ML20098H489

From kanterella
Jump to navigation Jump to search

Application to Amend Licenses DPR-57 & NPF-5,changing Tech Specs to Reflect Addition of Accumulator Leakage Rate Limits to Automatic Depressurization Sys Operability Criteria,Per NUREG-0737,Item II.K.3.28 & IE Bulletin 80-25
ML20098H489
Person / Time
Site: Hatch  Southern Nuclear icon.png
Issue date: 09/05/1984
From: Beckham J
GEORGIA POWER CO.
To:
Shared Package
ML20098H490 List:
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.K.3.28, TASK-TM IEB-80-25, NED-84-317, TAC-56047, TAC-56048, NUDOCS 8409130002
Download: ML20098H489 (3)


Text

y ..

' *- Georgia Power Cornpany

. 333 Piedmont Avenue .

Atranta. Georgia 30308

' Te!ephone 404 526-7020 Mailing Address.

Post Office Box 4545 -

- Atlanta, Georgia 30302 Georgia Power J. T. Beckham, J,- tresourru nnelectnccys:em i- vice eresident and Generat Manage' PJuclear operations NED-84-317 Septenber 5, 1984 Director of Nuclear Reactor Regulation Attention: . Mr. John F. Stolz, Chief

_ Operating Reactors Branch No. 4 Division of Licensing U. S. Ebclear Regulatory Cm mission Washington, D. C. 20555 NRC DOCKETS 50-321, 50-366 OPERATING LICENSES DPR-57, NPF-5 .

ENIN I. HATCH NUCLEAR PLANT UNITS 1, 2 REQUEST TO AMD3D TECHNICAL SPECIFICATIONS Gentlemen:

In accordance with the provisions of 10 CFR 50.90 as required by 10 CFR 50.59(c)(1), Georgia Power Cmpany proposes to anend the Plant Hatch Units 1 and 2 Technical Specifications (Appendix A to Operating Licenses DPR-57 and

.NPF-5). The ' proposed change adds accenulator leakage rate limits to the Autmatic Depressurization System (ADS) ' operability criteria. The leakage rate limits will ensure that the accmulators provide short term ADS operability in the event the pnematic supply to the ADS valves is lost, in accordance with NUEEG 0737 -Itan II.K.3.28 and I&E Bulletin 80-25.

Instructions for incorporation of the change and the affected Technical Specification pages are included in Enclosures 1 and 2.

%e proposed change has been reviewed and approved by the Plant Review Board and the Safety Review Board and has been determined not to constitute an unreviewed safety question. The probability of occurrence and the consequences of an accident or malfunction of equipnent important to safety would'not be increased above those analyzed in the FSAR because the operation of safety-related equipnent is not affected by the change.

Ebrthermore,- the leak rate tests will be performed at a pressure which will not cmprmiise the integrity of the accmulator systens. ne possibility of an accident or malfunction of a different type than any analyzed in the ESAR would not result fra this change because no new mode of operation or failure is-introduced. %e margin of safety as defined in the basis for any Technical Specification would not be reduced by this change because no existing Technical Specification is affected. The proposed change has been evaluated and has been determined not to involve a significant hazard. %is evaluation is docmented in Enclosure 3.

0409130002 840905 PDR ADOCK 05000321 W.

i

\

f 4#'N f

p PDR

e l

-.~  !

Georgia Power 1 Dir3ctor of Nuclear Reactor Regulation

- Attention: Mr. John F. Stolz, dilef Operating Reactors Branch No. 4'

, .'Septanber 5,.1984 Page Two Pursuant to 10 CFR 50.91, J. L. Leabetter of the Georgia Department of Natural Resources will be provided a copy of this sutnittal.

Payment of the appropriate licensing fee is enclosed.

J. T. Beckhan, Jr. states that he is Vice President of Georgia Power Cmpany and is authorized to execute this oath on behalf of Georgia Power Cmpany,

-and that to the best of his knowledge and belief the facts set forth in this letter are true.

GEDRGIA POWER CCMPANY By:

y J. T. Beckhan, Jf.

Sworn to subscribed fore me this 5th day of Septenber,1984.

Notary Public, Georgia, State at Large gj , __ g ,

My Commission Expires Sept.18,1987

' ' ~' Notary Public

-JHfab Enclosure xc: H. C. Nix, Jr.

Senior Resident Inspector J.' P. O'Reilly, (NRC-Region II)

J. L. Iedbetter

ENCIOSURE 1 NRC DOCKER 50-321'

. OPERATING LICENSE DPR-57

~ EDWIN I. HA'IGI' NUCLEAR PIANT UNIT 1 REQUEST 'IO AMEND TECHNICAL SPECIFICATIONS

%e proposed change to the Unit 1 Technical' Specifications (Appendix A to

Operating License DPR-57) would be incorporated as follows

Renove Page Insert Page 3.5-9 3.5-9 3.5-18 3.5-18