Application for Amends to Licenses NPF-9 & NPF-17, Implementing Generator Time Overcurrent Protection for Diesel Generators.Fee Paid
ML20096G003
Person / Time
Site: McGuire, Mcguire  
Issue date: 08/31/1984
From: Tucker H
DUKE POWER CO.
To: Adensam E, Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML20096G006 List:
References
TAC-55787, TAC-55788, NUDOCS 8409100309
Download: ML20096G003 (3)


Text

.-~

DUKE POWER GOMPANY P.O. BOX 33189 CHARLOTTE, N.G. 28942 HAL B. TUGKER us.rpuon me ressme"?

(704)373 4531

~ W11 cleat Pepet;CTION August 31, 1984 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation

- U. S. Nuclear Regulatory Commission

-Washington, D. C. 20555 Attention:

Ms. E. G. Adensam, Chief Licensing Branch No. 4

~

Subject:

McGuire Nuclear Station Docket Nos. 50-369 and 50-370

Dear Mr. Denton:

Attached are proposed license amendments to Facility Operating Licenses NPF-9 and NPF-17 for McGuire Nuclear Station Units 1 and 2, respectively.

The proposed amendment seeks to implement a Generator Time Overcurrent Protection for the diesel generators. The Generator Time Overcurrent Protection trips the associated diesel generator in the event of a multiphase fault on the switchgear bus to prevent the destruction of the diesel generator. This trip is not bypassed in the event of an Engineered Safeguard Signal. The switchgear fault is assumed to occur only on one bus, therefore the redundant diesel generator train is not affected and is available to meet the safety load requirements. Thus the Generator Time Overcurrent Protection only prevents the destruction of a diesel generator in the event of a major switch gear fault which would in any case prevent it from fulfilling its safety function.

A related modification is also planned to protect the diesel generators during testing. An Instantaneous Overcurrent Protection will be implemented to protect the generators during the testing periods. This trip will be automatically bypassed in the event of an Engineered Safeguard Signal and

- would not interfere with operation of any safety system.

The affected portion of the Technical Specifications is the surveillance requirements for the diesel generators (Technical Specification 4.8.1.1.2.e (7) (c)). Attachment I contains the proposed Technical Specification change.

Attachment II contains the Justification and Safety Analysis in support of the proposed change. Attachment III provides an analysis in accordance with the standards of 10CFR50.92 as required by 10CFR50.91. These analyses conclude f

that the proposed amendment has been reviewed and has been determined to have

%cP(

{

no adverse safety or environmental impact.

e

)

asflW D

D 0

W

,4s

m Mr. Harold'R. Denton,~ Director August 31, 1984 Page Two The necessary station modifications will be implemented following NRC approval of this proposed change. The request involves one application for amendment to the McGuire Technical Specifications. Accordingly,

pursuant to 10 CFR 170.21 a check for $150.00 is enclosed.

Please feel free to contact us if your require any additional information.

Very truly yours, AfA Hal B. Tucker WHMcD: sib

' Attachments cc: Mr. James P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Suite 2900 101 Marietta Steet, NW Atlanta, Georgia 30323 W. T. Orders Senior Resident Inspector McGuire Nuclear Station

Mr. Harold 'R.

Denton, Director -

August 31, 1984 Page Three HAL B. TUCKER, being duly sworn, states that he is Vice President of Duke Power Company; that he is authorized on the part of said Company to sign and file with the Nuclear Regulatory Commission this revision to the:McGuire Nuclear Station License Nos. NPF-9 and NPF-17 and that all statements and matters set forth therein are true and correct to the best of his knowledge.