..t IMSCORSin Electnc POWER COMPANY 231 W. MICHIGAN, P.O. BOX 2046, MILWAUKEE, WI 53201 July 11, 1984 Director of Regulatory Operations U. S. NUCLEAR REGULATORY COMMISSION Washington, D.

C.

20555 Gentlemen:

MONTHLY OPERATING REPORTS POINT BEACH NUCLEAR PLANT Attached are monthly operating reports for Units 1 and 2, Point Beach Nuclear Plant, for the calend.r month of June 1984.

Also attached is a revision to the May 1984 monthly operating report form AD-28B " Unit Shutdowns and Power Reductions" for Point Beach Unit 2.

This report has been revised to correct the sequential number for the shutdown listed on the form.

Very truly yours, n

de Vice Presiden Nuc ear Power C. W. Fay Attachments Copies to J.

G. Keppler - NRC, Region III NRC Resident Inspector C.

F. Riederer - PSCW k

[

O R

';1

N.

a e.

OPERATING DATA REPORT DOCKE T NO. SC -2 56 DATE July 1, 1984 COMPLETED BY

0. U. FAY TELEPHONE 414 277 2811 OPERATING STATUS
1. UNIT NAME: POINT BEACH NUCLEAR PLANT UNIT 1

. NOTES

2. REPORTING PERIOD:

JUNE 1984

3. LICENSED THERMAL POWER (NUT):

1518.

4. NAMEPLATE RATING (GROSS MWE):

523.8

5. DESIGN ELECTRICAL RATING (NET MWE): 497.
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 509.
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):

485.

8. IF CHANGES DCCUR IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NOT APPLICA0LE

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (HET MWE): NOT APPLICABLE
10. REASONS FOR RESTRICTIONS, (IF ANY): NOT APPLICABLE THIS NONTH YR TO DATE CUMULATIVE
11. HOURS IN REPORTING PERIOD 720 4,367 119,663
12. NUMPER OF HOURS REACTOR WAS CRITICAL 720.0 2,018.4 96,096.9
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 3.0 629.3
14. HOURS GENERATOR ON LINE 720.0 1,984.5 93.592.0
15. UNIT RESERVE SHUTDOWN HOURS 0.0 5.8 799.3
16. GROSS THERMAL ENERGY GENERATED (MWH) 1,076,350 2,870,430 126,405,742
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 369,630 991,280 42,387,260
18. NET ELECTRICAL ENERGY GENERATED (MWH) 353,890 941,040 40,303,474
19. UNIT SERVICE FACTOR 100.0 45.4 78.2
20. UNIT AVAILABILITY FACTOR 100.0 45.6 78.9
21. UNIT CAPACITY FACTOR (USING MDC NET) 101.3 44.4 68.9
22. UNIT CAPACITY FACTOR (USING DER NET) 98.9 43.4 67.8
23. UNIT FORCED OUTAGE RATE 0.0 0.0 2.6
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH):

{Ti NONE

)

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: NOT SHUTDOWN O

DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER DATED SEPTEMBER 22. 1977 n

?

DOCKl:T NO.

50-266 UNIT NAME Point Beach Unit 1 DATE July 9, 1984 COMPLETED BY C.

J.

Krause TELEPHONE 414/277-2001 AVERAGE DAILY UNIT POWER LEVEL MONTH June, 1984 AVERAGE AVERAGE AVERAGE DAILY DAILY DAILY POWER LEVEL POWER LEVEL POWER LEVEL DAY MWe NET DAY MWe NET DAY MWe NET 1

501 11 490 21 496 2

501 12 489 22 497 3

484 13 497 23 496 4

500 14 497 24 437 5

501 15 492 25 478 6

-499 16 496 26 469 7

501 17 496 27 479 8

498 18 496 28 494 9

500 19 496 29 500 10 499 20 490 30 478 31 EQR-28a 501-79) n v

m

UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

50-266 UNIT NAME Point Beach Unit 1 REPORT MONTH June, 1984 COMPLETED C

. Kr TELEPHONE 414/277-2001 e

m 4

C

'M tv o D

o-N oCD Ev C

e-4 e4 to C

-< o ee en e

ou o

mee em Ce No.

Date g

eg y

jjg Licensee Event gg o'g Cause and Corrective Action g

am e

v4 Report No.

m EU To Prevent Recurrence Q-M gmg g

8 i

i 1

3 4

F: Forced Reason:

Method:

Exhibit G-Instruc-S: Scheduled A-Equipment Failure (explain) l-Manual tions for Prepar-B-Maintenance or Test 2-Manual Scram ation of Data Entry C-Refueling 3-Automatic Scram Sheets for LER File l D-Regulatory Restriction 4-Other (explain)

(NUPEG-0161)

E-Operator Training & License Exam F-Administrative 5 Exhibit I-Same AD-28B G-Operational Error (explain)

Source 301-78)

H-Other (explain) x

.m

NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE Docket No.

50-266 Unit Name Point Beach Unit 1 Date July 9, 1984 Completed By C. W. Krause Telephone 414/277-2001 Unit 1 operated at approximately 498 MWe net throughout the period with no significant load reductions.

There has been no indication of primary-to-secondary steam generator leakage.

Significant safety-re' lated maintenance included modifying the steam-driven auxiliary feed pump discharge valves, work on the " fire system water backup to the bearing coolers" modifi-cation on the steam-driven auxiliary feed pumps, and a visual bearing inspection and oil change on the 3D emergency Diesel.

d

e t

OPERATING DATA REFORT DOCKET NO. 5t -:-01 DATE July 5, 1984 COMPLETED BY C. W. FAY TELEPHONE 414 277 2811 OPERATING STATUS

1. UNIT NAME: POINT BEACH NUCLEAR PLANT UNIT 2

. NOTES

2. REPORTING PERIOD:

JUNE 1984

3. LICENSED THERMAL POWER (MUT): 1518.
4. NAMEPLATE RATING (GROSS MUE):

523.8

5. DESIGN ELECTRICAL RATING (NET MWE): 497.
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 509.
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): 485.
8. IF. CHANGES OCCUR IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT, GIVE REASONS:

NOT APPLICABLE

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE): NOT APPLICABLE
10. REASONS FOR RESTRICTIONS, (IF ANY): NOT APPLICABLE THIS HONTH "R TO DATE CUMULATIVE
11. HOURS IN REPORTING PERIOD 720 4,367 104,448
12. NUMBER OF HOURS REACTOR WAS CRITICAL 720.0 4,341.6 92,769.8
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 8.8 207.1 14 HOURS GENERATOR ON LINE 720.0 4,277.9 91,180.7
15. UNIT RESERVE SHUTDOWN HOURS 0.0 15.4 198.1
16. GROSS THERMAL ENERGY GENERATED (MWH) 1,083,029 4,375,044 127,269,821
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 369,260 2,153,340 43,113,170
18. NET ELECTRICAL ENERGY GENERATED (MWH) 352,925 2,057,767 41,058,367
19. UNIT SERVICE FACTOR 100.0 98.0 87.3
20. UNIT AVAILABILITY FACTOR 100.0 98.3 87.5
21. UNIT CAPACITY FACTOR (USING MDC NET) 101.1 97.2 80.0
22. UNIT CAPACITY FACTOR (USING DER NET) 98.6 94.8 79.1
23. UNIT FORCED OUTAGE RATE 0.0 0.0 1.4
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE. AND DURATION OF EACH):

Five-week refueling outage scheduled to begin on September 28, 1984.

25. IF SHUTDOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: NOT SHUTDOWN DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC LETTER DATED SEPTEMBER 22, 1977

DOCKET NO.

50-301 UN:.T NAME Point Beach Unit 2 D A'..'E July 9, 1984 COllPLETED BY C.

W.

Krause TELEPHONE 414/277-2001 AVERAGE DAILY UNIT POWER LEVEL MOUTH June, 1984 AVERAGE AVERAGE AVERAGE DAILY DAILY DAILY POWER LEVEL POWER LEVEL POWER LEVEL DAY MWe NET DAY MWe NET DAY MWe NET 1

495 11 494 21 491 2

496 12 493 22 492 3'

496 13 495 23 491 4

495 14 494 24 468 5

496 15 489 25 495 6

494 16 493 26 483 7

494 17 437 27 489 8

494 18 495 28 493 9

495 19 494 29 493 10 495 20 493 30 482 31 EQR-28a (01-79)

'e UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-301 UNIT NAME Point Beach Unit 2 REPORT MONTH June, 1984 COMPLETED Y C W.

Kr s

TELEPHONE 414/277-2001

'"u c

tH tn o o

M "c

.St Pe en

- e ou o

mee om ce No.

Date g

  • g g

jyy Licensee Event gg g'g Cause and Corrective Action e

om e

v.c Report No.

m Eo To Prevent Recurrence Q~

M e t/) C o

2:

U 0

1 F: Forced Reason:

3 Method:

Exhibit G-Instruc-S: Scheduled A-Equipment Failure (explain) l-Manual tions for Prepar-B-Maintenance or Test 2-Manual Scram ation of Data Entry C-Refueling 3-Automatic Scram Sheets for LER File D-Regulatory Restriction 4-Other (explaia)

(NUREG-0161)

E-Operator Training & License Exam F-Administrative 5

4D-28B Exhibit I-Same G-Operational Error (explain)

Source (01-78)

H-Other (evnlain)

~

NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE Docket No.

50-301 Unit Name Point Beach Unit 2 Date July 9, 1984 Completed By C. W.

Krause Telephone 414/277-2001 Unit 2 operated at approximately 494 MWe net throughout the period with no significant load reductions.

On June 21, 1984, Unit 2 achieved 43 billion kilowatt hours of generation.

Primary-to-secondary steam generator leakage remains at less than 10 gallons per day.

A Licensee Event Report was submitted regarding the inadvertent safety injection actuation during shutdown described in last month's report.

There was no significant safety-related maintenance performed during this period.

Revision 1 07-09-84 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-301 UNIT NAME Point Beach Unit 2 REPORT MONTH May, 1984 COMPLETED C

kr s

TELEPHONE 414/277-2001 m

4 C

W tD o 4

on N

oc4 Ev c

,a wm c

-et u oe en e

ou o

mee o

as No.

Date D.

5D m

ooe Licensee Event v 'o m

05 Cause and Corrective Action N

$.5

  • Report No.

gu g.O To Prevent Recurrence o-gmg g

8 2

840518 S

89.1 B

1 N/A ZZ 5ZZZZZ Conducted corrective maintenance on moisture separator reheater, con-denser waterboxes and incore flux thimble plugs.

~

1 4

F: Force 8 Reason:

Method:

Exhibit G-Instruc-S: Scheduled A-Equipment Failure (explain) l-Manual tions for Prepar-B-Maintenance or Test 2-Manual Scram ation of Data Entry C-Refueling 3-Automatic Scram Sheets for LER File D-Regulatory Restriction 4-Other (explain)

(NUREG-0161)

E-Operator Training & License Exam F-Administrative 5

LD-2 8B Exhibit I-Same G-Operational Error (explain)

Source (01-78)

H-Other (explain)

.