ML20097K052

From kanterella
Jump to navigation Jump to search
Monthly Operating Repts for Aug 1984
ML20097K052
Person / Time
Site: Dresden  
Issue date: 08/31/1984
From: Maxwell D, Scott D
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF ADMINISTRATION (ADM), NRC OFFICE OF INSPECTION & ENFORCEMENT (IE)
References
84-891, NUDOCS 8409240183
Download: ML20097K052 (20)


Text

.

k.

OPERATING DATA AEPORT DOCKET NO.

050- 237 y

DATE Sept. 10, 1984 COMPLETED BY D.' C.-Maxwellt7 TELEPHONE g33 947_797n OPERATING STATUS NOTES 1.

Unit Name:

Dresden II>

2.-

Reporting Period: Aucunt. 1984

^\\

3 Licensed Thermal Power (MWt):

2,527 4.

Nameplate Rating (Gross MWe):

828 5.

Design Electrical Rating (Met MWe): 794 6.

Maximum Dependable Capacity (Gross MWe): 812 7

Maximum Dependable Capacity-(Net MWe):

772 8.

If Changes Occur -In Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:

9.

Power Level to Which Restricted, if Any (Net MWe):

10.

Reasons For Restrictions, if Any:

This Month Yr-to-Date Cumulative.

11.

Hours in Reporting Period 744 5.855 125,375 12.

Number of Hours Reactor Was Critical 744_o 5,667.3 97.891.8 13 Reactor Reserve Shutdown Hours 0

0 0

l

14. - Hours Generator On-Line 744.0 5,565.3 96,471.3 15.

Unit Reserve Shutdown Hours 0

0 0

I6.

Gross Thermal inergy Generated (MWH) 1,681,976 12,994,536 189,689,172 17 Gross Electrical Energy Generated (MWH) 512.582 4.176.556 60,678,755 18.

Net Electrical Energy Generated (MWH) 502.443 3.978.286 57,386,550 7

19 Uni t Service Factor 100.0 95.1 76.9

, 20.

Unit Availability Factor 100.0 95.1 76.9 21.

Unit Capacity Factor (Using MDC Net) 87.5 88.0 59.3 22.

Unit Capacity Factor (Using DER Net) 85.1 85.6 57.6 l

23 Unit Forced Outage Rate 0

4.9 11.3 24.

Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

Refueline outane scheduled to begin 10-1-84 for approximately 12 weeks.

25.

If Shut Down At End Of Report Period, Estimated Date of Startup:

1 8409240183 840831 1

PDR ADOCK 05000237 I

R PDR

9 a

OPERATING DATA REPORT

~

DOCKET NO. 050- 249' DATE Sept. 10, 1984 COMPLETED BY D.~ C. Maxwell.

a TELEPHONE (815) 942-2920 OPERATING STATUS NOTES 1.

Unit Name:

Dresden III 2.

Reporting Period: Aunust. 1984 3

Licensed Thermal Power (MWt):

2,527 4.

Nameplate Rating (Gross-MWe):

828 5.

Design Electrical Rating (Net MWe): 794 6.

Maximum Dependable Capacity (Gross MWe):

812 7.

Maximum Dependable Capacity (Net MWe):

773 8.

If Changes Occur in Capacity Ratings (Items 3 Through 7) Since Last Report, Give Reasons:

9 Power Level to Which Restricted, if Any (Net MWe):

10.

Reasons For Restrictions, if Any:

This Month Yr-to-Date Cumulative.

11.

Hours in Reporting Period 744 5,855 114,960 12.

Number of Hours Reactor Was Critical 713.0 1,293.2 84,138.2 13.

Reactor Reserve Shutdown Hours 0

0 0

14.

Hours Generator On-Line 6R7.6 873.8 80,734.9 15 Unit Rese,rve Shutdown Hours 0

0 0

16.

Gross Thermal Energy Generated (MWH) 1.469.741, 1,718,334 161,679,432-17 Gross Electrical Energy Generated (MWH) 444.512 519,053 52,471,972 18.

Net Electrical Energy Generated. (MWil) 437.647 472.206 50.702.790 19 Unit Service Factor 92.4 14.9 70.2 20.

Unit Availability Factor 92.4 14.4 70.2 21.

Unit Capacity Factor (Using MDC Net) 76.1 10.2 57.1 22.

Unit Capacity Factor (Using DER Net) 74.1 6.1 55.5 23.

Unit Forced Outage Rate 7;6 L2.6 24.

Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):

N/A 25.

If Shut Down At End Of Report Period, Estimated Date of Startup:

N/A

T s

DOCKET NO. 050-237 UNIT NAME Dresden II s

UNIT SHUTDOWNS AND POWER REDUCTIONS DATE September 10, 1984 COMPLETED BY D. C. Maxwell TELEPHONE (815) 942-2920 REPORT MONTH AUGUST, 1984 METHOD OF LICENSEE CAUSE & CORRECTIVE NO.

DATE TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS)

DOWN REACTOR 3 REPORT #

CODE 4 CODES PREVENT RECURRENCE None 1

2 3

4 F: Forced Reason:

Method:

Exhibit G-Instructions for S:

Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (

) File D-Regulatory Restriction 4-Other (Explain)

(NUREG-0161)

E-Operator Training & License Examination.

F-Administrative G-Operational Error G

H-Other (Explain)

DOCKET NO. 050-249 UNIT NAME Dred n III UNIT SHUTDOWNS AND POWER REDUCTIONS DATE September 10, 1985 COMPLETED BY D. C. Maxwe11 J

TELEPl!0NE (815) 942-2920 REPORT MONTH AUGUST, 1984 i

METHOD OF LICENSEE CAUSE & CORRECTIVE NO.

DATE TYPEI DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO I

(HOURS)

DOWN REACTOR 3 REPORT #

CODE 4 CODES PREVENT RECURRENCE I

84-8-5 S

0:39 B

Rx Remained Planned turbine overspeed test.

Critical 2

4-8-21 F

55:48 A

3 84-10/036-0 3A feedwater regulator valve failure.

l 1

2 3

4 i

F: Forced Reason:

Method:

Exhibit G-Instructione for S:

Scheduled A-Equipment Failure (Explain) 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report (

) File D-Regulatory Restriction 4-Other (Explain)

(NUREG-0161)

E-Operator Training & License Examination.

F-Administrative g

G-Operational Error H-Other (Exp? nn)

j AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-237 UtilT II-DATE September 10, 1984 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920 MONTH - August, 1984 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL

-(HWe-Net)

(MWe-Net)

I 755 17 575 2

746 18 601 3

737 19 580 4

718 20 625 Q

5 729

~ 21 711 6

723 22 717 7

718 23 710 8

7 14 24 700 9

705 25 704 10 581 26 560 11 675 27 578 12 654 28 696 13 768 29 679 14 706 30 680 15 725 31 614 16 653 O

i----~

57 1

v; AVERAGE' DAILY-UNIT POWER LEVEL DOCKET NO. 050-249

.UlliT III DATE September 10, 1984 COMPLETED BY D. C. Maxwell TELEPHONE 815/942-2920 MONTH Aunust. 1984 DAY AVERAGE DAILY POWEP, LEVEL-DAY AVERAGE DAILY POWER LEVEL (HWe-Net)

(MWe-Net) 1 669 17 793 2

679 18 537 3

652 19 680 4

607 20 769 5

365 21

~717 6

540 22 0

7 564 23 0

8 622 24 235 709 462 g

25 702 551 10 26 572 yy 674 70 12 28 625 723 y3 14 30 730 15 750 3i 756 16 748

k 1

J ii f:1f'niI

)lll 4

.i i*

e NO I

T C.

t EV ITCERR O

l C

ioc deca lpe R

4 8

9 T

1 L

U A

S

/

T N

E N

S O

R U

I G

T U

C A

M 1

E L

C E

E N

S T

A U

A

/

I N

A N

E C

N U

TN N

I E

A D

M S

E D

E R

E G

D T

A A

T L

UR E

OE R

B RM Y

OU T

N E

R F

E A

L S

0 48 4

3 E

FC ON R.

A EN W

RE UT e

TN v

AI i

NA t

M never P

TNE 3

M

.P 0

I 5

UQ O

E A

l

=

DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - AUGUST, 1984 l

NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION lU2ACAD-CAM Preventive W.R. #30602 N/A N/A Calibrated instruments.

Air Compres-cor, EPN l

PI-2-2540-12 PS-2-2540-20 PT 2-2541-20 I

Alerm Recirc Corrective W.R. #36676 N/A N/A Replaced alarm card.

~

Loop Flow Linit A, G-4 MO 1501-13A Preventive W.R. #36034 N/A N/A Bench tested breaker.

Wide Rrnge Preventive W.R. #36269 N/A N/A Performed DIS 1600, Rev. 4.

Torus Level Indicator SRM Chrnnel Corrective W.R. #31455 N/A N/A Cleaned input connector.

21 e

Accum. 34-11 Preventive W.R. #36477 N/A N/A Recalibrated pressure switch.

Etat B:nk I

i LPRM 16-490 Corrective W.R. #36151 N/A N/A Replaced bulb.

RBM/APRM Preventive W.R. #36487 N/A N/A Adjusted the RBMI APRM flow converter.

Flow Conver-ter I'

SRM 23 Corrective W.R. 30663 N/A N/A Cleaned input connectors.

i Prze:ure Preventive W.R. #36132 N/A N/A Calibrated indicator.

Indicating SW 263-52B t

DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - AUGUST, 1984 i

NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U2 HPCI Room Preventive W.R. #34916 N/A N/A Replaced belts.

Cooler U2 Scram Preventive W.R. #36739 N/A N/A Replaced reset switch with like for like.

R=tt Switch D/W Closed Preventive W.R. #36688 N/A N/A Replaced all three auxiliary contacts.

Cooling Water Supply Velva 2-3702 Valva 2-2301-Preventive W.R. #36557 N/A N/A Cleaned contacts on open limit switch.

65 U2 MO 2-2301-Preventive W.R. #36847 N/A N/A Dried stack ground.

Is now clear.

j Turbine Stop Preventive W.R. #36801 N/A N/A Replaced both open and closed limit switch Valv2 Above with like for like.

j S st Drain to Sump 2301-65 U2 Glind Corrective W.R. #36280 N/A N/A Removed lamps and replaced bush covers.

S ul Leak Off Pump (HPCI Sys-tra) i RPS "A" IRM Corrective W.R. #36718 N/A N/A Replaced joy stick.

I Bvp*:s joy l

etick t

RBCCW Return Corrective W.R. #32891 N/A N/A Reset breaker trip setting to 3 for all Volvm, EPN three phases.

l

  1. 3706 i

l

O DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION

.g Shutdown Preventive W.R. #36685 N/A N/A Removed motor from MO 2-1001-5A and Cooling Dis-installed on MO 2-1001-1B.

chrrgs Valve R2fum1 Plat-Preventive W.R. #28939 N/A N/A Replaced up/down switch.

- i f.

ferm U2 Gr:pple Preventive W.R. #30819 N/A N/A Restored grapple to normal.

U2 HPCI Preventive W.R. #35038 N/A N/A Installed 4 rings of packing.

I Drein Pot, EPN #2-2301-54 2-2301-46 Preventive W.R. #29116 N/A N/A Installed new diaphragm.

HPCI Turbine Preventive W.R. #32901 N/A N/A Changed disc and seat.

l Drein Pot Trep HPCI Vent Preventive W.R. #35974 N/A N/A Disassembled valve, cleaned and installed Velve new gasket.

D2 East Preventive W.R. #35625 N/A N/A East torus access' hatch is now closed and Torus Access secured.

H:tch Rx Level Preventive W.R. #33501 N/A N/A Repacked valve.

Yerw:y f,

Valv2s, EPN

  1. LIS-2-263-l SGA f

t

r DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - AUGUST, 1984 f

NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Terus Water Preventive W.R. #36284 N/A N/A Recalibrated both recorder pens.

Tcmperature R2c'ds., EPN

  1. 2-1640-1 2 DG Crank-Preventive W.R. #34380 N/A N/A Replaced pressure switch.

f cece Pres-l cure Switch i

=)

Isoletion Corrective W.R. #36033 N/A N/A Remade connector in Control Room.

Condsnser R-d Monitor "A",

EPN

  1. 2-1705-9A

_l 2-1501-27B Preventive W.R. #34787 N/A N/A Visual inspection made. Verified proper torque settings.

Rx Bldg.

Preventive W.R. #354 II N/A N/A Repaired and replaced versa valve Exchange Fan solenoids.

Istolation Valva Suppression Corrective W.R. 635059 N/A N/A Replaced capacitor and calibrated.

Pool Temp-eratura, EPN

  1. 1641-220A f

Drywall _High Preventive W.R. #34109 N/A N/A Installed new switch.

Pressure Switch for Cont. Spray, EPN #PS 2-1501-62C

,l DRESDEN UNIT 2

Iq SAFETY RELATED MAINTENANCE - AUGUST, 1984 I

};

i, g f

NATURE OF LER OR OUTAGE MALFUNCTION

[

EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Ij s

l'.

MO 1601-57 Corrective W.R. #34848 N/A N/A Repaired lock and replaced glass, h

'Locs1 Con-

[

trol Station AO 2-2301-28 Preventive W.R. #34889 N/A

-N/A Adjusted limits.on HPCI valve 2301-28.

MO 1501-13A Preventive W.R. #35956 N/A N/A Adjusted limits on LPCI valve 1501-13A..

2-1501-27A Preventive W.R. #34379 N/A N/A Adjusted limits on.LPCI valve 1501-27A.

SDC Ieola-Preventive W.R. #36655 N/A N/A Replaced shutdown cooling valve 1001-1B.

tion Valve, EPN #2-1001-IB HFA Relay Preventive W.R. #35338 N/A N/A Adjusted contacts on the MSL tunnel HFA relay.

HPCI Turbine Preventive W.R. #35103 N/A N/A Recalibrated HPCI drain pot high level' Exchange alarm.

Drein Pot High Level Torus Level

' Preventive W.R. #33835 N/A

-N/A Recalibrated torus level transmitter.

Trensnitter IRM 16 Preventive W.R. #24658 N/A N/A Recalibrated IRM 16.

(

.1

y

^

o DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION 3 W:st LPCI Corrective W.R. #34073 N/A N/A Found defective end cover gaskets. Replaced j

Room Cooler, and checked for leak.

EPN #3-5746I IB MSIV, EP!

Corrective W.R. #34555 N/A N/A Replaced defective O' ring - refilled with I

  1. 3-0203-1B oil.

i APRM 4 Corrective W.R. #33971 N/A N/A Replaced defective switch. Performed LPRM l

card tests.

Ok.

l LPRM 40-57B, Corrective W.R. #34387 N/A N/A Replaced defective switch. Performed LPRM LPRM GRI card tests.

Ok.

TCrus to Preventive W.R. #34280 N/A N/A Repaired vacuum breakers.

Drywell l

Vccuum Brr k2rs D3 MSIV Preventive W.R. #27924 N/A N/A Rebuilt and tested MSIV pilot valves 3-Pilot Valves and 4-way.

EPN #3-203-IA D3 MSIV Preventive W.R. #27920 N/A N/A Rebuilt and tested 2-and 4-way pilot Pilot Valves, valves.

EPN #3-203-2A D3 MSIV Preventive W.R. #27922 N/A N/A Rebuilt and tested 3-and 4-way pilot Pilot Valves valves.

EPN 3-203-IC

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE E M CT M EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION D3 MSIV Pilot Preventive W.R. #27917 N/A N/A Rebuilt and tested 3-and 4way pilot Valvr;a, EPN valves.

  1. 3-203-20 U3 Rx Clean-Corrective W.R. #33895 N/A N/A Indication was removed by light grinding.

up Weld #8-3E 3B LPCI Line Corrective W.R. #33698 N/A N/A Repaired indication on weld 16-10 on "B" 1506 (Weld #

LPCI line.16-10B loop),

EPN #3-1506-B CRD 7, EPN #

Corrective W.R. #32100 N/A N/A Corrective maintenance. Replaced 3-300-14-27 control blade D-7 (14-27).

Drywell Preventive W.R. #22608 N/A N/A Replaced packing on drywell equipment Equipment drain valve 3-2001-3.

I Dirchrrge Vulv' l

202-6B Seac Preventive W.R. #34189 N/A N/A Removed and reinstalled new elbow.,

Drain Line, EPN #0288A-3/4 "A" 3 Ec:t LPCI Preventive W.R. #34074 N/A N/A Inspected and repaired leak source.

Room Cooler, EPN #3-5746A i

U3 Rx Recirc Preventive W.R. #31480 N/A N/A Removed and replaced pipe hanger.

Linr: 3-0202B U3 Rx Recire, Preventive W.R. #31479 N/A N/A Removed and replaced pipe restraint on Lina 3-0202B-line 3-0202B-28.

l 28

7 73

.+c 4

g q.

DRESDEN UNIT 3 T. :

1:

SAFETY RELATED MAINTENANCE - AUGUST, 1984 4

L f!

y.

NATURE OF LER OR OUTAGE E M CTION-EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U3 Rx Recire, Preventive W.R. #31804 N/A N/A Removed and replaced angle iron brace.-

Syst=2 3

U3 Rx Recire Preventive W.R. #31600 N/A N/A Removed and replaced pipe re'straint on line [

Syztsa Weld 3-0201B-28, weld #28 K16 (IHSI). Also.

}-

  1. 28-KI6 removed and reinstalled spring support.

j; U3 Rx Recire Preventive W.R. #31504 N/A N/A Removed and replaced pipe restraint on System Weld line 3-02021A-20,-weld #22A-10.

'i.

  1. 22A-10 U3 0202-7B Preventive W.R. #33713 N/A N/A Removed and replaced MO valve h'andle to Velva allow overlay (weld 28-15) on B loop.

U3 Rx Recire Preventive W.R. #31798' N/A N/A Removed and replaced shear lugs on line Lins 3-0202A-3-0202A-28 weld #28-7.

28 Wald t.

  1. 28-7 N/A N/A-Removed and replaced 4"x4" square tube U3 A LPCI Preventive W.R. #33348 System steel support to allow weld overlay.

Support Wald Overlay Preventive W.R. #33560 N/A N/A Removed and replaced bolted hanger to of 28-13 (B allow weld overlay of weld #28-13 (B).

Loop) D3 Pip <t Hsnger Sup-port l

1 U3 Rx Recire, Preventive W.R. #31602 N/A N/A Replaced pipe restraint and verified i

System Weld proper replacement.

[.

  1. 28-K8 l

t

-f.

a

l a

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U3 Rx Recirc4 Preventive W.R. #31636 N/A N/A Removed and replaced pipe hanger to Hcngir 23A-allow IHSI to be performed.

10 Line (3-1202-Preventive W.R. #33290 N/A N/A Removed and replaced brackets on cleanup

8) U3 Rx system lines to allow automatic weld over-Cl cnup lay on welds 8-32 and 8-34.

Br:1kars

{

U3 Rx Water Preventive W.R. #33370 N/A N/A Removed and replaced I" stainless steel clernup Line line in Rx Cleanup pipeway (3-1233-1").

(1233-1")

U3 B-LPCI 8" Preventive W.R. #33400 N/A N/A Removed and replaced 8" bolted I-Beam to Support Beam allow weld overlay of B LPCI loop.

I Wald #28-13 Preventive W.R. #33719 N/A N/A Removed and replaced angle iron brace for U3 Rx Recirc thermocouple wire to allow overlay of weld Piping Inst.

  1. 28 on B-Loop.

Brrckat I

r IRM Chranel Corrective W.R. #33748 N/A N/A Replaced IRM # 12.

l 12, EPN I

  1. UP3-762C 3-D Electro-Corrective W.R. #27846 N/A N/A Replaced "D" electromatic.

matic, EPN

  1. 2-203-D l

t D3 MSIV Corrective W.R. #27921 N/A N/A Rebuilt and tested 3-and 4-way pilot Pilot Valves.

valves.

EPN #3-203-ID I

i

a g

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Weld #28-10, Preventive W.R. #33785 N/A N/A Installed option 2 (Gamma Port) per U3 R:cire.

Station Traveler.

Piping 33 Electro-Preventive W.R. #27900 N/A N/A Replaced pilot valve.

I matic, EPN

{

  1. 3-203-B f-3C Electro-Preventive W.R. #27899 N/A N/A Replaced pilot valve.

matic, EPN

  1. 3-203-C Weld #28-14, Preventive W.R. #33617 N/A N/A Removed and replaced spring can hanger D3 Pipe to allow weld overlay of weld #28-14 l

Hing2r (Weld (B-Loop).

Ov: rlty)

B-Loop (Weld Preventive W.R. '#33690 N/A N/A Removed and replaced union on spring can.

j

  1. 28-15), U3

+

Rx R:cire, i

Piping Over-1ry, EPN Line #3-0217-F-3/4" U3 Main Corrective W.R. #31824 N/A N/A Repaired indication on (A) main steam f

Steam Line line caused by cutting torch.

(A)

I D3 MSlv Preventive W.R. #27918 N/A N/A Rebuilt and tested 3-way and 4-way pilot Pilot Valve, valves.

EPN #3-203-2C i

I I

i f..

o DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTACE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION MO 2301-3 Corrective W.R. #34962 N/A N/A Replaced base.

Abova Set-Drein AO 3-2301-64A0 Drywell Preventive W.R. #34268 N/A N/A Replaced pressure switch 3-162B.

Prc~rure Switch #3-1628B I

i Main Steam Preventive W.R. #35259 N/A N/A Replaced switch.

Linn High Flow, EPN 3

  1. dPI53-261-2G Main Steam Corrective W.R. #34858 N/A N/A Completed repairs on MSL rad monitor.

Lina Lug Rad Monitor "B" R cire.

Corrective W.R. #33473 N/A N/A Ground out flow area and repaired per Pump Suction package procedure.

Valve FB 590-123C Preventive W.R. #33999 N/A N/A Replaced relay with like for like.

Auxilirry 10 SGC Time Delry Relay 3B R:cire.

Preventive W.R. #34559 N/A N/A Limit set properly.

MG S::t Hiad S::a1 Preventive W.R. #34272 N/A N/A Adjusted limits.

LT k Velve, j

EPN #3-220-51

D ~, W J c

. o DRESDEN UNIT'3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 i:

NATURE OF ~

LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Chrnnel A Preventive W.R. #33256 N/A N/A All alarms trips worked and reset properly.,

Reactor Replaced alarm on A channel.

Scram Annun-cistor J;

West SDV Preventive W.R. #34107 N/A N/A Adjusted ~open and close limit switch l

Drain Valve, on valve.

).

.EPN #3-302-157B l'

CRD 22-55, Preventive W.R. #33848 N/A N/A Replaced solenoid and o-rings.

F-14 CRD F-14 Preventive W.R. #33834 N/A N/A Replaced solenoid and o-rings.

(22-55), EPN

  1. 22-55-120 1<

MOV 3-220-1 Preventive W.R. #33399 N/A N/A Removed and reinstalled jumpers.-

i'

.N/A N/A Adjusted and checked all limit switches.

I U3 Torus to Preventive W.R. #34038 f,

Druw.all Vecuum l:

Brerkers, EPN #1601-31

& 32 I

1501-28A MO Preventive W.R. #34474 N/A N/A Verified and inspected torque switch Velva settings.

1501-28B MO Preventive W.R. #34475 N/A N/A Verified and inspected torque switch Valva settings.

1501-27B MO Preventive W.R. #34476

'N/A N/A

, Verified and inspected torque switch Valva settings.

t.

1

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE N m 0N EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION U3 LPCI Preventive W.R. #34034 N/A N/A Adjusted magnetic switch to give proper Ta t"ble indication.

Check, EPN

  1. 3-1501-25B C1:anup Preventive W.R. #33730 N/A N/A Replaced relay 595-128.

Iol tion Volv2 3-1201-1 Slrck Cable Preventive W.R. #33645 N/A N/A Replaced nut and adjusted slack cable Relcy limit.

U3 HPCI Roor Preventive W.R. #34494 N/A N/A Replaced belts and adjusted pulleys.

Cool r, EPN

  1. 3-5747 Bus 34-1 Corrective W.R. #31638 N/A N/A Reversed polarity on bus 34-1 syncro.

Syncro.

check relay.

Ch';ck Relay Abova Core Preventive W.R. #35009 N/A N/A Repaired and calibrated core spray Pl'te AP above core plate AP potentia meter.

Call I

U3 2301-35 Preventive W.R. #33167 N/A N/A Replaced light bulb at HPCI local panel.

I MOV U3 Rx Recirc. Preventive W.R. #31437 N/A N/A Removed and reinstalled pipe restraints Systcm on two recirculation lines to allow for IHSI coil replacements.

N/A N/A Tested hydrarlic and mechanical snubbers.

Snubbers Preventive W.R. #30463

,.)

n f)

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION SRM Chrnnel Preventive W.R. #28352 N/A N/A Replaced integrator module on SRM 24, 24, EPN#

RM3-750-1D Clrnup Line Preventive W.R. #32162 N/A N/A Removed and reinstalled pipe support on Support, EPN RWCU line.

  1. 1201-M-108 U3 Rx. Recirc. Corrective W.R. #33894 N/A N/A Removed by grinding and welding indica-Line 3-0201B-tion on the B recirculation pum, 28 "A" Facdwater Corrective W.R. #32949 N/A N/A Removed by grinding and welding indication N4D Line on the A feedwater line.

32(ME, EPN

  1. Weld #21-1 SRM rnd IRM Preventive W.R. # 19601 N/A N/A Replaced all SRM and IRMcables.

C:bica l

U3 Drywell Preventive W.R. #34097 N/A N/A Removed old diesel cooling water pump and Cooling H2O installed new one.

i Pump j

Bu3 34-1 Preventive W.R. #33268 N/A N/A Replaced target and seal in unit for over Relry Type voltage reset.

IAC U3 Electrical Preventive W.R. #28454 N/A N/A Performed routine relay calibration.

Prntretive Rel"ya HPCI MO 3-Preventive W.R. #33226 N/A N/A Performed routine relay calibration.

2301-3 Local Controller

~

DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - AUGUST, 1984 NATURE OF LER OR OUTAGE NECU EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION High Density Preventive W.R. #23873 N/A N/A Welded straps (2) SS.

Fuel Rack MO 1501-3B Preven ive W.R. #36262 N/A N/A Replaced light sockets with like for like.

Local Opera-t~r Dicral Gener-Preventive W.R. #36341 N/A N/A Replaced both TB and LOTS. Calibrated ster Tcmpera-per instrument data. card, tura Switches 3A C re Spray Corrective W.R. #36046 N/A N/A Replaced conduit connectors.

Motcr U3 ACAD/ CAM Preventive W.R. #31689 N/A N/A Adjusted and calibrated ACAD/ CAM drywell Drywell H.P.

high pressure switch - Units PS 3-254 0- 16 A,

Switch 2s 19A, 18B, 19B, 20 and 21 in the Control Room.

D3 Diesel Preventive W.R. #36334 N/A N/A Replaced and recalibrated diesel genera-i Generator tor pressure switch, PS3-6600-LWS.

W7. tar Pres-cura Switch, EPN #PS3-6600-LWS I lstion Preventive W.R. #27258 N/A N/A Replaced and lapped isolation valve conden :er 3-1301-3.

I S2fa Return Iwlttion i

V:lva, EPN

  1. 3-1301-3 i-
;.
j
  • L DRESDEN UNIT 2/3 i

SAFETY RELATED MAINTENANCE - itUGUST, 1984 HATURE OF LER OR OUTAGE MWNUM i EQUIPMENT

. MAINTENANCE NUMBER

,CAUSE RESULT CORRECTIVE ACTIC4I l

Rx V:nt and Preventive W.R. #32705.

N/A N/A Bench checked the listed sensor conver-iFuel Pool tors.

' Se =or" Con-

?

vertero EPN

i

  1. 1735A5B 1743A&B 2/3 Rx Bldg.

Preventive W.R. #36324 N/A N/A Welded paddle bar.-

t Crcne

' Spare IRM Preventive W.R. f35136 N/A N/A Installed and tested inop inhibit' push :

unenitor button on spare IRM monitor.

Ycrway Valve Preventive W.R. #36461 N/A N/A Replaced o-ring in valve manifold.

Manifold f

Rx Sidg.

Preventive W.R. #36923 N/A N/A Adjusted F.H.L.S. to accomodate restricted Crcn2 mode surveillance.

t 2/3 Rx Bldg.

Preventive W.R. #31823 N/A N/A Repaired shorted wire, f,

Overhee.d j

Crcna 2/3 Diecel Preventive W.R. #36844 N/A N/A Installed two rebuilt heat exchangers for Generctor 2/3 diesel generator.

f; Coolcnt Heat Exch nger o

Genercter May, 1984.

~

l 2/3 Discel Preventive W.R. #35398 N/A N/A Performed quarterly inspection during-Rosemount Preventive W.R. f35379 N/A N/A Bench tested amplifier.

Amplifier

  1. 1151-0137-0001 3

i

-ij s.

DRESDEN UNIT 2/3 SAFETY RELAiED MAINTENANCE - AUGUST, 1984 MALFUNCTION NATURE OF LER OR OUTAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Spare Quad Preventive W.R. #34027 N/A N/A Checked and repaired cards.

Trip Cards Rosemount Preventive W.R. #35380 N/A N/A Found Q3 failed. Replaced Q3 and bench Amplifier tested amplifier.

Model #01151-0008 DP Transmit-Preventive W.R. #31312 N/A N/A Repaired and calibrated Rosemount AP ters, EPN transmitters.

  1. 3-2541-002A TN-9 Cask Preventive W.R. #36525 N/A N/A Used emery cloth to remove three burrs on the upper south trunion of the TN-9 cask.

Barton Ampli-Preventive W.R. #36290 N/A N/A Resoldered thermistoc leads LPCI heat fier for 368 exchanger AP transmitter.

Transmitter Quad Trip Preventive W.R. #35727 N/A N/A Tested quad trip card test box for proper Card (Test operation. Found ok.

l Box) i HPCI Sig.

Preventive W.R. #35156 N/A N/A Bench tested HPCI signal convertor

' Conv. Ampli-amplifier #SP650.

fier #SP650 HPCI Sig.

Conv. Ampli-fier #SP650 Preventive W.R. #35157 N/A N/A Spare HPCI Signal Convertor amplifier failed bench test and junked.

I

h a

SUMMARY

OF OPERATING EXPERIENCE UNIT ONE AUGUST, 1984 The status of Unit I remains shutdown with all fuel removed. The environ-ment and equipment continues to be maintained as needed.

On August 31,.1984, an announcement was made by CECO. Corporate Offices that as of this date Unit I has been officially retired.

Chemical cleaning activities are continuing and during " mock runs" small leahs developed in some flanges and pump seals which necessitated delays.

It is expected in September, that another " mock.run" will'be performed and soon after that actual chemical cleaning of piping will be in operation.

1 i

f P

d 4 I

r a

} f J

mc

~

W.

e

=o.

SUMMARY

OF OPERATING EXPERIENCE UNIT TWO AUGUST, 1984' Unit 2 entered the month operating'at a power level of 775 MWe and operated continuously during the entire month (with normal power reductions for weekend surveillances). reaching a power level of 785 MWe with a capacity factor 'of 85.48% and an availability of 100%.

1 i

i 4

-r-~

y s.m y

-e

..-y.-.

y

p.

y r*

s

- e e

SUMMARY

OF OPERATING EXPERIENCE UNIT THREE

. AUGUST, 1984 08-01 to 08-05 Unit 3 entered.the month operating'at 680 MWe and was-limited by th'e condensate decineralizer differential pressure.. Load was ' reduced on August 4th in preparation for the planned turbine overspeed test which took place 4

early in the morning-of August 5th.

08-05 to 08-24 The unit operated from the '5th through August 21st when -

the 3A Feedwater Regulator valve failed and the unit scrammed. Prior to bringing the unit on-line, the Rx scrammed on August 22nd because of improper mode switch movement by the operator and on August 23rd the Rx 4

scrammed because of an IRM hi-hi condition by the LH. Dept.

The unit was brought on-line on August 24th.

08-24 to 08-31 The unit operated continuously during the remainder of the month reaching a power level of 780 MWe with a capacity factor of 74.78% and an availability of 92.41%.

i i

d 9

i y.e

+

w-Fy y

w t--

-7 9

r*-

w g

<r-c y

eV-

~

o e

-0 UNIQUE REPORTING REQUIREMENTS

' MAIN STEAM RELIEF VALVE OPERATIONS Relief valve operations during the reporting period are summarized in the following table. The table includes information as to which relief valve was actuated, how it was actuated, and the circumstances.resulting in its actuation.

Valves Description Unit Date Actuated Actuations Conditions of Events 1

08-01-84 to 08-31-84 None 2

None 3

None l

t l

~~

l i

IN Commonwealth Edison

-[

') Dresden Nucle r Power Sttion c2

(

y"--

--.. R.R. #1

\\

Morris, Illinois 80450

\\

j Telept one 815/942-2920 i

September 10, 1984 DJS LTR: 84-891 Director, Office of Inspection and_ Enforcement United States Nuclear Regulatory Commission Washington, DC 20555 Attention: Document Control Desk

Dear Sir:

Enclosed, please_ find Dresden Station's operating data for last month. This information is supplied to your office per the instruc-tions set forth in Regulatory Guide 1.16.

Sincerely,

_a (N UI i

D.

. Scott Station Superintendent Dresden Nuclear Power Station 4

DJS: BAS:hjb Enclosure cc: -Region III, Regulatory Operations, U.S. NRC Chief, Division Nuclear Safety, State of IL U.S. NRC, Document Management Branch Nuclear Licensing Administrator Nuc. Sta. Div. Vice Pres.

Manager, Tech. Serv. Nuc. Sta.

Tech. Staff AE On-Site NRC Inspector Sta. Nuc. Eng. Dept.

Comptroller's Office PIP Coordinator INPO Records Center File /NRC Op. Data File / Numerical f

'll