Each bay has an overall 48-percent clear opening based on 100-percent clean screen.

The screens are automatically operated-according to the differential water. level across each screen. Screen wash water is discharged from the screen wash ~~ headers through high pressure spray nozzles at 6 kg/sq cm l8

'(85 psi) to clean debris off the screens into an upper trash trough and through-gentle wash spray nozzles at.0.7 kg/sq cm (10 psi) to flush organisms from the fish trays on' the acreens into

.a fish trough.

The debris is removed from the trash trough by a motorized conveyor' system to a trash ~~ container for removal.

The fish are carried from the fish trough to a fish sluiceway running from the pumphouse back to Niantic Bay.

Th'e circulating water flows from the six circulating water pumps to the condenser through six independent 183-meter (600-foot) long lAmenchnent 8 3.4-1 December 1984

MNPS-3 EROLS 213-cm (84-inch) diameter pipelines. The pipe is copper nickel clad steel inside the pumphouse, reinforced concrete outside the pumphouse, and concrete encased fiberglass inside the turbine building. The 213-cm (84-inch) diameter pipes transition to 244-cm (96-inch) diameter pipes just upstream of the condenser to improve flow characteristics inside the inlet water boxes. The condenser is a single-pass, 46,758 square meter (503,300 square foot), triple shell condenser with 28.6-mm (1-1/8 inch) diameter titanium tubes.

Each condenser shell is served by two circulating water pumps. The circulating water discharges from the condenser outlet water boxes through six independent 4.3-by 4.3-meter (50-foot) long 213-cm (84-inch) diameter pipelines. The pipes are copper nickel clad steel followed by concrete encased fiberglass which combine into one 4.3 by 4.3 meter (14 by 14 foot) reinforced concrete tunnel. An additional flow of approximately 114 cubic meters / min (30,000 gpm) from the service water system enters the tunnel immediately downstream of the condenser.

This 503-meter (1,650-foot) long tunnel runs to a seal pit structure at the quarry where the circulating water passes over a weir, into the quarry, and finally through a channel into Long Island Sound. The water discharges from the seal pit structure at an average velocity of about 0.76 meters /sec (2.5 fps).

A 152 cm (60-inch) diameter recirculating tempering line is provided from the upstream end of the discharge tunnel to the circulating and service water pumphouse to prevent ice formation around the intake during the winter.

The circulating water pumps are arranged in pairs such that the three h

pairs of pumps serve the three condenser shells, as shown on Figure 3.4-1.

Each pair of pumps is interconnected at the circulating and service water pumphouse by lateral passageways and at the condenser inlet and outlet water boxes by cross connecting 168-cm (66-inch) diameter motor operated valves. This arrangement provides for recirculation of the discharged water for back flushing of the condenser, and for biofouling control of the intake lines, and the pumphouse.

An Amertap tube cleaning system is provided for each condenser flow path to maintain a high level of tube cleanliness.

This eliminates the need for a chlorine injection system in the circulating water system.

However, in the event that thermal backwashing or tube cleaning proves unsuccessful, provisions for a chlorine injection system have been incorporated into the design of the circulating water system.

The existing service water chlorination system (Section 3.4.2) has been designed with the capability to retrofit a chlorination system to provide sequential, intermittent chlorination downstream of the traveling water screens in each circulating water intake bay. This system would back up the 2

Amertap system to provide condenser slime control.

Should a more extensive, continuous chlorination program be required to control QE291.8 hard shell fouling in the intake structure, additional chlorination equipment would be necessary. Chlorination frequency, duration, and concentration are indeterminate at this time, since this option is not expected to be added to the circulating water system. However, any chlorination program would be within the EPA Effluent Limitation Guidelines in 40 CFR 423.

Amendment 2 3.4-2 April 1983 l

~ v

~MHPS-3 EROLS N

size and continuous movement of the plume, there is very little probability-that large numbers of fish ~ concentrate in the plume.

observations made~ with gill. nets set in the plume during the operation ( oft Millstone

.1 and 2

support this conclusion

-(Section 2.2.2).-

No fish kills external to the quarry have been

_ reported to date.

i 3.4.2 Service Water System LThe service water system provides cooling water for heat removal from the reactor plant auxiliary systems during all. modes of operation and

-from. the turbine plant auxiliary systems during_ normal operation.

The service water-also supplies lubrication water for the service and circulating water pump bearings. The service water system is shown schematically on Figure;3.4-4.

The -service water system consists of two redundant flow paths. Each flow path is composed of two service water pumps and two service water strainers along with the necessary piping, heat exchangers, and g-valves.. The service water pumps and strainers are located in the circulating and service water pumphouse (Figure 3.4-3). Each service water pump supplies-50 percent of the required flow, and is rated at 57 cubic meters / min (15,000 gpm), 36.6 meters (120-feet) total dynamic head (TDH). Each service water pump is located in a separate pump bay between the traveling water screen and the circulating water pump.

.Each pair of pumps is isolated in a flood protected, seismically designed cubicle inside the pumphouse. The service water.

strainers are self-cleaning.and have a maximum particle size of 1.59 s

mm (0.0625 inch).

Debris removed from the strainers is discharged back to Niantic Bay.

The ' service water system draws cooling water from Niantic Bay, and 4

after passing it through various heat exchangers, discharges it - into Long. Island Sound via the circulating water system discharge tunnel.

Service water!-flow-and heat load requirements under all operating conditions are listed.'in' Table 3.4-1.

Under all operating conditions,

'except for -the minimum Jengineered safety features required during a design basis accident (DBA), coincident with a loss lF of power (LOP), one service water pump on each of the two trains is operating. Under normal operation, the relatively small flow and g

temperature rise of the se rvice water system does not cause any

-appreciable increase in the temperature of the circulating water at the quarry discharge.

Under accident operating conditions (DBA coincident with LOP),. the temperature increase in the service ' water

system'.is substantial ( however, impact of the service water flow (1/30 of circulating water flow) is not expected to be significant

'after discharge ~into Long Island Sound.

l:

'To prevent'biofouling within the service water system, a chlorination system is provided. The chlorination system is shown schematically

.on' Figure 3.4-4.

. Dilution wateri for the chlorination system is t

provided directly from the' service water system. upstream of the i

3' chlorine injection nozzles. Chlorine is added to the dilution water

i. :

e 3.4-5

MNPS-3 EROLS so that the chlorine concentration at the discharge is maintained at 8

a maximum of or less than 0.25 ppm measured at the discharge structure of the circulating water system.

Chlorine levels in the service water system will be manually determined at regular 8

intervals.

The chlorine injection concentration will be manually adjusted to maintain the system at a predetermined concentration.

l The chlorination system is operated continuously whenever the service 8

water system is in operation. The screen wash system can function as a backup source of chlorine dilution water in the event the service water supply line is out of service. Prr.'isions have been made to allow chlorination of the circulating water system; however, it is anticipated that this system will not be required unless the thermal backwash or condenser tube cleaning system proves unsuccessful in control of biofouling.

O i

t I

l till l

Amendment 8 3.4-6 December 1984 l

L

s h

. ~~)

~.

MNPS-3 EROLS TABLE 3.4-1, SERVICE WATER FLOW AND HEAT LOAD REQUIREMENTS.UNDER ALL OPERATING CONDITIONS DBA Coincident with LOP Minimum Normal Normal Operating Normal Unit

.. Safety Features Safety Features Hot Shutdown-Cold Shutdown Engineered Engineered Loss of Power (LOP)

Condition Cooldown Condition Flow (gpm) 29.385 27.426 15.037 32.505 24.958 10.883 Flow (Ib/hr) 1.516 x 10' 1.523 x 10' 8.3 x 10' 1.62 x 10' 1.18 x 10' 6.1 x 10' Heat Load 213.72 235.74 425.44 855.82 160.72 93.68 291.6 O' BTU i

(-

s;)L AT*c (F) 8.2 (14.8) s.t (16.3) 30.0 (54.0) 3o.5 (54.s) 8.1 (14.5) s.1 (16.3) b F

e

)

Amendment 8 1 of 1 December 1984

l MNPS-3 EROLS

~

3.6 CHEMICAL AND BIOCIDE WASTES

^

This section describes the nonradioactive liquid waste discharges from Millstone 3.

The chemical additions to water used for the station operation are presented in Table 3.6-1.

3.6.1 Makeup Water Treatment System 3.6.1.1. Makeup Demineralizer Regeneration The makeup demineralizer system for Millstone 3 consists of two trains, each having a capacity of 469 liters / min (124 gpm).

Each train consists of an activated carbon filter, a cation demineralizer, an anion demineralizer, and a mixed bed demineralizer, arranged in series.

An ultrafiltration system is provided upstream of the demineralizers to remove suspended solids and large organic molecules

-- to prevent fouling of the demineralizer resins.

Under average operating conditions, the demineralizers require chemical regeneration of-the resins of one of the two trains approximately every 3 days. The total regeneration waste volume per train is 7

approximately 190,000 liters (50,000 kallons).

J

-The main constituent of the regeneration wastes is sodium sulfate, resulting from the use of sulfuric acid and sodium hydroxide as the regenerating chemicals. Regeneration of one train of the cation and anion demineralizers requires the use of approximately 189 liters (50 gallons) of acid (66*Be) and 363 liters (96 gallons) of caustic O\\

(50-percent solution), respectively. Regeneration of the mixed' bed demineralizer resins requires approximately 30 liters.(8 gallons) of acid and 45 liters (12 gallons) of caustic.

The combined regeneration vastes contain approximately 3,230 ag/1 of sulfate and 1,460 mg/l of sodium (Table 3.6-2).

Regeneration wastes from the cation, anion,. and mixed bed demineralizers are neutralized to a pH between 6.0 and 9.0 and discharged to the circulating water system as discussed in Section 5.3.

The waste neutralization system is shown schematically on Figure 3.6-1.

The system is a batch neutralization process in.-which wastes are recirculated within the-waste regenerant neutralizing sump. Acid and caustic are added to the' sump, as required, to adjust the pH of the wastes to within a range of 6.0 to 9.0.

When the pH is within this range, the sump contents are discharged to 'the circulating water discharge tunnel.

3.6.1.2 ' Condensate Polisher Regeneration Condensate. polishing demineralizers maintain the condensate and feedwater system water quality.

A total of eight mixed bed demineralizers (seven operating and one spare), each with a capacity of.10,690 liters / min (2,825 gpm),

are provided to demineralize condensate flow. Each polisher requires periodic regeneration of the resins'with sulfuric acid and sodium hydroxide.

It is expected that under. average operating conditions, one polisher'per day will be regenerated. The total regeneration waste volume per polisher is Amendment 7 3.6-1 April 1984

MNPS-3 EROLS approximately 121,000 liters (32,000 gallons), of which 87,100 liters (23,000 gallons) are discharged to the chemical waste sump to be neutralized and monitored for radioactivity. The remaining 34,100 liters (9,000 gallons) are recycled to the water recovery tank.

The condensate polishing regeneration wastes are discharged after neutralization to a pH between 6.0 and 9.0 to the circulating water discharge tunnel.

The main constituent of these wastes is sodium sulfate, resulting from the use of acid and caustic for regeneration.

It is estimated that the concentrations of sulfate and sodium in the wastes discharged to the circulating water are 3,930 mg/l and 1,770 mg/1, respectively.

If the condensate polishing regeneration wastes are determined to be radioactive, they will be treated as discussed in Section 3.5.2.

The waste neutralization system for condensate polisher regeneration wastes is similar to that described for the makeup demineralizer except that two sumps are supplied and are equipped with a common radiation monitor to detect potentially radioactive waste.

3.6.2 Biocide Wastes The circulating water system (Section 3.4) is a once-through cooling system which draws water from the Niantic Bay area of Long Island Sound at a rate of approximately 56.6 cubic meters /sec (2,000 cfs).

This water passes through the main condenser, which condenses steam exhausted from the turbine generator.

Physical and chemical characteristics of Long Island Sound water are discussed in Section 2.4 and Section 5.3.

The six circulating water pumps are arranged in pairs such that the three pairs of pumps serve the three condenser shells (Section 3.4).

Interconnection of each pair of pumps provides recirculation of the discharged water for backflushing of the condenser and for biofouling control of the intake lines and the pumphouse.

A mechanical condenser tube cleaning system (Amertap),

employing sponge rubber

balls, provides for control of biofouling in the condenser.

Chlorination of the circulating water for biofouling control is not anticipated.

J The service water system is a once-through cooling system which draws water from Long Island Sound at a rate of 1.87 cubic meter /sec (66 cfs). This water cools the components and heat exchangers in the engineered safety features building, control building, auxiliary building, turbine building, and other unit structures. After passing through these heat exchangers, the service water is discharged to the circulating water discharge tunnel, where it is mixed with the circulating water and discharged to the quarry located on the southeast extremity of Hillstone Point.

A gaseous chlorine solution is injected into the service water system 8

to control biofouling. The service water is chlorinated continuously for the control of mussels. A 2-year study of Millstone Units 1 and Amendment 8 3.6-2 December 1984

HNPS-3 EROLS O

2 is ongoing to determine the minimum amount of chlorine required to 8

prevent macrofouling.

Chlorination is controlled by grab sample monitoring such that the concentration of free available chlorine at the point where the mixture of service water and circulating water is 291.9 discharged to the quarry is maintained at a maximum of or less than 0.25 ppm.

After mixing with the quarry water, the concentration of total residual chlorine is reduced to a concentration below l8 detectable limits (i.e.,

less than 0.05 ppm).

In addition, the chlorine demand of the circulating water will further reduce the free residual chlorine concentration below that which would occur through dilution alone.

It is estimated that approximately 26,000 kg/yr 8

(57,000 lb/yr) of chlorine (as Cl ) will be used for service water a

chlorination.

3.6.3 Floor and Equipment Drainage Radioactive and potentially radioactive floor drainage is conveyed to the liquid radwaste treatment system (Section 3.5).

Nonradioactive floor and equipment drainage, resulting from pump seal leaks, pump seal and bearing water, floor washing, etc, is discharged to the yard storm sewer.

Oil contaminated floor drainage is conveyed to oil / water separators before discharge. The oil removed is collected in drums and hauled offsite for recycle or disposal. The amount of floor drainage discharged to the yard storm sewer on a daily basis is variable. There are three oil / water separators, each having a design capacity of 379 liters / min (100 gpm),

for the Millstone 3 plant areas.

Oil and grease concentrations in the separate effluent are limited to 10 mg/1, average and 20 mg/1, maximum.

3.6.4 other Liquid Wastes 3.6.4.1 Steam Generator Blowdown The design of the steam generator blowdown system provides a means of controlling the suspended solids concentration and the chemical composition of the steam generator shell water.

The system is capable of blowing down water from each of the four steam generators at various blowdown rates up to a maximum of 341 liters / min (90 gpm) per steam generator. Blowdown from each steam generator is conveyed to the blowdown flash tank in which pressure is maintained at a point slightly above the normal operating pressure of the fourth point feedwater heater shells. Characteristics of steam generator blowdown are presented in Table 3.6-3.

Steam from the flash tank is conveyed to the feedwater heaters. The remaining liquid in the flash tank drains by pressure differential to the condensate side of the condenser. Contaminants are removed from

.the liquid in the condensate polishing demineralizers, which are located downstream of the condenser.

By using the above system, steam generator blowdown will not be discharged to the environment under normal plant operating conditions. During an extended plant outage, the steam generator shells may be drained through the blowdown lines to the condensate polishing system vaste Amendment 8 3.6-3 December 1984

i MNPS-3 EROLS neutralization sump or, if required, to the low level waste drain j

tanks in the liquid radwaste system (Section 3.5).

3.6.4.2 Low Level Waste Drain Tank Approximately 473,000 liters (125,000 gallons) of distillate are discharged, on an annual basis, to the circulating water discharge tunnel from the boron evaporator for tritium control. This waste is initially stored in the 15,000-liter (4,000-gallon) low level waste drain tank prior to discharge to the circulating water. The waste is released from the low level waste drain tank at a rate of 189 liters (50 gpm) on an average of once every 18 days, l

The bulk of the discharges occurs during de 6 weeks prior to refueling. Distillate from the boron evaporator is treated using the boron demineralizers, boron demineralizer filter, and the effluent filters. Boron is the only constituent in this.aste.

Potentially radioactive floor and equipment drainage is collected and fed into the low level waste drain tanks via the aerated drains system and discharged to the circulating water at a rate of 189 liters (50 gpm) for approximately 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> on an average of once every month.

Contaminated shower drainage is also collected in the low level waste drain tanks and demineralized and discharged to the circulating water at 189 liters (50 gpm) in a rr.anner similar to the boron recovery evaporator distillate.

In both cases, the main contaminants are detergents from showers and floor washes.

Approximately 1,290 liters (340 gallons) of leakage from the reactor coolant system are assumed to occur on an annual basis. This leakage is diluted by washing down for decontamination purposes and further diluted in the low level waste drain tanks by other equipment and floor drainage.

Small quantities, less than 1 ppm of lithium hydroxide used for pH control, could be released from this source.

3.6.4.3 Waste Test Tank Discharges The high level radioactive liquid waste treatment system is described in Section 3.5.

Distillate from the waste evaporators is conveyed to the 5aste test tank and discharged after demineralization to either primary grade water storage or to the circulating water discharge tunnel, depending on the plant water balance.

The waste evaporators are designed assuming that all distillate will be discharged to the circulating water.

Whenever steam generator leaks exceeding the maximum allowable leak occur, the steam generator blowdtwn is processed by the waste evaporator.

The f:)llowing are the maximum amounts of liquids handled by the waste evaporators annually:

O Amendment 8 3.6-4 December 1984

n i

g.

gg.-_

fd

(

()/

<c aINPS-3 EROLS TABLE 3.6-l..

s

  • CHENICAL ADDITIONS-TO WATER USED FOR STATION OPERATION Chemical Use and Reason for Use Estteated IIonthly Quantttles (Ib/ano)

Frequency of Sveten Involved

.or Source of Chemical Addltton to System

.Statton Discharoe Chemical Additton, Average

.Maxlaum 1Averaos Maximum Soron (as R):

Reactor coolant Solubte neutron 20.000 lb/yr NA 0.86 O.17 lb/ day NA '

system adsorber Chromates (as K CrO.):

-l 8 Neutron shield-Corroston control 10 lb/yr NA None None NA tenk cooIing 8

Ammonia (as NH3) (28%):

Auxiltary steam Corrosion control 6

12 None None Continuous l

j and condensate

$ team ams power Corrosion controf 26.100 27.900 None None Continuous conversson 0

i Mydrarine (as N H.) (35%):

Reactor plant Corroston centroI-90 Ib/yr NA None None NA Co p t Cooling water. charging pumps cooling, safety injection pumps cooIing Aux 11Iacy steam

. Corrosion centrol 62.5 125 None None Continuous.

and condensate Steam and power Corroston control 735 870 None Notw Continuous conversion Chilled water Maintain pH; 7.5 12.5

.None None Once per day system control O Chlorine (as Cle):

8 Service teater systen Biofouting control 4.650 6.000 4.G50 6.000 continuous Amenement 8 1 of 3 December 1984

MNPS-3 EROt.S TABLE 3.C-t (Cont)

Cnemical Use and Reason for Use Estimated Monthly Quantittos (Ib/mo)

Frequency of System Involved or Source of Chemical Addition to System Station Discharge Chemical Addition Averacre Maxlaum Average Max 1 mum Sodium Hypochlortte (as C1, (15%):

Makeup ultraftitration Ultrafiltration 1.070 4.270 1.070 4.270 Once per day system cleaning cycle sulfuric Acid (as lie 50.)

(100%):

Once every 3 days Makeup deetnereltzer Regeneration of 7.962 15.924 egstpoent ton exchange resins 6 times per week Condensate poleshIng Regeneration of 19.t10 38.220 stued bed son euchange resins 7

Sodium Pt orentoe f

(as NaO68) (50%):

Once every 3 days Makeup dominerallrer Regeneration of 13.650 27.300 equipment ton exchange resins G tsmes per week Condensate polishing Regeneratson of 32.760 65.520 atwed bed son enchange resins Makeup ultra-pH adjustment NA NA NA NA As necessary filtration system t.Ime (as Ca(OH) ) {100%):

Condensate potIshing Regeneratson cf 400 3.200 400 3.200 Once every 4 days etwed bed ton exchange resins 7

oo sender:

Radtoacteve soled Waste solIdtfIcatton 32.500 lb/yr 40.000 lb/yr None None Once per year waste agent Dow Catalyst:

Radioacttve solid Waste 9ottdtfscatson 800 lb/yr 1.000 lb/yr None None Once per year waste agent Amendment 7 2 of 3 Aprii 1984 1

O O

O

~

r-y v,.

19 FPS-3 EROLS w

p 3.7 SANITARY AND OTHER WASTE SYSTEMS -

-(

SanitaryWasdes x

3.7.1 sanitary wastes from Millstone 3 are conveyed to the Town of

. aterford municipal sewer system via a pumping station and force W

,. p-main, located on the Millstone Site, which connect into the Town of Waterford municipal system.

A' raw - sewage analysis performed on a sample from the plant is presented in Table 3.7-2.

[

The ~ force main and pumping station are designed in compliance with the Connecticut Department of Environmental Protection standards and 8

the state of Connecticut Public Health Code.

-Based on a hydraulic loading of 25 gallons per capita per day and a three-plant population of 1,000 during normal plant operations, the estimated average daily sewage flow is 26,000 gallons per day.

The pumping station and force main have periodic preventive

, maintenance inspections and both have alarms signalled to a 24-hour manned station should a pumping problem occur.

3.7.2 Laboratory Wastes small quantities of laboratory wastes are discharged periodically to

(

the liquid waste tanks. These wastes consist primarily of reactor 4

and turbine plant samples, as well as small quantities of chemicals required for analytical testing of various plant systems. The wastes, are treated as described in. section~3.5 and are conveyed to'the liquid waste system prior to discharge.to the circulating water.

These wastes are directed to the auxiliary building contaminated waste sump and pumped to either.the low or to the high level waste drain tanks.

f 3.7.3. Auxiliary Boilers Two oil-fired auxiliary boilers will provide the Millstone 3 site with steam for space heating when tWe nuclear unit is not operating.

Auxiliary steam will only be required for outages occurring during the colder winter months. space heating is not necessary in the summer months.

l 1

e' Amendment 8 3.7 1 December 1984 4

V

~

IINPS-3 EROLS Millstone 3 refueling / maintenance outages will occur for approximately ten weeks (1,700 hours0.0081 days <br />0.194 hours <br />0.00116 weeks <br />2.6635e-4 months <br />) during the winter months. This time period is the estimated annual operating period for the auxiliary boilers. Both boilers will be operated simultaneously at 100-percent capacity, in order to provide sufficient steam to the site. Each boilet has a maximum firing rate of 78.3 x 108 Btu /hr.

No. 4 fuel oil will be supplied from two 91-cubic mette (24,000-gallon) tanks. Boiler and fuel parameters are listed in Table 3.7-3.

Emissions of particulates, sulfur dioxide (SO ), nitrogen dioxide 2

(NO ), carbon monoxide (CO), and total hydrocarbons from the combined 3

boiler system were calculated from boiler and fuel parameters and from EPA emission factors (EPA 1977).

Results for all pollutants were compared to applicable Connecticut standards (Table 3.7-4), and no violations were found (Connecticut Dept.

of Environmental Protection 1978).

Though the boilers are below the cutoff size requiring compliance with federal standards, boiler emissions do not exceed said requirements (EPA 1971).

3.7.4 Diesel Generators Two oil-fired diesel generators will provide emergency electricity when inplant outages occur. Each generator is capable of supplying 5,335 kWe.

The generators will operate on No. 2 diesel fuel oil supplied from two 121-cubic meter (32,000-gallon) storage tanks and two 550-gallon day tanks. Generator and fuel parameters are listed in Table 3.7-5.

Under testing conditions the diesels will not be operated simultaneously. Each diesel will be tested once a month for approximately three hours plus an additional 168 hours0.00194 days <br />0.0467 hours <br />2.777778e-4 weeks <br />6.3924e-5 months <br /> of annual maintenance testing.

The total annual operating period will be 408 hours0.00472 days <br />0.113 hours <br />6.746032e-4 weeks <br />1.55244e-4 months <br /> or 204 hours0.00236 days <br />0.0567 hours <br />3.373016e-4 weeks <br />7.7622e-5 months <br /> for each generator.

Connecticut emission regulations for fuel burning sources apply with the exception of NO, regulations for which diesel engines are exempt.

The diesel generators will not exceed the applicable Connecticut emission standards. Emissions of particulates, 50, NO,

CO, and 2

2 total hydrocarbons were calculated from generator and fuel parameters based on the generators operating at 100-percent load and from the manufacturer's emission factors (Colt 1982).

Emissions and the appropriate Connecticut emission regulations are listed in Table 3.7-6.

3.7.5 References for Section 3.7 Colt Industrien Operating Corp.1982. Letter from Olson, G.W.

(Colt) to Gardel, W. (SWEC). April 27, 1982.

Connecticut Department of Environmental Protection 1978. Abatement of Air Pollution. Section 19-508-1 to 100. Hartford, Conn.

Environmental Protection Agency (EPA) 1971. Standards of Performance for Fossil-Fuel Fired Steam Generators. 40CFR60, Washington, D.C.

3.7-2

i 3

l MNPS-3 EROLS TABLE 3.7-1 This table has been deleted 8

i r

i 1

i 4

4 f

t i

Amendment 8 1 of 1 December 1984

<^

l

-.,, _. _.....- ~.. _.. _ _. _ _, _... _,,.., _,. _ _ _ _. _ _ _.. _ _ _.. _,. _ _ _ _,, _. _ _..

, _ _.__._____ _.__._. __..__ ~.__

MNPS-3 EROLS TABLE 3.7-2 RAW SEWAGE ANALYSIS (1)

Concentration Parameter mg/l Total dissolved solids 743 Total suspended solids 112 Ammonia nitrogen (N) 76.7 Nitrite nitrogen (N) 0.0 Nitrate nitrogen (N) 0.17 Oil and grease 24.6 Chemical oxygen demand 240 Biological oxygen demand 140 (5-day BOD)

NOTE:

(18 Based on analysis of raw sewage sample collected on April 22, 1981, at the Millstone Plant j

l 1,

l O

l 1 of 1 l

MNPS-3 EROLS 4

'/~~N LIST OF EFFECTIVE PAGES i

s

'q,) ^

Page, Table (T), or Amendment Figure (F)

Number 5-1 thru 5-iv 0

5-v 5

5-vi thru 5-viii 0

5.1-1 thru 5.1-12 0

5.1-13 5

5.1-14 thru 5.1-50 0

5.1-51 5

i 5.1-52 thru 5.1-60 0

5.1 5 5.1-62 0

5.1-63 5

2 5.1-64 thru 5.1-79 0

T5.1-1 (1 of 1) 0 T5.1-2 (1 of 1) 0 T5.1-3 (1 of 1) 0 T5.1-4-(1 thru 2 of 2) 0 T5.1-5 (1 of 1) 0 T5.1-6 (1 thru 3 of 3) 0 T5.1-7 (1 of 1) 0

.y.

-T5.1-8 (1 of 1) 0 T5.1-9 (1 of 1) 0 T5.1-10 (1 of 1) 0 T5.1-11 (1 of 1) 0 T5.1-12 (1 of 1) 0 T5.1-13 (1 of 1) 0 T5.1-14 (1 of 1) 0 T5.1-15 (1 of 1) 0 T5.1-16 (1 of 1) 0 T5.~1-17 (1 of 1) 0 T5.1-18 (1 of 1) 0 T5.1-19 (1 thru 2 of 2) 0 FS.1-1 0

F5.1-2 0

F5.1-3 0

FS.1-4 0

F5.1-5 0

F5.1-6 0

F5.1-7 0

F5.1-8 0

F5.1-9 0

F5.1-10 0

F5.1-11 0

F5.1-12 0

F5.1-13 0

O FS.1-14 0

(

F5.1-15 0

Amendment 8 EPS-1 December 1984 1

MNPS-3 EROLS LIST OF EFFECTIVE PAGES (Cont)

Page, Table (T), or Amendment Figure (F)

Number F5.1-16 0

F5.1-17 0

FS.1-18 0

F5.1-19 0

F5.1-20 0

F5.1-21 5

FS.1-22 0

F5.1-23 0

F5.1-24 0

FS.1-25 0

F5.1-26 0

F5.1-27 0

5.2-1 thru 5.2-11 0

5.2-12 2

5.2-13 2

5.2-14 thru 5.2-15 0

T5.2-1 (1 of 1) 0 T5.2-2 (1 of 1) 0 T5.2-3 (1 of 1) 0 T5.2-4 (1 thru 2 of 2) 0 T5.2-5 (1 of 1) 0 T5.2-6 (1 of 1) 0 T5.2-7 (1 of 1) 0 T5.2-8 (1 of 1) 5 T5.2-9 (1 of 1) 5 T5.2-10 (1 of 1) 5 T5.2-11 (1 of 1) 5 T5.2-12 (1 of 1) 5 T5.2-13 (1 of 1) 5 T5.2-14 (1 of 1) 5 T5.2-15 (1 of 1) 5 T5.2-16 (1 of 1) 5 T5.2-17 (1 of 1) 5 T5.1-18 (1 of 1) 5 T5.1-19 (1 of 1) 5 T5.2-20 (1 of 1) 0 T5.2-21 (1 of 1) 0 T5.2-22 (1 of 1) 0 T5.2-23 (1 of 1) 0 T5.2-24 (1 of 1) 0 T5.2-25 (1 of 1) 5 F5.2-1 0

F5.2-2 0

F5.2-3 0

F5.2-4 0

Amendment 8 EPS-2 December 1984

_i,.

NNPS-3 EROL5 LIST OF EFFECTIVE PAGES (Cont)

O Page, Table (T). or Amendment Figure (F)

Number 5.3-1 thru 5.3-4 8

T5.3-1 (1 thru 2 of 2) 0 T5.3-2 (1 thru 6 of 6) 0 T5.3-3 (1 of 1) 8 5.4-1 thru 5.4-4 0

T5.4-1 (1 thru 2 of 2) 0 5.5-1 thru 5.5-7 0

5.6-1 thru 5.6-6 0

' T5.6-1 (1 of 1) l' T5.6-2 (1 of 1) 0

. T5.6-3 (1 of 1) 5 0

5.7-1 5.8-1thru5)8-2 0

O a

w 4

, e s

4 5

A 4

Amendment 8 EPS-3 December 1984 s

4 gigiin iiii

HNPS-3 EROLS f3 5.3 EFFECTS OF CHEMICAL AND BIOCIDE WASTE DISCHARGES 5.3.1 Water Quality Standards and Effluent Limitations Water quality standards and classifications for the State of Connecticut were adopted by the State Department of Environmental Protection (DEP) on September 20, 1977. According to these standards, the waters in the vicinity of the Hillstone Nuclear Power Station are classified as

"... suitable for bathing, other recreational purposes, Class SB, industrial cooling, and shellfish harvesting for human consumption after depuration; excellent fish and wildlife habitat good aesthetic value."

Water quality standards for Class SB waters are presented in Table 5.3-1.

Effluent limitations for Hillstone 1, 2, and 3 are contained in National Pollutant Discharge Elimination System (NPDES) Permit No. CT0003263 (State of Connecticut DEP Order No. 1505 Modified). A summary of the limitations contained in the permit relating to discharges from Hillstone 3 are listed in Table 5.3-2.

5.3.2 Impact of Liquid Waste Discharge The major discharge associated with operation of the plant is approximately 59.4 cubic meters /sec (2,096 cfs or 942,000 gpm) of water used for cooling the main steam condensers and various heat exchangers within the plant. This water is withdrawn from Niantic Bay and is 7'N discharged to Long Island Sound, via the quarry cut. The chemical

'")

composition of this water is essentially unchanged from that taken in at the intake and passed through the plant.

The major liquid waste discharges from the plant are chemical wastes resulting from regeneration of the makeup demisieralizers and of the condensate polishing demineralizers.

Table 5.3-3 lists average Long Island Sound water quality based on data collected during the 1974 baseline water quality study (section 2.4).

The data have been tabulated for three areas of the Sounds Niantic Bay in the vicinity of the intake structure (Station 8); Long Island Sound at the discharge from the quarry cut (Station 1); and Long Island Sound at a point between the quarry cut and Twotree Island (Station 2).

Figure 2.4-13 shows the location of these stations. Since the data in Table 5.3-3 indicate very little difference in water quality at these three locations, no attempt has been made to predict receiving water quality outside of a defined mixing zone. The impact on Long Island Sound chemical water quality resulting from the discharge of once-through cooling water will be minimal. The impact of the vaste heat in this discharge is discussed in Section 5.1.3.

As discussed in Section 3.6, an average of approximately 443,000 liters 8

(117,000 gallons) per week of regeneration wastes from the makeup demineralizer system will be discharged, after neutralization (to pH 6.0 to 9.0), to the circulating water discharge tunnel.

The principal constituents of this waste are sodium and sulfate at concentrations of

( 'I 1,460 mg/l and 3,230 mg/1, respectively. The concentration of sodium in s

this waste is less than that of the intake water, and, therefore, there Amendment 8 5.3-1 December 1984

HNPS-3 EROLS will be no increase in concentration of sodium in the discharge to the quarry.

The concentration of sulfate in the regeneration wastes is approximately 786 mg/l greater than in the circulating waters however, assuming that this waste is discharged to the circulating water tunnel 8

at 7,57 liters / min (200 gpm), the resulting increase in the circulating water discharge concentrations is less than 0.2 mg/1. The discharge impact of neutralized makeup demineralizer regeneration vastes on receiving water quality is minimal.

The discharge of regeneration wastes from the condensate polishing demineralizers to the circulating water will also have a negligible impact on water quality.

Under average conditions, approximately 23,000 gallons per day of acutralized condensate polisher regeneration wastes may be discharged to circulating water.

These wastes will 8 l c ntain approximately 3,930 mg/l of sulfate and 1,770 mg/l of sodium (Section 3.6).

Biofouling in the main steam condenser is controlled through the use of a mechanical condenser tube cleaning system (Amertap) employing captive sponge rubber balls. The use of chlorine for biofouling control in this system is not anticipated. As described in Section 3.6, the service 8l water system is chlorinated continuously. The concentration of free available chlorine in the service water at the point where the service water and circulating water is dischar@ d to the quarry is maintained at 8 l a maximum of or less than 0.25 ppm. After mixing with the quarry water, this concentration is reduced through dilution below detectable limits for free available chlorine. The chlorine demand of the circulating and 8

quarry water reduces the chlorine concentration, such that less than 0.1 ppm total residual chlorine will be discharged to Long Island Sound.

5.3.3 Effects of Chemical and Blocide Discharges on Aquatic Biota The chemical constituents of the discharge of Hillstone 3 (Sections 5.3.1 and 5.3.2) are practically indistinguishable from ambient water at the intake (Niantic Bay). Average discharge stream concentrations are within the range of ambient Niantic Bay concentrations for all parameters sampled during water quality surveys.

Additional dilution in the discharge plume ensures no adverse chemical effects on plankton, fish, or benthos in the vicinity of Hillstone Point.

Chlorination is not used to control biofouling in the circulating water system of Hillstone 3 (section 5.3.2).

An Amertap system is employed for condenser cleaning and a thermal backwash system is used in the intake to control the growth of organisms such as mussels.

Piping for chlorination of the circulating water system will be installed for H111 stone 3: however, its use is not anticipated unless the mecaanical tube cleaning system should prove ineffective in controlling fouling of the condenser tubes.

8l Continuous chlorination is used to control biofouling in the service water system. The level of free available chlorine at the point where the service water and circulating water are discharged into the quarry 8 l is maintained at a maximum of or less than 0.25 ppm. After mixing with Amendment 8 5.3-2 December 1984

MNPS-3 EROLS

'l the quarry water, concentration of free available chlorine at the quarry cut is further reduced to an essentially undetectable level.

Thus, no impact to the aquatic biota of Long Island Sound is anticipated.

Synergistic effects of the thermal and chemical components of the Millstone 3 discharge are unlikely to occur at the Millstone Point site, since concentrations of the chemical effluent at the point of discharge (the quarry cut) are essentially indistinguishable from ambient levels.

In addition, dilution of the discharge occurs rapidly, such that concentrations likely to be encot.ntered by aquatic organisms in those portions of the plume with less elevated temperature are, for all intents and purposes, at ambient levels. Thus, any impact to aquatic biota results from the thermal component rather than from the chemical or biocide component of the discharge.

Section 5.1.3 discusses the thermal effects of the discharge in detail.

5.3.4 condenser Tube Corrosion A study was conducted in 1979 to determine the impact of condenser tube corrosion on trace metal concentrations in Long Island Sound (Waslenchuk 1980). This study determined the concentrations of copper, l8 nickel, and zine and the impact of operation of Hillstone Units 1 and 2 on these concentrations. The Hillstone Nuclear Power Station utilizes a once-through cooling water system. Long Island Sound water is passed through the condensers of Millstone Units 1 and 2,

which contain l8 copper / nickel condenser tubes with sacrificial zine blocks used as

(

corrosion inhibitors, and then discharged to Long Island Sound.

~'

In order to determine the effect of plant operation on trace metal concentrations in Long Island Sound, samples were collected at the plant intake and plant discharge.

Samples were also collected along the discharge plume axis and to either side of the plume, as well as at two locations approximately 2 kilometers to either side of Millstone Point to determine ambient far-field concentrations.

Ambient concentrations of dissolved copper measured at the two far-field sampling stations averaged 1.2 ug/l at the eastern station and 1.5 ug/l at the western station.

A single far-field sample contained 1.0 ug/l of nickel and 1.4 ug/l of zinc. Concentrations of dissolved copper, nickel, and zine measured at the plant intake averaged 1.2 ug/1, 2.4 ug/1, and 0.4 ug/1, respectively. Concentrations of these parameters measured at the plant outfall increased by an average of 1.1 uq/1 for all parameters.

Analyses of intake and outfall water samples were performed to determine the relative concentrations of dissol'.3d and particulate phases of the metals under study.

Intake total metal and dissolved concentrations showed essentially no contribution from particulate copper, nickel, and zinc.

Dissolved metal concentrations in the outfall samples increased only slightly over intake concentrations while total metal concentrations increased by 3.9 ug/1, 0.6 ug/1, and 1.2 ug/l for copper, nickel, and zinc, respectively. The majority of these increases'were in the particulate fraction and are attributed to the plant cooling system.

Analysis of water samples collected in the area of the discharge plume f}

indicate that the increased metal concentrations in the plant discharge Amendment 8 5.3-3 December 1984 r

MNPS-3 EROLS return to ambient levels at a rate similar to that of temperatures with the plume's return to ambient levels (see Section 5.1.3).

Although the results of this program indicated an increase in the levels of copper, nickel, and zine between intake and discharge attributable to the cooling system, the values reported were within the range of ambient concentrations observed during the 1974 baseline study and during the ongoing water quality monitoring program (see Section 2.4 and Table 5.3-3).

In addition, the elevated concentrations returned to ambient levels at a rate similar to temperature along the discharge For these reasons, it is concluded that corrosion of the 8 l plume.

copper / nickel condenser tubes at Millstone Units 1 and 2 will have minimal impact on the water quality of Long Island Sound.

Millstone 3 uses titanium condenser tubes, therefore, there will be no 8

additional contribution tc the heavy metal concentrations in 1.ong Island Sound due to corrosion of the condenser tubes of this unit.

5.3.5 Reference for Section 5.3 Waslenchuk, D.G.

1980.

The Concentration, Reactivity, and Fate of Copper, Nickel, and Zine in a Coastal Power-Station Cooling Water Plume.

Final Report to Northeast Utilities Company (NUSCo.), January 1980.

O O

Amendment 8 5.3-4 December 1984

MNPS-3 EROLS TABLE 5.3-3 5

LONG ISLAND SOUND WATER QUALITY

  • Intake Discharge L.I. Sound Parameter **

Station 8 Station 1 Station 2 Ammonia - N 0.016 0.054 0.053 Nitrite - N 0.008 0.008 0.008 Nitrate - N 0.201 0.201 0.185 Organic - N 0.315 0.471 0.400 Total Phosphate 0.175 0.220 0.216 Ortho-Phosphate

-<0.1

<0.1

<0.1 Condensed PO,

<0.1 0.113

<0.1 Organic Carbon 9.85 16.9 11.6 011 and Grease 8.83 6.64 9.02 Sulfates 2444 2409 2372 MBAS 0.08 0.07 0.09 Free Cla ND***

ND ND l8 Combined Cl, ND ND ND Suspended Solids 28.1 28.2 30.1 Boron 2.52 2.51 2.51 Copper 0.038 0.043 0.033 Nickel 0.085 0.084 0.092 Iron 0.092 0.100 0.093 O_

Manganese 0.020 0.025' O.023 Zinc 0.013 0.014 0.011 Aluminum 1.014 0.730 0.490 s

Total Chromium 0.060 0.057 0.062 Lead 0.100 0.090 0.091 Total Alkalinity 240 238 244 Chloride 17814 18278 17709 Potassium 565 630 582 Calcium 245 249 250 Magnesium 1059 1103 1068 Arsenic ND ND ND-Molybdenum 0.135 0.350 0.100 Titanium ND ND ND Vanadium 0.055 0.061 0.081 1Ca&nium 0.020 0.025 0.023 Beryllium ND ND ND 4

Mercury ND-ND ND Total Solids 33430 33929 34049 Volatile Solids 5400 6085 6235 Tin 2.2 3.7 3.7 ND ND ND Phenol NOTES:

  • Data based on baseline water quality study (Section 2.4)
    • All concentrations are expressed in ug/l unless otherwise noted.

\\

      • ND - Not detected

[b Amendnent 8 1 of 1 December 1984 4

f

a.

MNPS-3 EROLS LIST OF EFFECTIVE PAGES y

28)

Page, Table (T), or Amendment Figure (F)

Number 1'

i thru 11-0 6-i thru 6-v 0

6.1-1 thru 6.1-17 0

6.1 5 6'.1-19 thru 6.1-28 0

6.1-29 5

6.1-30 thru 6.1-41 0

6.1 5 7

6'.1-43 thru 6.1-50 O

T6.1-1 (1 of 1) 0 T6.1-2 (1.thru 3 of 3) 0 T6.1-3 (1 of 1).

0 T6.1-4 (1 of 1) 0 T6.1-5 (1 of 1)'

0

+

T6.1-6 (1 of 1) 0 T6.1-7 (1 of,1) 0 T6.1-8 (1 thru 5 of 5)

O T6.1-9'(1 thru 2 of 2) 0

.T6.1-10 (1 thru 5 of 5) 0 6

F6.1-1 0

F6.1-2 0

F6.1-3 0

F6.1-4 0

F6.1-5 0

F6.1-6.

O F6.1-7 0

F6.1-8 0

F6.1-9 0

.F6.1-10 0

F6.1-11 0

~

'F6.1-12 0

F6.1-13 0

F6.1-14 5

F6.1-15 0

F6.1-16 0

F6.1-17 0

F6.1-18=

0 6.2-1 thru 6.2-2 8

-t 4"

6.2-3 thru 6.2-6 0

T6.2-1 (1 of 1) 0 6.3-1 5

6.4-1 0

Amendment 8 EP6-1 December 1984 4

-;f

w j

MNPS-3~EROLS a..

N 6.2 ' APPLICANT'S PROPOSED OPERATIONAL MONITORING PROGRAMS' O-6.2.1 Proposed Ecological Monitoring of Millstone 3 Cperation W

6.2.1.1 Plankton Community

'The _ ' following sampling programs are proposed to provide quant'itative estimates of the number, seasonality, and types of plankton' entrained in the condenser cooling system of Millstone 3 and concurrently in

. Millstone 1 or 2.

Ichthyoplankton i

1

-Field Sampling Frequency The field portion-of the Millstone 3 operational ichthyoplankton

[

monitoring' program-will~ be largely a

continuation of the

~

i preoperational monitoring methodology (Section 6.1.1.2) with some.

modifications suggested by data collected-in preoperational.

be the inclusion of the l 8

[

monitoring phase..

One modification will a rotating Millstone 3 discharge as a sample site,.to be sampled on basis with Millstone.1 and 2 discharges. The entrainment sampling t

j frequency should also be modified from -the present three samples,

taken 3 days weekly.(day-and night), to a frequency that varies with

-season. From' January through May, two samples (1 day -and 1 night) will. be collected 4-days per week. From June through September, two 4

samples-(1 day and-1 night) will be taken 3 days per week, and from October through -December two samples (1 day and 1 night) will be taken 1 day per week. Fish eggs _ will be identified in.six samples 8

per week - from April through September, and fish larvae will be-identified in'all samples except during June.

In this month only two samples. per week will be analyzed for fish larvae. These changes in

. sampling frequency a,re proposed because of the seasonal pattern of.

Y vichthyoplankton occurrence and the potential impact.during periods'of reduced analysis is Iow.

These changes would not affect the Applicant's-ability to meet the associated objectives of the e

entrainment program... ".to provide-quantitative. estimates of'_the abundance.and species composition of the... fish larvae entrained" (Section 6.1.1.2.1). 'The newly proposed seasonal sampling ~ program ' l 8 has' virtually no effect on sensitivity of analysis on the taxa of j

greatest importance..

It only modestly affects sensitivity of analysis of the less' abundant forms (less than 10-percent change) in variance estimates on weekly means of all species tested (Toble'6.2-1),

while representing a major increase in the cost / time i-efficiency _of the entrainment ichthyoplankton program.

in h

LAn = offshore 'ichthyoplankton field program will.be conducted at a

[representativestation(Station 5)in mid-Hlantic Bay to_' put the 3

~

Millstone into perspective.. l 8

'~

numbers of _ fish larvae entrained at Stepwise oblique, 60-cm bongo tows with 0.333-am mesh nets will be Itaken -both day and night weekly from April through August and on alternate weeks from September through March at Station 5.

t a

i Amendment 8 6.2-1 December 1984

. s, w m u-n eum rme n-m e-.m N ~ ~ rr m r

C e

HNPS-3 EROLS LaUoratory Processing Methodology The laboratory portion of the Millstone 3 operational ichthyoplankton monitoring ;dogram should be a continuation of the preoperational monitoring imethodology (as described in Section 6.1.1.2 of this report), wf th the exception that egg count 3' and identification would be conducted only on samples collected from Aoril through September.

This change in the processing step of field collections is the subject of a pending request to the NRC for change in Environmental

/ Technical Specif: cations.

October through March ichthyoplankton samples would not 'Fe processed for fish eggs because the potential impact of entrainmenti of fish eggs during the fall-winter months is very low.

Fish larvae will be sorted and identified in entrainment and offshore samples, using the methods described in Seqtion 6.1.1.2.

Phytoplankton/ Chlorophyll A i

A phytoplankton/ chlorophyll A study has not beer proposed as a part of the operatio tal monitoring cf Millstone 3, since the potential

.k '

impact on phytoplankton with three-unit operation will be minimal (S*: tion 5.1. E and the objectiie' of providing some seasonal

\\

re..stionships between phytoplankton and the local dominant a j

j. N zooplankton species should be acc6mplished before Millstone 3 startup.

s s

6.2.1.2 Impingement Monitoring

't-)

With the installment and operation of a sluiceway expected at g

Millstone 1,in 1982 and at Millstone 3 upon startup in 1986, a 1-year

4 sempling program for each sluiceway will be utilized to test the e!fectiveness of the fish return systems.

Information coll:cted K

lf.uring these studies will be compatible with previous impingement data; species vill be identified to the lowest possible taxon, measured, and enumerated. Immdiate and latent species survival data -

will also be gatnered and s aielyzed.

Impinged organisms at Millstone 2 will be sampled as before, with three 24-hour counts per week. Field and laboratory techniques will also remain the same for program continuity (See Section F. 1.I,2).

)\\

6.2.1.3 Exposure Pamhs

<f

. [F 1 The? exposure par.el program for the Millstone Nuclear Power Station

+1 was" initiated in June 1968. From 1968 to 1981, the dimensions and

',e[T, materials

,of the two panel types have remained consistent:

'.W4 x 9.5 x 1.9-cm soft pine and 25.4 x 9.5 x 0.4-cm asbestos 6

9 '

.)

cement (Transite). Prior to 1979, two exposure periods, 1 month and 12 months, were used~for sampling fouling and wood-boring species at six sites: th'ree adjacent to the power station (Fox Island, Millstone Harbor, and Intaka); one in the thermal effluent (Effluent); one 1,500 meters east of the thermal effluent (White Point); and one O

y Araendment 8 6.2-2 December 1984 i

V 4

MNPS-3 EROLS LIST OF EFFECTIVE PAGES f

4 Page, Table (T), or Amendment Figure (F)

Number Appendix E Title page O

E-i thru E-ii 0

E-iii 5

E-iv thru E-v 0

E-l'thru E-7 0

El-1 thru El 0

-TE-1 (1 thru 3 of 3) 0 TE-2 (l'of 1)-

0 TE-3 (l'of 1) 0 TE-4 (1 thru 3 of 3) 0 TE-5 (1 of 1) 0 TE-6 (1 thru 2 of 2) 0 TE-7~(1 of 1) 0 4

TE-8 (1 of 1) 0 TE-9-(1 of 1) 0

  1. ~

FE-1 0

FE-2 0

FE-3 8

FE-4 0

O 1

I'

  • k

.. ri-O Amendment-8 LEP-El December 1984 i-m m14 m.A#= W 8W'*uw*M'-W-Nem5-

-ww--PWr'9e@ wee-+me-we->--+h.-+'emw4ee -w er e=e-+rr-v+-we-4-e e-w -r w T w s-

- -we-

+

/#~

(s

)

BINDER PROMOTER & CATALYST OR

/

REACTOR ACCEPTABLE ALTERNATE PHOCESS I

PLANT SERVICE 2 $$E +04CihR.

g 4,36E+ 01Cl/FT3-SPENT RESIN S (1) 3 3 HIPPING M OFFSITE OTHER SERVICE 2.60E +01 C1/YR, TBS FT3/YR CONTAIN7 1.30E-01Cl/FT3 J

b d b SPENT FILTERS 6.TTE4 02Cl/YR-MISCELLANEOUS CASKS AS SHIELOING OPERATION &

M WASTE (2)

MAINTENANCE NEGLIGIBLE SOO FT 3/ YR ACTIVITY d b RADIOACTIVE SPENT LIQUID B.16 CI/ YR, R ESINS (f)(S)

WASTE "3

SYSTEM 2.04E-02CI/FT 400 FT /YR 3

BORON EVAPORATOR BORON 1.2TCl/YR BOTTOMS (3)

RECOVERY W

B.47-03Cl/FT '

150 FT s/yg SYSTEM O

5 REGENERANT

'N CHEMICAL CONDENSATE EVAPORATOR POLIS HING 7

BOTTOMS M MILLSYONE UNIT 2 PROCESSING FACILITY FACILITY O FTsfyn (4}

OPERATION 6 MISCELLANEOUS MAINTENANCE COMPRESSIBLE C

WASTES (2)

M CONTAINERS W COMPA OR FSIT ACTIVITY 4000 FT3/YR NOTES:

1. Cl/FT3 VALUES BASED UPON VOLUME OF RAW SPENT RESINS
2. Cl/FT3 VALUES BASED UPON VOLUME OF PACKAGED WASTE
3. Cl/FT3 VALUES BASED UPON VOLUME

.i OF RAW BOTTOM S FIGURE E-3 4.

NORMAL EXPECTED RADIATION LEVELS EiEE70TBeNESSAR RADIOACTIVE SOLID WASTE SYSTEM

' ^" ' " ^ " " ^ ' ' "

S. ALTEPNATE METHOD WOUL '100UCE APPROxMATELY 3OOO rT6 4 O' MILLSTONE NUCLEAR POWER STATION RAW EVAPORATOR BOTTOMS. THis W

3 N

METHOD WOULO NOT BE THE NORMAL OR PREFEPRED METHOD OF DISPOSAL.

ENVIRONMENTAL REPORT OPERATING LICENSE STAGE AMENDMENT 8 DECEMBER 1984

MNPS-3 EROLS (January 31, 1983 Letter)

.f-~)s,

LIST OF EFFECTIVE PAGES If Page, Table (T), or Revision Figure (F)

Number Date EROLS Questions (Index)

(1 thru 2 of 2) 0 April 1983 QE100.2-1 1

September 1983 TQE100.2-1 (1 of 9 thru 9 of 9) 1 September 1983

-Q231.1-1 0

April 1983 1

Q240.1-1 thru Q240.1-2 1

September 1983 FQ240.1-1 1

September 1983 FQ240.1-2 1

September 1983 FQ240.1-3 1

September 1983 FQ240.1-4 1

September 1983 FQ240.1-5 1

September 1983 Exhibit 240.1-1 (25 pages) 0 September 1983 Q240.2-1 0

April 1983 QE290.1-1 0

April 1983 QE291.1-1 thru QE291.1-3 0

April 1983 QE291.2-1 0

April 1983

'TQI291.2-1 (1.thru 2 of 2)

'O April 1983 TQE291.2-2 (1 of 1) 0 April 1983 TQE291.2-3 (1 of 1) 0 April 1983 TQE291.2-4 (1 of 1) 0 April 1983 jq

-QE291.3-1 thru QE291.3-2 0

April 1983

. ~('~^)

QE291.4-1 0

April 1983 QE291.5-1 0

April 1933 QE291.6-1 0

April 1983

.QE291.7-1 0

April 1983 QE291.8-1.

O April 1983

.QE291.9-1 0

April 1983 QE291.10-1 0

April 1983

'QE291.11-1 0

April 1983 QE291.12-1 0

April 1983 FQE291.12-1 0

April 1983 QE291.13-1 O

April 1983

.QE291.14-1 0

April 1983

-QE291.15-1 0

April 1983 QE291.16-1 0

April 1983 QE291.17-1 0

April 1983 QE291.18-1 1

April 1984 QE311.5-1 0

April 1983 TQE311.5-1 (1 of 1) 1 December 1984

.TQE311.5-2 (1 of 1) 1 December 1984 TQE311.5-3 (1 of 1) 1 December 1984 TQE311.5-4.(1Rof 1) 1 December 1984 TQE311.5-5 (1 of 1) 1 December 1984 TQE311.5-6 (1 of 1)

December 1984

-TQE311.5-7 (1 of 1) 1 December 1984 TQE311.5-8 (1 of 1) 1 December 1984

. /~~s.

.TQE311.5-9 (1 of-1) 1 December 1984 Q

)

.TQE311.5-10-(1 of 1) 1 December 1984 Revision 4 EPQ-1 December 1984

,___,,__._,-..___m.

MNPS-3 EROLS (January 31, 1983 Letter)

LIST OF EFFECTIVE PAGES (Cont)

Page. Table (T), or Revision Figure (F)

Number Date TQE311.5-11 (1 of 1) 1 December 1984 TQE311.5-12 (1 of 1) 1 December 1984 TQE311.5-13 (1 of 1) 1 December 1984 TQE311.5-14 (1 of 1) 1 December 1984 TQE311.5-15 (1 of 1) 0 April 1983 TQE311.5-16 (1 of 1) 0 April 1983 TQE311.5-17 (1 of 1) 0 April 1983 QE320.1-1 thru QE320.1-2 0

April 1983 QE320.2-1 0

April 1983 Q470.1-1 0

April 1983 TQ470.1-1 (1 of 1) 0 April 1983 TQ470.1-2 (1 of 1) 0 April 1983 TQ470.1-3 (1 of 1) 0 April 1983 Q470.2-1 0

April 1983 Q470.3-1 0

April 1983 Q470.4-1 1

January 1984 O

l l

O Revision 4 EPQ-2 December 1984

~

1

(

MNPS-3 EROLS I

TABLE QE311.5-1 1980 POPULATION DISTRIBUTION 0-10 Miles Distance failes) 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5--

4.0-4.5-5.0-6.0-7.0-8.5-Direction' D1 1.d_

LL.

LIL E'

L.D._. L1.

LD LL' LIL 6dL LD LS_

11.0 Totei N

0-0 116 495 119 357 773 91 17-45 317 359 1,697 1,823 6,209 NNE.

0

-0

' 31 325 475-806 614 241 288 1,904 1,850 1,295 1,862 3,623 13,314 NE 23 153 57

-439 410 191 1,036 2,595 5,649 6,537 5,717 4,020 3,728 2,643 33,198 ENE 6

'68 160 210 111-108-514 4,127 1,182 140 7,223 1,364 4,475 4,387 24,075 E

O 16' 528 165 212 250' 844 1,871 209 76 751 0

621 2,263 7,806' ESE-0 0

73 89

. 68 11' O

0 0

0 0

0 176 334 751 SE O-0 0

0 0

0 0

0 0

0

.0 0

-0 0-0 SSE O

O O

O O

O O

-~0 0

0 0

0 0

0 0

S 0

0 0

0 0

0 0

0 0

0 0

0 118 126 244 SSW O

O O

O O

O O

O O

O O

O 5

90 95 SW 0

0 0

0 29 13?

O O-0 0

0 0

0 0

161 i

WSW 0

0 0

0 1,302 179 204 112 0

1,009 1,103 1,510 35 18 5,472 W

0 0

0 257 1019 383 409 694 23 295 435 187 525 765 4,992 WNW O

O O

516.

723 504 524 23 40 32 157 52 518 421 3,510 MW 0

0 37 580 364 147 645.

297 89 319 573 52 513 392 4,006 NNW 0

122-458 198 438 272 246 232 400 155 455 75 1,076 1,268 5,395 Total' 29 359 1,460 3,274 5,270 3,340 5,809 10,283 7,897 10,512 18,581 -8,914 15,349 18,153 109,230l Revision 1 1 of 1 December 1984

t MNPS-3 EROLS TABLE QE311.5-2 1985 POPULATION DISTRIBUTION 0-10 Miles 01 stance imiles) 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.

5.0-6.0-7.0-8.5-Direction R R R R

R R

R R

R R

R R

R lad!

Total N

O O

119 507 122 365 791 93 17 46 324 368 1,746 1,886 6,384 NNE O

O 32 333 487 824 628 246 293 1,916 1,860 1,325 1,907 3,775 13,626 NE 23 156 58 449 420 196 1,060 2,588 5,621 6505 5,728 4,064 3,790 2,753 33,411 ENE 6

70 164 215 114 110 513 4,107 1,176 142 7,336 1,389 4,500 4,455 24,297 E

O 17 541 169 216 256 854 1,862 208 77 762 0

628 2,282 7,872 ESE O

O 75 92 69 12 0

0 0

0 0

0 198 375 821 SE O

O O

O O

O O

O O

O O

O O

O O

SSE O

O O

O O

O O

O O

O O

O O

O O

S O

O O

O O

O O

O O

O O

O 132 141 273 SSW 0

0 0

0 0

0 0

0 0

0 0

0 6

101 107 SW 0

0 0

0 30 139 0

0 0

0 0

0 0

0 169 WSW 0

0 0

0 1,367 188 215 118 0

1,082 1,182 1,619 38 18 5,827 W

0 0

0 264 1,062 402 429 729 24 316 466 201 563 791 5,247 WNW 0

0 0

531 748 529 550 24 42 33 166 56 557 453 3,689 NW 0

0 38 597 375 155 677 312 94 342 602 54 542 418 4,206 NNW 0

125 469 203 450 279 253 237 416 165 478 79 1,119 1,320 5,593 Total 29 068 1,496 3,360 5,460 3,455 5,970 10,316 7,891 10,624 18,904 9,155 15,726 18,768 111,522 Revision 1 1 of 1 December 1984 9

9 9

~

~~

": ' ^

^

(

y;

)-

v' Nd'

'Q '

MNPS-3 EROLS TABLE QE311.5-3 1990 POPULATION DISTRIBUTION 0-10 Miles Distance falles) 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-6.0-7.0-8.5-Direction. R L.(L L.1_

2.d.

R J d_

R 3 d_

L.1_

R 6.d_

Id_ - 6 1._

1(kQ Total N

O O

121 515

.124 371 804 94 18 47 330.

374 1,792 1,956 6,546 NNE O

O 32 338:

494 837 637 249 298 1,948 1,892 1,346 1,943 3,980

'13,994 NE 24 159 59 456

'427 199 1,075 2,630 5,712 6,610 5,799 4,093 3,835 2,880 33,958 ENE 6

71 166 218 116 112 521 4,173 1,195 142 7,368 1,390 4,558 4,472 24,508 E

O 17 549 172 220 260 869 1,892 211 77 765 0

632 2,297 7,961 ESE O

O 76 93 70 12 0

0 0

0 0

0 220 417 888 SE O

O O

O O

O O

O O

O O

C 0

0 0

SSE O

O O

O O

O O

O O

O O

O O

O O

l S

O O

O O-0 0

0 0

0 0

0 0

147 157 304 SSW 0

0 0

0 0

0 0

0 0

0 0

0 6

112 118 SW

.0 0

0 0

31 142 0

0 0

0 0

0 0

0 173 WSW 0

0 0

0 1,395 191 219 120 0 1,173 1,282 1,755 41 18 6,194 l

W 0

0 0

275 1,092 411 438 744 25 34:

505 217 611 814 5,473 WNW 0

0 0

553 775 540 562 25 43 34 170 61 603 488 3,854 NW 0

0 40 621 390 158 691 318 96 371 614 56 560 439 4,354 NNW 0

127 477 209 468 286 257 241 424 176 488 84 1,146 1,358 5,741 l

Total 30 374 1,520 3,450 5,602 3,519 6,073 10,486 8,022 10,919 19,213 9,376 16,094 19,388 114,066 l

Revision 1-1 of 1 December 19m

MNPl-3 EROLS TABLE QE311.5-4 2000 POPULATION DISTRIBUTION 0-10 Miles Distance (miles) 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-6.0-7.0-8.5-Direction R

L9_

h 2.dL h

L9_

L1_

LD_

R LIL ftdL LIL R

10.0 TOTAL N

O O

118 505 121 364 788 92 17 46 323 367 1,857 2,125 6,723 NNE O

O 32 332 485 821 625 245 292 1,909 1,854 1,320 1,928 4,262 14,105 NE 23 156 58 448 419 195 1,055 2,576 5,593 6,473 5,766 4,183 3,948 3,068 33,961 ENE 6

69 163 214 113 110 510 4,086 1,170 146 7,536 1,422 4,661 4,574 24,780 E

O 17 539 169 216 255 852 1,853 207 79 783 0

646 2,349 7,965 ESE O

O 75 91 69 12 0

0 0

0 0

0 248 470 965 SE O

O O

O O

O O

O O

O O

O O

O O

SSE O

O O

O O

O O

O O

O O

O O

O O

S 0

0 0

0 0

0 0

0 0

0 0

0 166 177 343 SSW 0

0 0

0 0

0 0

0 0

0 0

0 7

127 134 SW 0

0 0

0 32 145 0

0 0

0 0

0 0

0 178 WSW 0

0 0

0 1,436 197 226 124 0

1,320 1,443 1,975 46 18 6,785 0

0 0

283 1,124 423 451 766 25 384 568 245 687 849 5,805 WNW 0

0 0

569 798 556 578 25 44 35 178 68 677 546 4,074 NW 0

0 41 640 402 163 712 327 99 417 632 57 589 476 4,555 NNW 0

124 468 208 482 287 253 237 427 193 502 91 1,187 1437 5,896 TOTAL 29 366 1,494 3,459 5,697 3,529 6,050 10,331 7,874 11,002 19,585 9,728 16,647 20,478 116,269 l Revision 1 1 of 1 December 1984 O

O O

l

' (}

i ("}

-.(. i

'd MNPS-3 EROLS TABL.E-QE311.5-5

-2010 POPULATION DISTRIBUTION 0-10. Miles.

Distance faites1 0.0-0.5-1.0-

1. 5 -

2.0-2.5-3.0-3.5-4.0-4.5.

5.0-6.0-7.0-8.5-Direction.

~Q

- 1,.,Q.,,

-Q Q-Q Q

-Q Q-Q Q

Q Q'

Q' j_Q,_Q lqJA_L '

N 0-0 115-491 118 353 765 90 17 45 314 356 1,922 2,316 6,902.

NNE O

O 31 322 471 - 796 605 240-292 2,025.-

1,970 1,281 '1,902 4,896

.14,831 NE 22 151 56

'435 407 189 1,021 2,858 6,282 7,270 6,136' 4,163 3,954

.3,379-36,323 ENE ~

6 67 158 208 110-107 567 4,589 1,314 139 7,200 1,308 4,954 4,359 25,086 E

O 16 523 163 210 247 876 2,081 232 76 748 0

649 2,366 8,187 ESE O

O.

72-88 67' 11 0

'O O

O

'O O

288 547 1,073 SE O

O 0-0 0

0-0 0

0-

~0 a

0 0

0 0

SSE O

0 O.

0 0

0 0

0 0

0 0

0 0

0

-0 9

S 0

0 0

0 0

0

'O O

O O

O O

193 206 39?'

i SSW 0-0 0

0 0

0 0

0 0

0 0

0 8

147 155. j SW 0

0 0

0 28 131

-0 0

0 0

0 0

0 0

159 WSW 0

0 0

0 1,285' 176 202 111 0

1,586 1,733 2,372 55 17 7,537 W

O O

O 319 1,099 378 404 685 23 456 683 294 825 875 6,041 WNW 0

0 0

641 842 497 517 23 40 31 166 82 809 631 4,279-NW 0

0 46 721 446 149 637 293 88.

501 566 51 559 485 4,542 NNW 0

121 454 216 543 294 244 230 395 224 449 103 1,141 1,429 5,843 TOTAL 28 355 1,455 3,604. 5,626 3,328 5,838 11,200 8,683 12,353 19,965 10,010 17,259 21,653 121,357 Revision 1 1 o f' 1 -

December 1984

s MNPS-3 EROLS TABLE QE311.5-6 2020 POPULATION DISTRIBUTION 0-10 Miles Distance (miles) 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-6.0-7.0-8.5-Di rec t i on R 1d_ h 2J_

h LR_

,h ILdL L3._

.LD_

6.J_

L_Q_

h' lQJ Total N

O O

108-461 111 332 719 84 16 42 295 335 1,976 2,535 7,014 NNE O

O 29 303 443 745 566 229 286 2,204 2,148 1,203 1,830 5,713 15,699 NE 21 142 53 408 382 177-955 3,307 7,382 8,543 6,702 4,078 3,896 3,746 39,792 ENE 5

63 148 195 104 100 657 5,393 1,545 127 6,568 1,108 5,370 3,961 25,344 E

O 15 490 153 196 232 910 2,445 273 69 682 0

646 2,367 8,478 1,181l ESE O

O 68 83 63 11 0

0 0

0 0

0 330 626 SE O

O O

O O

O O

O O

O O

O O

O O

SSE O

O O

O O

O O

O O

O O

O_

0 0

0 S

0 0

0 0

0 0

0 0

0 0

0 0

221 236 457 SSW 0

0 0

0 0

0 0

0 0

0 0

0 9

169 178 SW O

O O

O 22 101 0

0 0

0 0

0 0

0 123 WSW 0

0 0

0 997 137 157 86 0 1,916 2,094 2,866 67 13 8,333 W

0 0

0 367 1,024 293 313 531 18 547 825 355 997 892 6,162 WNW 0

0 0

738 887 386 401 18 31 24 143 99 971 728 4,426 NW 0

0 53 830 504 122 494 227 68 606 439 40 488 472 4,343 NNW O

113 427 224 625 300 226 216 334 262 349 118 1,034 1,365 5,593 Total 26 333 1,376 3,762 5,358 2,936 5,398 12,536 9,953 14,340 20,245 10,202 17,835 22,823 127,123 Revision 1 1 of 1 December 1984 O

O O

['

j f'}

^

y f..)

.N b

MNPS-3 EROLS-TABLE QE311.5-7' p

2030 POPULATION DISTRIBUTION 0-10 Miles..

4

'A.l Distance faites) 0.0-0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-6.0-7.0-

8. 5.

Direction R-R h R

E' R

R R

Q- ~R R

R R

J.Qd Total N.

'O O

98 418.

100 301 652 76 14 38 268 304. 2,020 2,781

.7,070 4

NNE

-0

.0' 26 275 401 674 509 214

.280 2,458 2,403 1,090 1,722-6,738 16,790 NE 19 129 48 370 347 160-860 I,952 8,961 10,369 7,500 3,926 3,772 4,180 44,593 E'NE 5

'57 134 176 94 90 785 6,547-1,875 108 5,609 812 5,920 3,357 25,569 E

O 14 443 139 178..

211-957 2,968-332 59 583 0

635 2,352

.8,871 ESE O

O 61 75 57 110 0-0 0

0 0

0 375 711 1,289 i

~

t SE O

O-0 0

0 0

0-0 0

0 0

0 0

0 0

i~

SSE O

O 0-0 0

0-0 0-0 0

0 0

0.

0 0

t S

O O

'O 0.

0 0

0 0-O' O

O O

251 268 519 SSW 0

0 0

0 0

0 0

0 0

0 0

0 11 192 203 SW 0

0 0

0 12 57 0

0 0

0' O

O O

O 69 WSW 0

0 0

0 563 77 88 49 0 2,320 2,535 3,471 81 9

9,193 W

0 0

0 431

'898 166 177 300 10 656 999 430 1,208-899 6,174 f

WNW 0

0 0

866 937 218 227.

10 17 14 104 120 1,168 842 4,523 i

NW D

0 62.

974 579 80 279-128 39 733 248 22 371 437 3,952 NNW 0

103 387~

233 731-307 201 196 242 307 197 136 859 1,238 5,137 b

9 i

Total 24

.303 1,259 3,957 4,897 2,351 4,735 14,440s 11,770 17,062 20,446 10,311 18,393 24,004 133,952l f

l Revision 1 1 of 1 December 1984 -

i t

3 w

m

MNPS-3 EROLS TABLE QE311.5-8 1980 POPULATION DISTRIBUTION 0-50 Miles Distance (miles) 0.0-10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-Direction M

M JLQ M

M 2hD ILD M

4hD hh_Q

$L_Q Total N

6,209 3,585 3,801 4,215 2,394 3,819 2,2,992 15,034 16,350 9,419 9,416 97,234 NNE 13,314 3,449 7,323 12,988 13,256 16,095 7,918 10,604 14,725 14,430 15,579 129,681 NE 33,198 3,521 4,375 2,492 1,747 4,426 3,753 9,235 16,357 49,825 108,963 237,892 ENE 24,075 8,129 3,167 4,347 6,244 8,012 6,631 11,430 21,117 44,766 74,863 212,781 E

7,806 582 1,898 2,910 4,632 7,414 1,652 4,908 6,921 1,135 1,592 41,450 ESE 751 101 0

0 0

0 0

615 0

0 0

1,467 SE O

O O

O 154 889 0

0 0

0 0

1,043 SSE O

O 54 57 395 1,676 0

0 0

.0 0

2,182 S

244 0

133 205 2,128 6,574 235 0

0 0

0 9,519 SSW 95 580 111 581 1,826 6,467 8,464 8,756 518 0

0 27,398 SW 161 0

380 3,126 1,681 5,897 6,150 13,287 18,457 21,206 55,673 126,018 WSW 5,472 335 0

0 0

0 0

0 310 7,239 45,270 58,626 W

4,992 6,324 5,059 3,739 8,566 10,729 14,997 32,277 120,757 142,931 109,444 459,815 WNW 3,510 2,782 3,485 4,311 2,175 6,066 18,007 39,549 94,929 65,705 138,140 376,659 NW 4,008 673 979 1,287 1,810 6,905 21,332 39,104 118,751 280,731 98,897 574,477 NNW 5,395 1,104 1,089 1,389 2,881 6,688 9,153 16,221 82,445 56,488 46,438 229,291 587,533l Total 109,230 31,165 31,854 41,647 49,889 91,657 121,284 201,020 511,637 693,875 704,275 Revision 1 1 of 1 December 1984 O

O O

(q)

('y/)'

' (Qj) g~s

,f-~s

.Q/

1 MNPS-3 EROLS TABLE QE311.5-9 1985 POPULATION DISTRIBUTION 0-50 Miles Distance failes) 0.0-10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-1Qd 12.5 15.0 17.5 20.0 25.0 30.0 35.0 40.0 45.0 50.0 TotsI DIRECTION N

6,384 3,709 3,912 4,284 2,455 3,957 23,609 15,179 16,554 10,076 9,761 99,880 NNE 13,626 3,588 7,467 13,148 13,437 16,421 8,508 11,390 15,482 15,051 15,949 134,067 NE 33,411 3,719 4,624 2,596 1,782 4,584 4,114 9,967 17,574 51,922-113,306 247,599-ENE 24,297 8,299 3,323 4,506 6,464 8,543 7,069 12,579 24,369 50,548 84,619 234,616 E

7,872 615 1,960 3,029 4.847 7,741 1,695 5,414 7,094 1,389 1,947 43,603 ESE 821 113 0

0 0

0 0

633 0

0 0

1,567 SE O

O O

O 173 998 0

0 0

0 0

1,171 SSE O

O 61 64 444 1,881 0

0 0

0 0

2,450 S

273 0

149 230 2,388 7,380 264 0

0 0

0 10,684 SSW 107 651 125 652 2,051 7,258 9,501 9,828 582 0

0 30,755 SW 169 0

427 3,509 1,886 6,619 6,902 14,916 20,715 23,803 62,487 141,133 WSW 5,827 343 0

0 0

0 0

0 347 8,125 50,813 65,455 W

5,247 6,469 5,248 3,892 8,923 11,397 15,836 32,973 120,630 143,186 111,192 464,993 WNW 3,689 2,858 3,573 4,490 2,340 6,618 19,025 40,663 96,648 68,167 139,867 397,938 NW 4,206 722 1,034 1,350 1,911 7,399 22,266 41,515 122,277 280,976 101,434 585,090 MNW 5,593 1,191 1,188 1,500 3,103 7,290

  • 0,122 17,299 84,245 58,860 48,278 238,669 TOTAL 111,522 32,277 33,091 43,250 52,204 98,086 128,911 212,356 526,517 712,103 739,653 2,689,970 Revision 1 1 of 1 December 1984

MNPS-3 EROLS i

TABLE GE311.5-10 1990 POPULATION DISTRIBUTION 0-50 Miles Distance (milest 0.0-10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-D i rect ion M

12.5 15.0 17.5 20.0 25.0

.3_QA 35.0 40.0 45.0 50.0 Total N

6.546 3,845 4,038 4,382 2,508 4,038 24,188 15,349 16,732 10,618 10,086 102,330 NNL 13,994 3,756 7,704 13,492 13,794 16,796 9,080 12,173 16,285 15,654 16,533 139,261 NE 33,958 3,995 4.972 2,701 1,783 4,660 4,432 10,726 18,817 53,874 115,930 255,048 ENE 24,508 8,470 3,404 4,611 6,662 8,984 7,708 13,903 25,912 52,328 85,862 242,352 E

7,961 639 2,036 3,125 5,030 8,086 1,877 5,978 7,758 1,486 2,084 46,060 ESE 888 126 0

0 0

0 0

694 0

0 0

1,708 SE O

O O

O 193 1,111 0

0 0

0 0

1,304 SSE O

O 67 71 494 2,093 0

0 0

0 0

2,725 S

304 0

166 256 2,659 8,214 293 0

0 0

0 11,892 SSW 118 725 139 726 2,283 8,077 10,575 10,938 647 0

0 34,228 SW 173 0

475 3,906 2,100 7,367 7,682 16,601 23,059 26,493 69.554 157,410 WSW 6,194 348 0

0 0

0 0

0 387 9,042 56,556 72,527 W

5,473 6,556 5,355 3,992 9,230 11,849 16,307 33,430 121,678 144,531 113,678 472,079 WNW 3.854 2,933 3,649 4,691 2,480 7,057 19,843 41,837 98,320 70,148 141,846 396,653 NW 4,354 767 1,079 1,401 1,995 7,804 23,217 43,848 126,477 285,359 104,083 600,384 NNW 5,741 1,260 1,266 1,583 3,301 7,820 10,959 18,379 86,3??

61,444 50,254 248,334 TOTAL 114,066 33,420 34,350 44,937 54,512 103,956 136,161 223,856 542,399 730,977 766,4662,785,100l Revision 1 1 of 1 December 1984 O

O O

g

[%

]-

/"'~y

. _3

(

(, '

5 a

MNPS-3 EROLS'

-TABLE QE311.5-11

-2000 POPULATION DISTRIBUTION 50 Miles Distance failes) 0.0-

.10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-

-Direction E_Q 12.5 15.0 17.5 20.0-25.0 -

30.0 35.0 40.0 45.0 50.0 Total N

6,723 4,184 4,312 4,476 2,556 4,177 25,449 16,407 18,056 11,685 10,729 108,754 NNE 14,105 4,075 8,098-14,028 14,355 17,458 9,619 13,057 17,607 16,591 17,446 146,439 NE

' 33,961 4,355 5,424 2,857 1,807 4,890 4,812 11,529 20,117

-56,342 119,918' 266,012

'ENE 24,780.

8,796 3,614 4,849 6,955 9,539 8,541 14,918 28,267 56,030 89,983..

256,272 E

7,965 684 2,153 3,301 5,282 8,534 2,072' 6,297 8,710 1,556 2,181 48,735 ESE 965 142 0

0 0

0 0

694 0

0 0

1,802 1

SE 0

0 O

O 217 1,251 0

0 0

0 0

1,460 SSE O

O 76 80

.557 2,358 0

0 0

0 0

3,071 i

S 343 0

187 290 2,995 9,253 331 0

0 0

0 13,399 SSW 134 816 156 819 2,571 9,102 11,910 12,324 729 0

0 38,561 SW 178 0

535 4,399 2,366 8,300 8,656 18,701 25,974 29,844 78,347 177,300 WSW 6,785 352 0

0, 0

0 0

0 436 10,186 63,711 81,470 W

5,805 6,644 5,606 4,254 9,787 12,951 17,866 34,599 125,287 148,472 117,327 488,598 WNW 4,074 3,030 3,761 4,971 2,728 7,948 21,572 43,721 101,040 73,366 145,793 412,004 NW 4,555 849 1,175-1,516 2,168 8,606 25,062 48,039 132,619 289,048 107,362 620,999 NNW 5,896 1,441 1,479 1,759 3,516 8,42?

12,290 20,245 90,375 66,280 52,843 264.546 Total 116,269 35,'368 36,576 47,599 57,860 112,789 148,180 240,531 569,217 759,400 805,640 2,929,429 i

i m-Revision 1 1 of 1.

December 1984 i

s

s MNPS-3 EROLS TABLE QE311.5-12 s

2010 POPULATION DISTRIBUTION 0-50 Hi1es Distance fmiles) 0.0-10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-D i rect ion 10,Q 12.5 15.0 17.5 20.0 25.0 30.0 35.0 40.0 45.0 50.0 Total N

6,902 4,557 4,665 4,774 2,577 4,003 26,468 17,255 18,778 12,147 11,256 113,382 NNE 14,831 4,564 9,030 15,654 15,978 18,456 10,363 14,292 19,329 17,342 17,925 157,764 NE 36,323 5,239 6,538 3,043 1,643 4,635 5,007 12,045 20,753 57,555 122,483 275,264 ENE 25,086 9,143 3,391 4,770 7,216 9,792 9,069 15,515 29,458 57,961 92,581 263,982 E

8,187 694 2,370 3,364 5,488 8,882 2,201 6,493 9,270 1,602 2,247 50,789 ESE 1,073 165 0

0 0

0 0

694 0

0 0

1,932 SE O

O O

O 253 1,456 0

0 0

0 0

1,709 SSE O

'O 88 93 648 2,744 0

0 0

0 0

3,573 S

399 0

218 337 3,485 10,768 385 0

0 0

0 15,592 SSW 155 950 182 951

?,992 10,592 13,862 14,341 848 0

0 44,873 SW 159 0

622 5,119 2,753 9,657 10,074 21,762 30,225 34,728 91,173 206,272 WSW 7,537 341 0

0 0

0 0

0 507 11,854 74,138 94,377 W

6,041 6,458 5,395 4,190 10,097 12,769 17,085 34,344 134,595 157,780 125,673 514,427 WNW 4,279 3,151 3,822 5,442 2,848 8,225 22,179 46,163 103,799 74,321 151,134 425,363 NW 4,542 905 1,218 1,553 2,230 8,938 27,032 52,038 143,630 318,041 112,252 672,379 NNW 5,343 1,493 1,551 1,767 3,700 8,857 13,049 22,278 96,017 72,458 56,864 283,877 Total 121,357 37,660 39,090

'51,057 61,908 119,774 156,774 257,220 607,209 815,789 857,7263,125,564!

Revision 1 1 of 1 December 1984 O

O O

p 6

,r

'~

J MNPS-3 EROLS-TABLE QE311.5-13 2020 POPULATION DISTRIBUTION 0-50 Miles Distance faites) 0.0-10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-l Di rec t ion 10.0 12.5 15.0 17.5 20.0 25.0 30.0 35.0 40.0 45.0 50.0 Total N

7,014 4,983 5,080 5,168 2,555 3,607 27,369 18,277 19,522 12,194 11,703 117,472 NNE 15,699 5,159 10,292 17,946 18,246 19,640 10,980 15,459 21,209 18,000 18,318 170,948 NE 39,792 6,392 7,991 3,223 1,359-4,088 5,102 12,505 21,223 58,461 124,853 284,989 ENE 25,344 9,495-2,900' 4,492 7,465 9,994 9,680 16,036 30,448 59,698 94,562 270,114 E

8,478 679 2,641 3,362 5,693 9,258 2,388 6,665 9,774 1,645 2,307 52,890 ESE 1,181 189 0

0 0

0 0

694 0

0 0

2,064 SE O

O O

O 289 1,667 0

0 0

0 0

1,956 SSE O

O 101 107 741 3,142 0

0 0

0 0

4,091 S

457 1

249 386 3,989 12,325 440 0

0 0

0 17,847 SSW 178 1,087 208 1,089 3,426 12,126 15,868 16,418 971 0

0 51,371 SW 123 0

712 5,860 3,153 11,057 11,531 24,914 34,602 39,758 104,337 236,087 j

WSW 8,333 317 0

0 0

0 0

0 580 13,573 84,877 107,680 l

W 6,162 6,048 4,891 3,931 10,210 11,812 15,000 33,235 148,397 171,245 136,597 547,528 WNW 4,426 3,262 3,828 5,987 2,870 8,095 22,071 48,774 106,318 73,421~

157,403 436,455 NW 4,343 940 1,228 1,546 2,223 8,948 29,062 55,697 156,933 361,845 117,347 730,112 NNW 5,593 1,478 1,551

'1,665 3,783 8,978 13,273 24,299 102,680 79,395 61,252 303,947 Total 127,123 40,030 41,672 54,762 66,002 124,737 162,764 272,973 652,657 889,235 913,596 3,345,551 i

Revision 1 1 of 1 December 1984

r-MNPS-3 ER1LS TA8LE QE311.5-14 2030 POPULATION DISTRIBUTION 0-50 Miles Distance imiles)

Direc-0.0-10.0-12.5-15.0-17.5-20.0-25.0-30.0-35.0-40.0-45.0-tion 10.0 12.5 15.0 17.5 20.0 25.0_

30.0 35.0 40.0 45.0 50.0 Total N

7,070 5,457 5,560 5,673 2,494 2,977 28,129 19,404 20,179 11,791 12,064 120,798 NNE 16,790 5,867 11,916 20,976 21,229 21,035 11,529 16,632 23,285

.18,545 18,513 186,317 NE 44,593 7,855 9,835 3,405 946 3,215 5,069 12,652 21,064 58,371 125,139 292,144 ENE 25,569 9,857 2,112 3,993 7,608 9,742 9,676 16,009 30,476 59,578 94,651 269,271 rg E

8,871 637 2,972 3,260 5,758 9,358 2,450 6,690 9,831 1,649 2,312-53,788 ESE 1,289 215 0

0 0

0 0

694 0

0 0

2,198 SE O

O O

O 329 1,894 0

0 0

0 0

2,223 SSE O

O 115 121 842 3,569 0

0 0

0 0

4,647 S

519 1

283 438 4,532 14,003 499 0

0 0

0 20,275 SSW 203 1,235 236 1,238 3,890 13,774 18,027 18,652 1,102 0

0 58,357 SW 69 0

809 6,657 3,581 12,560 13,101 28,304 39,308 45,166 118,577 268,132 WSW 9,193 281 0

0 0

0 0

0 659 15,417 96,421 121,971 W

6.174 5,405 4,066 3,456 10,126 9,995 11,436 31,179 166,893 189,069 150,460 588,259 WNW 4,523 3,373 3,782 6,626 2,789 7,522 21,182 51,621 108,640 70,611 164,681 445,350 NW 3,952 954 1,20.

1,487 2,138 8,612 31,162 59,042 172,953 422,210 122,882 826,593 NNW 5,137 1,385 1,469 1,446 3,776 8,814 12,961 26,333 110,463 87,186 66,181 325,153 Total 133,952 42,522 44,356 58,776-70,038 127,070 165,2?3 287,212 704,853 979,593 971,881 3,585,476 i

l l

l Revision 1 1 of I December 1984

+

l

[

O O

O i