_ _ _ _ _ _ _ _.
r+.,
Thomes J. Martin Public Service Electric and Gas Company 80 Park Plaza Newark, N.J. 07101 201/430-8316 -
Vice President Engineering and Construction c;0'g6 August 20, 1984 Dr.. Thomas E. Murley, Administrator U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region I 631 Park Avenue King of Prussia, Pennsylvania 19406
Dear Dr. Murley:
POTENTI AL CONSTRUCTION DEFICIENCY DESIGN DEFICIENCY-UNDERRATED CABLE HOPE CREEK GENERATING STATION On July 20, 1984, a verbal report was made to Region I, Office of Inspection and Enforcement representative, Mr.
E.
C. McCabe, advising of a potentially significant construction l
deficiency concerning underrated electrical cable.
The following interim report is provided in accordance with 10CFR50.55(e).
l Our Architect;/ Engineer and Constructor, Bechtel, has informed us of a Hope Creek design deficiency specifying cable with a i
conductor temperature rating of 90 C for connection to Valcor solenoid valves.
Bechtel has determined that the terminal block temperature of these solenoid valves dictates the use of connection cable with a rating of 150 C.
This design deficiency applies to the Hope Creek Instrument Gas Compressor System.
A report conveying the requisite safety analysis and details concerning our corrective action is expected to be submitted to your office by September 28, 1984.
Very truly yours, s'
/
8409100240 840820 PDR ADOCK 03000354 i
' 8 PDR Il 0 12-f)
' ~ '
t w
+
-,j y ;,;
Dr. T.
E.
Murley_
2 8-20--84 C... Office.of Inspection and Enforcement
~ Division of Reactor Construction. Inspection -
Washington, D. C. 20555 NRC' Resident Inspector - Hope Creek;.
P. ~ O. -Box - 2 41 Hancocks Bridge, NJ '08038 Records - Center'-
' Institute of Nuclear Power Operations 1100 Circle 75. Parkway, Suite-1500 Atlanta, GA 30339