Monthly Operating Rept for Nov 1984
ML20101H238
Person / Time
Site: Crane 
Issue date: 11/30/1984
From: Hukill H, Smyth C
GENERAL PUBLIC UTILITIES CORP.
To: Mcdonald W
NRC OFFICE OF ADMINISTRATION (ADM), NRC OFFICE OF RESOURCE MANAGEMENT (ORM)
References
5211-84-2303, NUDOCS 8412280185
Download: ML20101H238 (6)


Text

t 1

OPERATING DATA REPORT DOCKET NO.

50-289 DATE December 18, 1984 l COMPLETED BY C. W. Smyth TELEPHONE (717) 44R.R551 OPERATING STATUS NOTES

3. UNIT NAME:

THREE MILE ISLAND UNIT 1

2. REPORTING PERIOD:

NOVEMBER,1984.

1

3. LICENSED THERMAL POWER (MWT) :

2535.

D4. NAMEPLATE RATING (GROSS MWE) :

871.

5. DESIGN ELECTRICAL RATING (NET MWE):

819.

6. MAXIMUM DEPENDABLE CAPACITY (GROSS ' MWE) :

824.

7. MAXIMUM DEPENDABLE CAPACITY (NET MWE) :

776.

8. IF CHANGES OCCUR IN (ITEMS 3-7) SINCE LAST REPORT, GIVE REASONS:
9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE)
10. REASONS FOR RESTRICTIONS, IF ANY:

THIS MONTH YR-TO-DATE CUMMULATIVE

11. HOURS IN REPORTING PERIOD 720.

8040.

89833.

12. NUMBER OF HOURS REACTOR WAS CRITICAL 0.0 0.0 31731.8
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 838.5
14. HOURS GENERATOR ON-LINE 0.0 0.0 31180.9
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 0.

O.

76531071.

17. GROSS ELECTRICAL ENERGY GENERATED (MWH)

O.

O.

25484330.

18. NET ELECTRICAL ENERGY GENERATED (MWH)

O.

O.

23840053,
19. UNIT SERVICE FACTOR O.0 0.0 34.7 i 20. UNIT AVAILABILITY FACTOR 0.0 0.0 34.7
21. UNIT CAPACITY FACTOR (USING MDC NET) 0.0 0.0 33.9
22. UNIT CAPACITY FACTOR (USING DER NET) 0.0 0.0 32.4
23. UNIT FORCED OUTAGE RATE 100.0 100.0 62.2 l
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH

( 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:

h.

4 0

PDR.

T i h

3 AVERAGE DJ.ILY UNIT POWER LEVEL DOCKET NO.

50-289 UNIT TMI-1 DATE December 18, 1984 COMPLETED BY C. W. Smyth TELEPHONE (717) 948-8551 MONTH:. NOVEMBER DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWE-NET)

(MWE-NET) 1 0,

17 0.

'2 0.

18 0.

3 0.

19 0.

4 0.

20 0.

5 0.

21 0.

6 0.

22 0.

7 0.

23 0.

8 0.

24 0.

9 0.

25 0.

10 0.

26 0.

11 0.

27 0.

12 0.

28 0.

13 0.

29 0.

14 0.

30 0.

15 0.

31 N/A 16 0.

~. -

a f

UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT NAME TM1-1 DATE December-18. 1984 _

_ u Rmuth REPORTMONTH Nnuomhor 1984 COMPLETED 8Y f{ 717) MB-8551, TELEPHONE e.

.! ?

3

.E Licensec

{g Cause & Corrective No.

D;:te g

gg g

jg5 Event g?

Action to

$E j di g Report a mU O

Prevent Recurrence H

g 5

1 84/18/12 y

720 p

i N/A ZZ ZZZZZZ Regulatory Restraint Order I

2 3

4 F: Forced Reason:

Method:

Exhibit G Instructions S: Scheduled A Equipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance of Test 2-Manual Scram.

Entry Sheets for Licensee C-Refueling 3 Automatic Scram.

Event Report (LER1 File (NUREG-D-Regulatory Restriction 4-Other (Explain) 0161)

E-Operator Training & License Examination F-Admi.. strative 5

G-Operatjonal 9tror (Explain)

Exhibit I San e Source Il-Other (Explain)

.~

NRC MONTHLY REPORT - NOVEPBER 1984

.o 4

The Unit was shut down the entire month by order of the NRC. The plant remained in cold shutdown with core cooling provided by the Decay Heat Removal System.

The RCS was partially drained most of the moith to permit continued inspections of tubes.

MAJOR SAFETY RELATED MAINTENANCE The following major maintenance items were completed during the month:

OTSGs RC-H-1A/8 i

During the month of November, Eddy current testing of Once Through Steam Generator (OTSG) tubes commenced. Work completed included the refurbishing of Eddy current test equipment, removal of the upper and lower manway covers, the installation of work tents / platforms, equipment set-up, template installa-tion, and fabrication / installation of lower temporary manway covers.

This testing is being conducted as a normally scheduled Tecii Spec surveillance and will continue into December. The results of these inspections will be forwarded, when available, under separate correspondence.

EMERGENCY DIESEL GENERATORS EG-Y-1A/B i

Work was completed on EG-Y-1A in November including coolant leak reapairs, timing adjustments, replacing lube oil filters and a satisfactory 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> test run. A DC oil pump motor was sent out for rewinding and is to be returned in December.

Timing adjustments were completed on the "B" diesel generator and trip tests were completed on both diesel generators. All tests were performed with satis-factory results.

I DECAY HEAT CLOSED COOLING PUMP DC-P-1A i

i The DC-P-1A mechanical seal installation was completed in November with seal installation, reassembly of the pump, coupling alignment and a satisfactory test run. All work is complete.

DECAY HEAT CLOSED COOLING COOLER DC-C-1A i

DC-C-1A work completed was tube cleaning, waterbox r.nd end cover cleaning, in-spection of the water box, PC-7 and coal tar epoxy installation, tube leak checks, tube thickness inspections and reinstallation of the end covers. All work is complete.

l DECAY HEAT REMOVAL PUMP DH-P-1A

.l Mechanical seal replacement work on pump DH-P-1A was completed in November.

1 The pump internals were disassembled, the old seal removed and new seal in stalled, the pump internals were reassembled into the pump casing, couplin aligned and dowel pins installed. The pump was satisfactorily tested. Al work is complete.

MAKE-UP AND PURIFICATION PUMP MU-P-1A Work commenced on MU-P-1A to resolve high current reading on the motor. The pump was test run then uncoupled from the speed increaser and alignment checked. The speed increaser then was run and uncoupled from the motor, and the alignment checked.

The inotor was test run and all data analyzed. The speed increaser high speed bearing was found to be running at a higher temperature and misalignment was found between the motor and speed increaser.

Work will continue next month with further inspections and coupling alignment.

W 1

..i

. REFUELING INFORMATION REQUEST 1.

Name of Facility:

~

Three Mile -Island Nuclear Station, Unit 1 2.

Schedule'd date for next refueling shutdown:

Unknown

~

3 Scheduled date for restart following refueling:

Unknown

h. 'Will refueling or resumption of operation thereafter' require a technical.

specification change or other license amendment?

If answer is yes, in general, what will these be?

If answer is no, has the reload fuel design and core configuration been reviewed by your Plant Safety Review Committee to determine whether any unreviewed safety questions are associated with the core reload (Ref. 10 CFR Section 50 59)?

If no such review has. taken place, when is it scheduled?

Amendment No. 50, Cycle 5 reload, was approved on 3-16-79 5

Scheduled date(s) for submitting proposed licensing action and supporting information:

N/A 6.

Important licensing considerations associated with refueling, e.g. new or different fuel design or supplier, unreviewed design or performance analysis methods, significant changes in fuel design, new operating procedures:

N/A 7

The number of fuel assemblies (a) in the core, and (b) in the spent fuel stora6e pool:

(a) 177 (b) 208 n

i 8.

The present licensed spent fuel pool storage capacity and the size of any increase in licensed storage capacity that has been requested or is planned, in number of fuel assemblies:

l The present licensed capacity is 752. There are no planned increases at this time.

[

9 The projected date of the last refueling that can be discharged to the spent

[

fuel pool assuming the present licensed capacity:

1988 is the last refueling discharge which allows full core off-load capacity (177~ fuel assemblies).

s.-

e GPU Nuclear Corporation Nuclear

,ome ar8a s

Middletown, Pennsylvania 17057 0191 717 944 7621 TELEX 84 2386 Writer's Direct Dial Number:

December 18, 1984 5211-84-2303 Office of Management Information and Program Control Attn:

W. C. Mcdonald c/o Distribution Services Branch DPC, ADM U. S. Nuclear Regulatory Commission Was hington, DC 20555

Dear Sir:

Three Mile Island Nuclear Station, Unit 1 (TMI-1)

Operating License No. DPR-50 Docket No. 50-289 November Monthly Operating Report Enclosed please find two (2) copies of the November Operating Report for Three Mile Island Nuclear Station, Unit 1.

Sincerely, p

H. D. Hukill Director, TMI-1 HDH/JGB/kds Enclosures cc:

V. Stello Dr. T. E. Murley s

h I

l h

1 GPU Nuclear Corporation is a subsidlary of the General Public Utilities Corporation g g