. ATTACHMENT 1 J;rssy Centr:I Pcw2r & Light Company

)}

Macison Avenue a: Punct. Bout Road p

,j_, L,',,

Momstown. New Jersey 07963 (201)455-8200, March 3,1980 s

Mr. Peter Koltay Huclear Regulatory Commission 631 Park Ave.

King of Prussia, PA 19406

Dear Mr. Koltay:

)

SUBJECT:

4160 Volt Fire Protection Vault

,e

=m

'7 Please~ find the following-documents and dradin'gs that you requested

~~

concerning the 4160 volt switchgear vault:

1.

System description for 4160 volt Switchgear Ro'om; 218-77-18.1, Rev. 1.

2.

Safety evaluation for the Fire Protection System Augmentation 4160 volt switchgear vault, 218-77-18.2 Rev. O.

3.

Design criteria 218-77-38, Rev. O.

~

~

4.

Installation Specification, 218-77-45, Rev. 2.

5.

Installation Specification, 218-77-61, Rev.1.

6.

GPU drawings E-1-110-313-001, Rev.1; E-1-110-313-002, Rev.1, and E-1-110-313-003, Rev.1.

-7.

Marine Fabricators drawings Job #26465 101 thru 110 Rev. 2.

8.

Bowman Construction drawings, 28555, Sheets 1, 2, and 3 dated 12-20-79.

Please be advised that some of your concerns regarding the 4160 volt vault have been<previously addressed in the following letters:-

8 041221 0

DR PDR O

i Jefiey Ct".:rs' Power 6 L g-* C,ompany is a fJe noer o'14 General Puba: Uv.1.es Systern

a.

Ivan Finfrock to the Director, NRC, dated March 23,1978; t

b.

Ivan Finfrock to the Director, NRC, dated June 1,1979.

In addition, all fire protection modifications have been reviewed in detail and approved by JCP&L's Fire Protection Consultant, Professional Loss Control Inc.

With respect to the exterior walls of the vault, they have been designed to provide a three-hour fire barrier to protect the switchgear from the lube oil fire hazard. This has been accomplished by a coating of fire retardant material applied to the exterior surfaces of the vault walls and ceiling.

Manufacturer's test data, based upon ASTM E-119 testing, indicates that a two inch coating on. Walls and decks is the required thickness needed to. provide a three-hour fire barrier..

Any fire originating inside the vault will be of short duration due to the low fire loading, the detection system, and the nanual CO.

For this 2

reason, the interior wall separating the redundant switchgear is a two-hour fire barr.ier by designet-In actuality, however.. -the' fire rating is probably much. greater..tt'Detai:1. A on GPUSC drawing E,1_110-313-001 shows..the interior.

det <ing :or wallccovered on each side with-lath and:1-11'/.16""of Pyrocrete:102.~.0

-In cordance with the.manu#acturer's-test ' data',xthis would be equivalent'.to a two-hour barrier on each side of the ~ interior wall. ~,

Concerning the seismic adequacy of Pyrocrete, manufacturer's test data indicates excellent adhesion and minor indentation without cracking resulting from impact testing, as compared with poured in-place concrete.

If you have any further questions,.please contact me.