n n

n.

g-M TENNEOCEE VAL.LEYJAUTHORIT.

+

CHATTANOOGA [ TENNESSEE s74ot

.400 Chestnut' Street Tower II:

M 84 0CT 29 QatpPG,1984'

~

BLRD-50-438/83-62 :

.BLRD-50-439/83-55'

!U.S. Nuclear Regulatory Consission

' Region II._

Attn:l Mt. : James P. 0'Reilly,: Regional Administrator.'

101 Marietta Street,: NW,- Suite 2900 Atlanta,. Georgia H 30323

Dear Mr,

" O'Re' illy:

BELLE

- NUCLEAR PLANT UNITSIl[ AND' 2 ' FUEL OIL-LINE RUPTURE IN

~

I

,TRANSAMERICA DELAVAL, INC., GENERATORS ~- BLRD-50.438/83-62, BLRD-59.439/83 THIRD INTERIM REPORT,

~

- The subject de'ficiano'y was' initially mported.'t NRC-0IE Inspector P. E. Fredrickson'on November 21, 1983 in accordance.with 10 CFR 50.55(e) '

as NCR BLN MEB 8303. This was followed.by our interim reports dated

-December 20,1983 and : April 6,.1984. LEnclosed is our third interim report..

. We expect to submit our next mport by October -15,1985. - We consider 10 CFR Part 21 applicable to this. deficiency.

If you have any questions, please 'get in touch' with R. H. Shell at FTS 858-2688.

Very.truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, nager Nuclear Licensing Enclosure oo:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of -Inspection and Enforcement U.S. Nuclear Regulatory Comunission Washington, - D.C.

20555 Records Center (Enclosure)

' Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 l

l l

OFFICIAL COPY i

n i

8411210094 841023 L

PDR ADOCK 05000438l g 2/

An Equal Opportunity Employer

. ~ -.

...-.4...-

' ENCLOSURE

~

BELLEFONTE. AND PLANT UNITS-1 AND 2

' PUEL OIL-LINE RUPTURE IN TRANSAMERICA.DELAVAL, INC.,- GENERATORS BLRD-50-438/83-62, BLRD-50-439/83.NCR'BLN MEB 8303 3

.10 CFR 50.55(e)~

~'

THIRD INTERIM REPORT' Description of Deficiency-

- l A potential problem has oeen ' identified concerning the fuel oil line from -

the engine-mounted fuel transfer pump to the engine fuel oil header on the -

standby diesel generator in that excessive. engine vibration could'cause the line to break. The resulting loss of fuel oil would shut the engine down and the subsequent fbel spray. could be ignited by the exhaust system. -

These generators are supplied to TVA by' Transamerica Delaval, Inc. (TDI) of-Oakland, California. TDI informed TVA of this potential problem in their letter. dated September. 30, 1983.

Interim Progress s

TVA is still in the process of' investigating the subject-deficiency.

Corrective actions -to be taken have been identified as reported in _our-second interim report dated April 6,1984. However, further corrective actions and a scheduled date for completion of these. actions will be provided upon implementation of the TDI diesel generator Owners group program.