"L,

"*2 Thomas J. Martin Public Service Electric and Gas Company 80 Park Plaza Newark. N.J.07101 201/4304316 Vice Presidens Engineering and Construction September 28, 1984 Dr. Thomas E. Murley, Administrator U. S. Nuclear Regule. tory Commission Of fice of Inspection and Enforcement Region I fN (B[h 631 Park Avenue King of Prussia, Pennsylvania 19406

Dear Dr. Murley:

POTENTIAL CONSTRUCTION DEFICIENCY BIF BUTTERFLY VALVES IiOPE CREEK GENERATING STATION On August 31, 1984, a verbal report was made to Region I, Office of Inspection and Enforcement representative, Mr. E.

j Kelly, advising of a potentially significant construction deficiency concerning butterfly valves supplied by BIF Industries.

The following interim report is provided in accordance with 10CFR50.55 (e).

Our Architect / Engineer and Constructor, Bechtel, has informed us that a cleanliness inspection of two (2) butterfly valves supplied by BIF Industries revealed extensive corrosion damage to the tapered pins securing the valve stem to the disc.

A review of the BIF fabrication drawing determined that the pins 1

were to be made of Monel (ASME SB 164, C1. B).

Iloweve r, chemical analysis of one of the corroded pins indicates that the material is apparently 400 series stainless steel.

Such a stainless steel would be galvanically dissimilar to the alwninum bronze disc material and susceptible to corrosion.

Bechtel has issued Nonconformance Report No. 3711 to document and control the discrepant hardware.

j A report conveying the requisite safety analysis and details concerning our corrective action is expected to be submitted to your of fice by November 2, 1984.

Very truly yours, 1060581 840928

/6) 1 D

ADOCK 050003S4 8

PDR 9

or

r=

-3

-g.

s i.

j s

Dr.

T.

E. Murley 2

9-28-84 i

C Office of Inspection and Enforcement Division of Reactor Construction Inspection Washington, D. C. 20555 NRC Resident-Inspecto'r - Hope Creek -

P. O.-Box 241 Hancocks Bridge, NJ~08038 1

J Records Center Institute of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 Atlanta, GA 30339 i

4 l

l 4

i i

1 1

1 I

I 1

i 4

, _ _.