ML20092P316

From kanterella
Jump to navigation Jump to search
Rev 1 to Environ Qualification Master Equipment List
ML20092P316
Person / Time
Site: Vermont Yankee Entergy icon.png
Issue date: 05/09/1984
From:
VERMONT YANKEE NUCLEAR POWER CORP.
To:
Shared Package
ML20092P309 List:
References
NUDOCS 8407060162
Download: ML20092P316 (55)


Text

I gl . . ,

ENCLOSURE 2 ENVIRONMENTAL QUALIFICATION MASTER EQUIPMENT LIST Revision 1 8407060162 840629 PDRADOCK05000g P

k

.a.~__.__- _ _ = _ _ _ _ . _ _ _ _ _ _ . . _ _ . _ _ . _ . ..

VERM0NT YANKEE NUCLEAR P0WER STATION FRODlKED : 64/05/07 ENVIRONMENTAL QUALIFICATION CF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST FACE 1

!  !  ! QUALIFICATION ! CEFICIENCY/  !

ID NLMBER  ! WMACTURER ! MOCEL N.NBER ! STATUS  ! RESOLUTION  ! COMMENTS 8

CONTAIEMENT ATMOSPHERIC DILUTION SYSTEM FS0-109-75A-1  ! ATK0MATIC ' 15840-VPI-MOD ! JCO-1  ! NO DOC / REPLACE  !

FS0-109-75A-2 ! ATK0MATIC  ! 15840-VPI-MOD ! JCO-1  ! NO CCC/ REPLACE  !

F50-109-75A-3  ! TARCET ROCK  ! 75E002  ! QUALIFIED  !  !

F50-109-7%-4  ! TARCET ROCK  ! 75E002  ! QUALIFIED  !  !

FS0-109-75B-1  ! ATK0MATIC  ! 15840-VFI-MOD ! JCO-2  ! NO DOC / REPLACE  !

F50-109-72B-2 ! ATK0MATIC  ! 15640-VPI-MOD ! JCO-2  ! NO DOC / REPLACE  !

F50-109-75C-1  ! ATKOMTIC  ! 15840-VPI-M0D ! JCO-2  ! NO DOC / REPLACE  !

F50-109-75C-2 ! ATKOMTIC  ! 15640-VPI-MOD ! JCO-2  ! NO DOC /REFtACE  !

F50-109-75D-1  ! ATK0MATIC  ! 15840-VFI-M0D ! JCO-?  ! NO DOC /REFtACE  !

F50-109-75D-2 ! ATK0MATIC'  ! 15840-VPI-POD ! JCO-2  ! NO DOC / REPLACE  !

FSO-109-76A  !  !  ! QUALIFIED  !  ! CATEGC6Y D FSO-109-76B  ! TARGET ROCK  ! 82-U  ! QUALIFIED  !  !

NG-11A  !  !  ! QUALIFIED  !  ! CATEGORY D NG-11B  !  ! ' QLiALIFIED  !  ! CATEGORY D NG-12A  !  !  ! QUALIFIED  !  ! CATEGORY D NG-12B  !  !  ! QUALIFIED  !  ! CATEGORY D NG-13A  !  !  ! QUALIFIED  !  ! CATEGORY D NO-13B  !  !  ! QUALIFIED  !  ! CATEGORY D SAH-VG-5A  ! TELEDYPE  ! 225CMA-2  ! QUALIFIED  !  !

SAH-VG-5B  ! TELEDYNE  ! 225CMA-2  ! QlALIFIED  ! '

VG-9A  !  !  ! QUALIFIED  !  ! CATECORY D VG-95  !  !  ! QUALIFIED  !  ! CATEGORY D VG-22A  !  !  ! RIALIFIED  !  ! CATEGORY D VG-22B  !  !  ! QUALIFIED  !  ! CATEGORY D VG-23  ! TARCET ROCK  ! 75E002  ! QUALIFIED  !  !

VG-24  ! TARCET ROCK  ! 75E002  ! RIALIFIED  !  !

VG-25  ! TARGET ROCK  ! 75E002  ! QUALIFIED  !  !

VG-26  !  !  ! O A IFIED  !  ! CATEGORY D VG-33  ! TARCET ROCK  ! 75E002  ! CUALIFIED  !  !

VG-34  ! TARCET ROCK  ! 75E002  ! QUALIFIED  !  !

t EMERGENCY POWER SYSTEM A-ECCS BATT  ! C+D  ! KC-9  ! QUALIFIED-  !'  !

A-ECCS BC  ! C+D  ! ARR24CE50F3 ! JCO-3  ! RAD +HELB DATA /REi.0CATE ! NOTE 2 A-ECCS DP  ! PERCURY  ! -! QUALIFIED  ! .!'

B-ECCS BATT -  ! C+D  ! KC-9  ! QUALIFIED  ! ~!

B-ECCS BC  ! C+D  ! ARR24CE50F3 ! JCO-3 - ! PAD +HELB DATA / RELOCATE ! NOTE 2 B-ECCS DP  ! MERCURY  !  ! QUALIFIED  !  !'

DC-14  !  !  ! QUALIFIED  !  ! CATEGC6Y D

.. . .. _. ~ ._ _ - ,- -

I i

VERM0NT YANKEE NUCLEAR P0WER STATION PRORiCEL : 84/05/09 ENVIRONMENTAL QUALIFICATICN CF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PAGE 2

-~ !  !  ! OURIFICATICN ! IEFICIENCY/  !

ID NUMBER  ! MANUFACTURER ! MOCEL MBER ! STATUS  ! RESOLUTION  ! COMMENTS L .

E M E R 0 E N.C Y P0WER SYSTEN (CfNTINLED)

DC-1B  !  !'  ! QUALIFIED  !  ! CATEGORY D DC-2A  ! WESTINGHOUSE ! TYPE W  ! JCD-5  ! DOC /QDR  !

DC-2B

' '!  ! 00ALIFIED  !  ! CATECORY D MCC-8B ' WESTINGHOUSE ! TYPE W  ! JCO-5  ! KC/0DR  !

MCC-BE  ! WESTIN4 0JSE ! TYPE W  ! JCO-5  ! DOC /0DR  !

MCC-9B  ! WESTINGHOUSE ! T)PE W ' JCO-5  ! 000/0DR  !

MCC-9D  ! WE5TINGH0 LEE ! TYPE W  ! JCD-5  ! i)CC/QDR  !

MCC-89A  ! ITE  ! 5600  ! OUALIFIED  !  !

MCC-895  ! ITE  ! 5600  ! M R IFIED  !  !

PP-89  ! WESTINGHO:SEJ  !  ! JCO-5  ! DOC /0DR  ! FART OF MCC-9D UPS-1A  !  !  ! QUALIFIED  !  ! CATEGORY D LFS-1B  !  !  ! GUALIFIED  !  ! CATEGORY D VAC-B  ! CEN ELECTRIC !  ! QUALIFIED  !  !

HEATING & VENTILATION SYSTEM RRU-5  ! RELIANCE ELEC !  ! QLE IFIED  !  !

RRU-6  ! RELIANCE ELEC !  ! OUALIFIED  !  !

RRU-7  ! RELIANCE ELEC !  ! OUALIFIED  !  !

RRU-8  ! RELIANCE ELEC !  ! QUALIFIED  !  !

STANDBY GAS ThiATHENT SYSTEM. ,

EUH-2  ! CHROMALOX 9W !D106-l!4426-000! JCO-9  ! NO DOC /QC6  !

ElH-4  ! CHROMALOX 9 G !D106-il4426-000! JCO-9  ! NO DOC /0DR  !

FS-1-125-1A  ! MCK6ALD/ MILLER! NP-8  ! JCO-10  ! NO DOC / REPLACE  !

FS-1-125-1B  ! MCDONALD / MILLER! NP-8  ! JCO-10  ! NO DOC /REFtACE  !

LS-SB-1A  ! MICR0 SWITCH  ! OPD-AR-6809' ! JCO-!!  ! RAD /QDR  !

LS-55-15  ! MICROSWITCH - ! CFD-AR-6809 ! JCO-Il  ! RAD /0C6 -  !

LS-SE-2A  ! MICR05 WITCH  ! OPD-AR-6809 ! JCO-!!  ! RAD /QDR  !

LS-SB-2B  ! MICROSWITCH  ! OPD-AR-6809 ! JCO-Il  ! RAD /0E6  !

LS-55-3A  ! MICR0 SWITCH  ! OPD-AR-6809 ! JCO-Il  ! RAD /0DR  !

LS-SB-3R -  ! MICROSWITCH !CFD-AR-6009 ! JCO-11  ! RAD /00R  !

LS-SB-4A  ! MICROSWITCH  ! OPD-AR-6809 ! JCO-11  ! RAD /0DR  !

LS-SB-48  ! MICR0 SWITCH  ! OPD-AR-6009 ! JCO-Il  ! RAD /0DRt  !

LS-SB-5  ! MICR0 SWITCH  ! 0PD-AR-6809 ! JCO-!!  ! RAD /Qf6  !

REF-2A  ! RELIANCE ELEC !  ! 00ALIFIED  !  !

REF-2B  ! RELIANCE ELEC ! -! 00ALIFIED  !  !

SB-1A  ! ASCO  ! 206-380-7F  ! OUALIFIED  !  !

SB-!B  ! ASCO  ! 206-300-7F  ! OUALIFIED  !  !

~

l I

e 1 VERM0NT YANKEE NUCLEAR POWER STAT!ON PRODUCED : 64/05/09. .

l ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIFitENT MASTER EQUIPMENT LIST PAGE 3

~

' !  !  ! RRIFICATION ! [EFICIEEY/  !

ID NLMEER  ! MANLFACTURER ! MOCEL MMBER ! STATUS  ! RESOLUTION  ! COMMENTS r

'STANDBI. OAS TREATMENT SYSTEN (CONTINLED)

SB-2A  ! ASCO  ! 206-380-7F  ! OVALIFIED  !  !

SB-2B  ! ASCO  ! 206-380-7F  ! OVALIFIED  !  !

SB-3A  ! ASCO -' 206-380-7F  ! QUALIFIED  !  !

SB-3B  ! ASCO  ! 206-380-7F  ! RRIFIED  !  !

SS-4A  ! ASCO  ! 206-380-7F  ! OlR IFIED  !  !

SB-4B  ! ASCO  ! 206-380-7F  ! QUALIFIED  !  !

SB-5  ! ASCO  ! 206-380-7F  ! QUALIFIED  !

TSH-1-125-15A ! CMOMALOX  !  ! JCO-12  ! NO DOC /CDR  ! FART OF ELECTRIC HFATER(EtH-2)

TSH-1-125-15B ! CHROMALOX  !  ! JCO-12  ! NO DOC /QDR !PART OF ELECTRIC HEATER (ELH-4)

NUCLEAR BOILER SYSTEM WJ-2-80A  ! ASCO  ! NP8323A36V  ! OlR IFIED  !  !

A0V-2-809  ! ASCO  ! NPS323A36V  ! 00ALIFIED  !  !

A0'J-2-80C  ! ASCO  ! NP8323436V  ! OUALIFIED  !  !

A0V-2-80D  ! ASCO  ! N#8323A36V  ! RIALIFIED  !  !

A0V-2-66A  ! ASCO  ! W8323A36V  ! MIALIFIED  !  !

MJ-2-86B ' ASCO  ! NP8323A36V  ! OlR IFIED  !  !

A0V-2-86C  ! A500  ! NP8323A36V  ! OVALIFIED  !  !

A0V-2-86D  ! ASCO  ! W 8323A36V  ! OlRIFIED  !  !

LS-A0V-2-80A  ! NANCO  ! EA-740  ! OUALIFIED  !  !

LS-A0V-2-80B  ! NAMCO  ! EA-740 !QUALIFjED  !  !

LS-A0V-2-80C  ! M MC0  ! EA-740  ! OUALIFIED  !  !

LS-A0V-2-80D .! NANCC  ! EA-740  ! OlRIFIED  !  !

LS-A0V-2-844  ! NAMCO  ! EA-740  ! OlR IFIED  !  !

LS-A0V-2-86B  ! NANCO  ! EA-740  ! OlRIFIED  !  !

LS-A0V-2-86C  ! NAMCO  ! EA-740 ' QUALIFIED  !  !

LS-A0V-2-86D  ! NAMCO ' EA-740  ! OlR IFIED  !  !

FCV-2-39  ! ASCO  ! 206-823-3  ! 00ALIFIED  !  !

FCV-2-40  !  !  ! OVALIFIED  ! .! CATE00RY D FT-2-110A  !  !  ! R E IFIED  !  ! CATECG Y D' FT-2-110B  !  !  ! QUALIFIED  !  ! CATECGY D FT-2-!!0C  !  !  ! OUALIFIED  !  ! CATECGY D FT-2-!!00  !  !  ! OlR IFIED  !  ! CATECGY D MOV-2-534  ! LIMITORQUE '! SMB-2  ! JC0-13.  ! RAD /REPL4CE N0 TOR + BRAKE!

MOV-2-538  ! LIMITORQlE  ! SMB-2  ! JCO-13  ! RAD / REPLACE MOTOR + BRAKE!

MOV-2-54A  ! LIMITORQUE  ! SMB-000  ! R RIFIED  !  !

MOV-2-54B  ! LIMITORRE  ! SMB-000  ! 00ALIFIED  !  !

NOV-2-66A  ! LIMITC6 ME  ! SMB-000  ! JCO-14  ! RAD / REPLACE NOTCR  !

l' s

u .._ .. - .. .u-.--~.-.--.-. . ~ . - . - - --

h s-VERH0NT YANKEE NUCLEAR P0WER STATION PRORCED : 64/05/09 EWIRCNMENTAL QUALIFICATICN CF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PAGE 4

- !  !  ! OlRIFICATICH ! DEFICIENCY /  !

ID NUMBER  ! MANUFACTLRER ! N0fEL NLMPER ! STATUS  ! RESOLUTICW  ! COMMENTS C

NUCLEAk B0ILER SYSTEM (CONTINUED)

MOV-2-66B  ! LIMITORQUE  ! SMB-000  ! JCO  ! RAD / REPLACE MOTOR  !

MOV-2-74  ! LIMITORQlE  ! SMB-000  ! JCO-15  ! RAD /REPLME MOTOR  !

- MOV-2-77  ! '!  ! OlRIFIED  !  ! CATEGORY D PS-2-71-1A  ! SOR  ! M-E3-CIA  ! JCD-16  ! N0 TEST DATA /PCFtACE  !

!  ! GGMMRTTX10  !  !  !

PS-2-71-1B  ! SOR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST DATA / REPLACE  !

'  !  ! GGMMRTTX10 - !  !  !

PS-2-71-lC  ! SOR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST DATA / REPLACE  !

!  ! 00MMRTTX10  !  !  !

PS-2-71-ID  ! SCR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST DATA /REFtACE  !

!  ! GGMMRTTX10  !  !  !

PS-2-71-2A  ! SOR  ! 6N-E3-CIA  ! JCO-16 8 NO TEST DATA / REPLACE  !

! ' GGttRTTX10  !  !  !

PS-2-71-2B  ! SOR  ! M-E3-CIA  ! JCO-16  ! NO TEST DATA /REPLME  !'

!  ! GGMMRTTX10  !  !  !

PS-2-71-2C  ! SOR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST DATA / REPLACE  !

!  ! CGMMRTTX10  !  !  !

PS-2-71-2D  ! SOR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST MTA/REPL ME  !

!  ! GGMMRTTX10  ! '  !

PS-2-71-3A  ! SOR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST M TA/ REPLACE  !

!  ! GGMMRTTX10  !  ! .!

PS-2-71-3B  ! SCR  ! 6N-E3-CIA  ! JCO-16.  ! h0 TEST DATA /REFtACE  !

!  ! GGNMRTTX10  !  !  !

PS-2-71-3C  ! SCR  ! 6N-E3-CIA  ! JCO-16  ! NO TEST DATA / REPLACE  !

!  ! ggt 1RTTX10  !.  !  !

PS-2-71-3D  ! SOR  ! 6N-E3-CIA  ! JCO-16.  ! NO TEST DATA /REPLM E  !

!  ! GGiMRTTX10  !  !  !

PS-2-128A  !  !  ! OlR IFIED  !  ! CATEGORY D PS-2-1283  !  !  ! glr IFIED  !  ! CATEGORY D PS-2-134A  ! BARKSDALE  ! B27-A12-SS  ! JCO-18  ! NO TEST DATA / REPLACE  !

PS-2-134B  ! BARKSDALE  ! B2T-Al2-SS  ! JCO-18  ! NO TEST MTA/REPLKE  !

r PS-2-1340  ! BARKSMLE  ! B2T-Al2-SS  ! JCO-18  ! NO TEST DATA /REPLME  !

PS-2-134D  ! BARKSDALE 8 B2T-A12-SS  ! JCO-18  ! NO TEST DATA /REPLME  !

W-2-71A .! ASCO  ! 206-381-6F  ! QUALIFIED  !  !

RV-2-718  ! ASCO  ! 206-381-6F  ! OUALIFIED  !  !

RV-2-710.  ! ASCO  ! 206-381-6F-  ! OVALIFIED  !  !

RV-2-71D '! ASCO  ! 206-381-6F  ! 00ALIFIED  !  !

SRV MONITOR  ! CEN. ELECTRIC ! 21984061  ! JCO-17  ! TEMP + PRESS /QIR  ! l Y: - . I

VERM0NI YANKEE NUCLEAR POWER STATION PRODUED 2 84/05/09 ENVIRONMENTAL QUALIFICATION CF ELECTRICAL EQUIFtENT

^

MASTER EQUIPMENT LIST PAGE 5

' !  !  ! QUALIFICATICN ! [EFICIENCY/  ! 1 ID NUMBER  ! MANLFACTLRER ! N0 EEL NUMBER ! STATUS  ! RESOLUTICH !COMMEhTS NUCLEA( B0ILER SYSTEM (CONTINUED)

PM.-!!2D1943G005 TS-2-121A  ! FEN 6AL  ! 17002-40  ! JCO-20  ! N0 TEST M TA/PEFtACE  !

TS-3-121B-  ! FENWAL '! 17002-40  ! JCO-20  ! NO TEST DATA / REFT EE  !

TS-2-121C  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST DATA / REPLACE  !

TS-2-121D  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST DATA /REftACE  !

TS-2-122A  ! FEhwAL  ! 17002-40  ! JCO-20  ! NO TEST DATA / REPLACE  !

TS-2-122B  ! FENWAL  ! 17002-40 ' ! JCO-20  ! NO TEST DATA /REFtACE  !

TS-2-122C  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST DATA / REPLACE  !

TS-2-122D  ! FENWAL  ! 17002-40  ! JCD-20  ! NO TEST DATA /REFtACE  !

TS-2-123A  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST M TA/REFtACE  !

TS-2-123B  ! FEMAL  ! 17002-40  ! JCO-20  ! h0 TEST DATA /REPL EE  !

TS-2-123C  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST MTA/REFLACE  !

TS-2-123D  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST DATA / REPLACE  !

TS-2-124A  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST DATA /REPLEE  !

TS-2-124B  ! FENWAL  ! 17002-40  ! JCO-20  ! NO TEST DATA / REPLACE  !

TS-2-124C  ! FENWAL  ! 17002-40  ! JCD-20  ! NO TEST MTA/ REPLACE  !

TS-2-124D  ! FENWAL  ! 17002-40  ! JC0-20  ! NO TEST DATA / REPLACE  !

ZE-2-1A  ! ENIEVC0  ! 2273AM20  ! JCD-21  ! TOC /EIn  !

ZE-2-1B ' ENTEVC0 ' 2273Af@  ! JC0-21  ! DOC / Din  !

ZT-2-1A  ! B+W  !  ! JCD-21  ! TEMP + PRESS / REFT EE  !

ZT-2-1B  ! B+W  !  ! JCO-21  ! TEMP + PRESS / REFT EE  !

NUCLEAR BOILER VESSEL INSTRUMENTATION SYSTEM LITS-2-3-73A  ! YARWAY  ! 441C(E  ! JCO-26  ! RAD LACKIN0/ REPLACE  !

LITS-2-3-7]B  ! YARWAY  ! 4418CE  ! JCO-27  ! RAD LACKIN0iREFLACE  !

LT-2-3-57A  ! ROSEM0lNT  ! 1152DF4  ! QUALIFIED  !  !

LT-2-3-57B  ! ROSEM0lNT  ! 1152If4  ! QUALIFIED  !  !

LT-2-3-58A  ! ROSEMOUNT  ! 1152ff4  ! QUALIFIED  !  !

LT-2-3-588  ! ROSEM0LNT  ! 1152DP4  ! QUALIFIED  !  !

LT-2-3-72A ~ ! ROSEMOUNT  ! Il52DP4  ! QUALIFIED  !  !

LT-2-3-72B  ! ROSEM0LNT  ! 1152ff4 -! QUALIFIED  !  !

LT-2-3-72C  ! R05910VNT  ! 1152If4  ! QUALIFIED  !  !

LT-2-3-72D  ! ROSEM0LNT  ! !!52DP4  ! QUALIFIED  !  !

PS-2-3-52C-  ! BARKSDALE  ! B2T-M12-SS  ! JCO-28  ! NO TEST DATA / REPLACE  !

PS-2-3-52D  ! BARTON  ! 26M-7572  ! JCO-28  ! INStFFICIEhT DOC / REPLACE!

PT-2-3-55A  ! R05EM0lNT  ! 1152 Fe  ! OllALIFIED  !  !

PT-2-3-55B  ! Rt/xRNT  ! !!52GP9  ! QUALIFIED -!  !

PT-2-3-55C - ! ROCEM0lNT  ! !!520P9  ! QUALIFIED  !  !

- 2 _, _]

__ .._ _ _ . _ . ~ . . _ . . _ _ _ _ _

]

VERM0NT YANKEE NUCLEAR P0WER STATION PR0INED 84/05/09.

ENVIRONMENTAL DIRIFICATION OF ELICTRifAL EQUIPMENT MASTER EQUIPMENT LIST PACE 6

!  !  ! OlRIFICATICN ! IfFICIENCY/  !

ID NUMBER  ! f%huFACTLRER ! ICDEL NtNBER ! STATUS  ! RESCLUTION !CONMENTS t

NUCLEA$. B0ILER VESSEL !NSTRUNENTAT10N SYSTEN (CONT!NLED)

PT-2-3-55D  ! ROSEM0lNT  !!!52GP9 ' OtRIFIED  !  !

PT-2-3-56A  ! ROSEMalNT  ! 1152CM  ! QUALIFIED  !  !

PT-2-3-56B  ! ROSEM0LNT  ! !!526P9  ! OUALIFIED  !  !

PT-2-3-56C  ! ROSEMXNT  ! Il526P9  ! QLE IFIED  !  !

PT-2-3-560  ! ROSEM0 TNT  ! !!52CM  ! OtR IFIED  !  !

2-3-5'4(M)  ! ROSEMOUNT  ! 510DU  ! 00ALIFIED  !  !

2-3-55A(X)  ! ACASTAT  ! EGP9001  ! QUALIFIED  !  !

2-3-55B(M)  ! ROSEM0LNT  ! 5100U  ! OVALIFIED  !  !

2-3-55B(X)  ! A6ASTAT  ! E0PB001  ! OtRIFIED  !  !

2-3-55C(M)  ! ROSEM0 TNT  ! 510[U  ! JCO-33  ! IELB TEMP / REPLACE  !

2-3-55C(X)  ! ACASTAT  ! ECM 001  ! JCO-34  ! WLB TEMP /0DR  !

2-3-55D(M)  ! ROSEMOUNT  ! 510[U  ! JCO-33  ! WLB TEMP /REPLA G  !

2-3-55D(X)  ! AGASTAT  ! ECM 001  ! JCO-34  ! HELB TEMP /0DR  !

2-3-56A(M)  ! R0 FEM 0LNT  ! 510fC  ! JCO-22  ! RAD /DESICW C)MNGE  !

2-3-56A(SI)  ! ROSEM0UNT  ! 510EU  ! JCO-22  ! RAD /IESIGN CHANGE  !

2-3-56A(X)  ! ACASTAT  ! E0P9001  ! JCO-23  ! RAD /0DR  !

2-3-56A(Xf)  ! AC4 STAT  ! EGPB001  ! JC0-23  ! RAD /QDR  !

2-3-56BtM)  ! ROSEM0LNT  ! 5100U  ! JCO-24  ! RAD + TEMP / REPLACE +I60N CHG!

2-3-56B(S1) !ROSEM0LNT  ! 510[0  ! JCO-24  ! RAD +TET/ REPLACE +DSCN CH0!

2-3-54B(X)  ! AC4 STAT  ! EGPB001  ! JCO-25 -! RAD + TEMP /QDR  !

2-3-56B(X1)  ! KASTAT  ! EGPB001  ! JCO-25  ! RAD + TEMP /OfG  !

2-3-56C(M)  ! ROSEMOUNT ' 510D0  ! JCO-227  ! RAD /[ES!GN CHANGE  ! ..

2-3-56C(SI)  ! ROSEMOUNT  ! 510IU  ! JCO-22  ! RAD /DESICN C)%NCE  !

2-3-56C(X)  ! K4 STAT  ! ECM 001  ! JCO-23.  ! RAD /OfR  !

2-3-56C(XI)  ! AGASTAT  ! EGPB001  ! JCO-23  ! RAD /QIR  !

2-3-56D(M)  ! ROCEMOUNT  ! 510fC  ! JCO-24  ! RAD + TEMP / REPLACE +DSGN CH0!

2-3-56D(SI)  ! ROSEMOUNT  ! 510D0  ! JCO-24  ! RAD + TEMP / REPLACE +DSGN CHG!

2-3-56D(X)  ! KASTAT  ! ECM 001  ! JCO-25  ! RAD + TEMP /QDR -!

2-3-56D(XI)  ! ACASTAT  ! EGP9001  ! JCO-25  ! RAD + TEMP /Of6  !

2-3-57 AIM)  ! ROSEMOUNT  ! 510fC  ! QUALIFIED  !  !

2-3-57A(SI)  ! ROSEMOLNT  ! 510N  ! OlR IFIED  !  !

2-3-57A(S2)  ! ROSEMOUNT  ! 510fC  ! QUALIFIED  !  !

2-3-57AIX) .! ACASTAT  ! E0PB001  ! QUALIFIED  !  !

2-3-57A(II).  ! AC4 STAT  ! E6F9001  ! OtRIFIED  !  !

2-3-57A(X2)  ! ACASTAT  ! E0PB001  ! OtR IFIED  ! .  !

2-3-57B(M)  ! ROSEM0 TNT- '! 510D0  ! 00ALIFIED  !-  !

2-3-57B(SI)  ! ROSEM0 TNT  ! 510fC  ! QUALIFIED  !  !

2-3-57B(S2)  ! ROSEMOUNT -  ! 51000  ! QUALIFIED  !  !

. - . VERM0NT YANKEE NUCLEAR P0WER STATION PRCCJCED : 84/05/00 ENVIRONMEhTAL QUALIFICATICN OF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PAGE 7

!  !  ! 00ALIFICATICN ! IEFICIENCY/  ! -

IDfdJMBER  ! MANLFACTUFER ! WarEL NLHBER ! STATUS ! RESCtVTICN ' COMMENTS

,e i i  !  !

NUCLEA B0ILER VESSEL IN5TRUMENTATION $YSTEM (CONTINlED)

! QUALIFIED  !  !

2-3-57B(X)  ! AGASTAT  ! EGFB001 2-3-57B(X1)  ! K4 STAT  ! ECfB001  ! QUALIFIED  !  !

2-3-57B(X2)  ! G STAT  ! EGPB001  ! QUALIFIED  !  !

2-3-5M(M)  ! R05EM0thT  ! 510iC  ! JCO-33  ! HELB TEMP /REFtACE  !

2-3-58A(SI)  ! ROSEM0LNT  ! 510E0  ! JCO-33  ! HELB TEMP /FIPLACE  !

! 510rC  ! JCO-33  ! HELB TEMP /REFtACE  !

2-3-58A(S2)  ! ROSEK W T 2-3-58A(X)  ! AGA5 TAT  ! EGPB001  ! JCO-34  ! HELB TEMP /QDR  !

! JCD-34  ! HELB TEMP /QIG  !

2-3-5M(XI)  ! KASTAT  ! EGPB001 2-3-58A(X2)  ! AC45 TAT  ! ECfB001  ! JCO-34  ! HELB TEMP /QIG  !

2-3-ESB(M)  ! ROSEMC&T  ! 510IU  ! JCO-33  ! HELB TEMP / REPLACE  !

2-3-58B(SI)  ! RC5EM0lHT  ! 510DU  ! JCO-33  ! HELB TEMP /REFtACE  !

2-3-5SB(S2)  ! ROSEMOUNT  ! 5100U  ! JCO-33  ! HELB TEMP / REPLACE  !

2-3-58B(X)  ! AGA5 TAT  ! ECfB001  ! JCO-34  ! HELB TEMF/QER  !

2-3-58B(X1)  ! AGA5 TAT  ! ECfB001  ! JCO-34  ! HELB TEMP /Qi6  !

2-3-58B(X2)  ! AGA5 TAT  ! ECfB001  ! JCO-34  ! HELB TEMP /CER  !

2-3-72A(M)  ! ROSEMOUNT  ! 510D0  ! JCO-22  ! MD/IESIGN CHANGE  !

2-3-72A(51)  ! ROSEMOUNT ' 51000  ! JCO-22  ! RAD /IESIGN CHANCE  !

2-3-72A(52)  ! ROSEWUNT  ! 5100U  ! JCO-22  ! MD/[ESIGN CHANGE  !

2-3-72A(53)  ! R05EM0lNT  ! 510IU  ! JCO-22  ! MD/IESIGN CHAKE  !

2-3-72A(54)  ! R05EM0th7  ! 510rC  ! JCO-22  ! PAD /IESIGN CHANCE  !

2-3-72A(55)  ! RC6EKONT  ! 510E0  ! JCO-22  ! RAD / DESIGN CHANCE  !

2-3-72A(X)  ! K45 TAT  ! ECfB001  ! JC0-23  ! RAD /QIR  !

2-3-72A(X1)  ! AGASTAT  ! ECfB001  ! JCO  ! RAD /QCR  !

2-3-72A(X2)  ! AGASTAT  ! ETR14B3B001  ! JCO-23  ! RAD /QER  !

2-3-72A(13)  ! AC45 TAT  ! EGPB001  ! JCO-23  ! RAD /QDR  !

2-3-72A(X4)  ! AGASTAT  ! EGFB001  ! JCO-23  ! RAD /QDR  !

2-3-72A(X5)  ! AGA5 TAT  ! ECFB001  ! JCO-23  ! RAD /QDR  !

2-3-72B(M)  ! ROSEN ST  ! 510C0  ! JCO-24  ! RAD + TEMP /REFtACE+f6CA CHG!

2-3-72B(SI)  ! RO5EMOUNT  ! 51000  ! JCO-24 !RAf+ TEMP / REPLACE +DSCW CHG!

2-3-72B(52)  ! ROSEMC@ T  ! 5100U  ! JCO-24 !RAE* TEMP /PIPLACE+DSCW CM!

2-3-72B(53)  ! ROSEMOUNT  ! 510D0  ! JCO-24  ! RAD + TEMP / REPLACE +DSGN CHG!

2-3-72B(54)  ! ROSEMOUNT  ! 510[0  ! JCD-24 !RAf*TElf/REFLACE+D5CW CM!

2-3-72B(55)  ! RC6EM0lNT  ! 510fC  ! JCO-24 !MDvTEMP/ REPLACE +DSGN CHG!

2-3-72B(X)  ! AGA5 TAT  ! ECfB001  ! JC0-25  ! RAD + TEMP /QEA  !

2-3-72B(X1)  ! K4 STAT  ! ECfB001 ' JCO-25  ! RAD + TEMP /QE6  !

2-3-72B(X2)  ! AGASTAT  ! ETR14B3B001  ! JCC-25  ! RAD + TEMP /QDR '!

2-3-72B(X3)  ! K4 STAT  ! EGPB001  ! JCO-25  ! RAD + TE!F/QCR  !

2-3-72B(X4)  ! KASTAT  ! ECfB001  ! JCO-25  ! RAD + TEMP /QIn  !

m ...,_n_.,,_ ....__--__.,.___.. ._._ e - j

- - - . . ~ . - , - ~ , . - ~ - - . . - . . . . - - . . - - .. ..

VERM0NT YANKEE NUCLEAR POWER-STATI0N PRODUCED : 64/05/09 ENVIRONMEhTAL QUALIFICATION OF ELECTRICAL EQUIFtENT MASTER EQUIPMENT LIST PEE 8

~ !  !  ! QUALIFICATICN ! [EFICIENCY/  !

ID MER  ! MAN.FACTLRER ! MOTEL NUMBER ! STATUS  ! RESOLUTION !CCittEhTS c.

NUCLEA& B0ILER VESSEL INSTRUMENTATION SYSTEM (CfNTINlED) 2-3-72B(X5)  ! AGASTAT  ! EGPB001 - ! JCO-25  ! RAD + TEMP /QDR  !

2-3-72C(M)  ! ROSEMOUNT  ! 510DU  ! # 0-22  ! RAD /IESICW CHANCE  !

2-3-72C(SI)  ! ROSE N T ~! 510D0  ! JCO-22  ! RAD /IE5IGN CNE  !

< 2-3-72C(52)  ! ROSEM0LNT  ! 510D0  ! JCO-22  ! RAD /IESICW C M E  !

2-3-72C(S3)  ! ROSEMOUNT  ! 510IU  ! JCO-22  ! RAD /IESIGN CHAEE  !

2-3-72C(X)  ! KASTAT  ! ECfB001  ! JCO-23  ! RAD /QIR  !

2-3-72C(XI)  ! ACASTAT  ! ECfB001  ! JCO-23  ! RAD /QER  !

2-3-72C(X2)  ! AGASTAT  ! ETR14B3B001  ! JCO-23  ! RAD /QIR  !

2-3-72C(X3)  ! E4 STAT  ! EGPB001  ! JCO-23  ! RAD /QER  !

2-3-72D(M)  ! ROSEMRNT  ! 51000  ! JCO-24  ! RAD + TEMP /PIPLKE+[66N CHG!

2-3-72D(S1)  ! ROSEMOUNT  ! 510DU  ! JCO-24 !EAD+ TEMP /REPLE F+DSGN C E !

2-3-72D(S2)  ! ROSENLhT  ! 5100U  ! JCO-24  ! PAD +TENP/REPLEE+D5CW CHG!

2-3-72D(S3)  ! ROSEM0thT  ! 510DU  ! JCO-24  ! RAD + TEMP / REPLACE +DSGN CHG!

2-3-72D(X)  ! AC45 TAT  ! ECfB001 8 JCO-25  ! RAD + TEMP /QiR -!

2-3-72D(X1)  ! MASTAT  ! ECfB001  ! JCO-25  ! RAD + TEMP /QER  !

2-3-72D(X2)  ! EASTAT  ! ETR14B38001 ! JCO-25  ! FAD + TEMP /QIR  !

2-3-72D(X3)  ! AGASTAT  ! EGPB001  ! JCO-25  ! RAD + TEMP /QDR  !

CONTROL ROD DRIVE SYSTEM LT-3-231A 8 ROSEM0thT  ! !!53DB4PG  ! QUALIFIED -  !  ! NOTE 3 LT-3-231B  ! ROSEM0thT  ! 1153DB4PG  ! QUALIFIED  !  ! NOTE 3 LT-3-231C  ! ROSEMOUNT  ! !!53DB4PG  ! QUALIFIED  !  ! NOTE 3 LT-3-231D  ! ROSEM0thT  ! !!53DB4PG  ! OUALIFIED  !  ! NOTE 3 LT-3-231E  ! ROSEM0UNT  ! !!5 454PG  ! QUALIFIED  !  ! NOTE 3-LT-3-231F  ! ROSEMOUNT  ! Il53DB4PG  ! Olk iFIED  !  ! NOTE 3 LT-3-231G  ! ROCEMOUNT  !-1153054PG  ! QUALIFIED  !  ! E TE 3 LT-3-231H  ! R05EM0thT  ! !!5 4B4PG  ! QUALIFIED  !  ! hOTE 3 PS-3-242A  ! PCI  ! A1711  ! NOT REQ / QUALIFIED ! !TO BE RENVED PENTilNG MC APFR0'iAL PS-3-2423  ! PCI  ! A1711  ! NOT REQ /0UAlIFIED ! !TO BE REMOVED FENDING NRC AFFROVAL PS-3-242C  ! PCI  ! A1711  ! E T TiQ/ QUALIFIED !~ !TO BE REMOVED PENDI M NRC APPROVAL PS-3-242D:  ! PCI  ! A1711  ! NOT REQ / QUALIFIED ! !TO BE REMOVED PENDING NRC AFfROVAL SE-3-ARI-A  ! ASCO  ! PM316E36E  ! QUALIFIED  !  !

.SE-3-ARI-B  ! ASCO  ! F S316E36E  ! QUALIFIED  !  !

.SE-3-31A-  ! ASCO  ! HVA90-405-2A ! JCO-31  ! NO TEST DATA /QiG  !

SE-3-31B  ! ASCO  ! HVA90-405-2A ! JCO-31  ! NO TEST DATA /QDR  !

SN-3-140A  ! ASCO.  ! WLBX831636 -! JCO-32  ! NO TEST DATA /RFPLK E  !.

SN-3-140B  ! ASCO  ! WPLBX831636 ! JCO-32  ! NO TEST DATA /REPLK E  !

S0-3-13-117~  ! ASCO  ! HVA90-405-2A ! JCO-31  ! NO TEST LATA /QCR  ! SCRAM SOLEN 0lL5-89 TOTAL E

~

VERM0NT YANKEE NUCLEAR P0WER STATION PRCMED 84/05/09.

ENVIRCNENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PACE 9

!  !  ! QUALIFICATION ! [EFICIENCY/ !

ID NUMEER  ! MANUFACTLRER ! M0iEL MJMBER ! STATUS  ! RESOLUTICN !CatENTS C 0 N T R 0 ll, R 0 D D R'I V E SYSTEN (CONTINLED)

S0-3-13-!!8  ! ACCO  ! HVA90-405-2A ! JCO-31  ! NO TEST DATA /QDR  ! SCRAM SOLEN 0!DS-89 TOTAi.

25 'M-Al  !-  !  ! QUALIFIED  !  ! CATE6C6V D 25-5M-B1  ! -!  ! QUALIFIED  !  ! CATECGY D 25-565-A2  !  !  ! GlRIFIED  !  ! CATEGORY 0 25-56B-B2  !  !  ! QUALIFIED '  ! CATEGORY D 3-231A(M)  !  !  ! QUALIFIED  !  ! CATEC# i D 3-231A(SI)  !  !  ! QUALIFIED  !  ! CATECG ) D 3-231A(X)  !  ! ' QUALIFIED '  ! CATECG Y D 3-231A(X1)  !  !  ! QUALIFIED  !  ! CATECGY D 3-231B(M)  !  !  ! QUALIFIED  !  ! CATECGY D 3-231B(SI)  !  !  ! QUALIFIED  ! ' CATECGY D 3-231B(I)  !  !  ! QUALIFIED  !  ! CATECGY D 3-231F.(X1)  !  !  ! QUALIFIED  !  ! CATEGORY D 3-23?.C(M)  !  !  ! QUALIFIED  !  ! CATECGY D 3-2'!C(X)  !  !  ! QUALIFIED  !  ! CATECGY D 3-031 dim)  !  !  ! QUALIFIED  !  ! CATECGY D 3-231D(X)  !  !  ! OlR IFIED  !  ! CATECGY D 3-231E(M)  !  !  ! QUALIFIED  !  ! CATEGORY D 3-231E(I)  !  !  ! QUALIFIED  !  ! CATECGi D 3-231F(M)  !  !  ! QUALIFIED  !  ! CATECGY D 3-231F(X)  !  !  ! QUALIFIED  !  ! CATECGY D 3-231G(M)  !  !  ! CARIFIED  !  ! CATEGORY D 3-2310(S1)  !  !  ! QUALIFIED  !  ! CATECGY D 3-2310(X)  !  !  ! QUALIFIED  !  ! CATECGY D 3-2310(XI)  !  ! ' QUALIFIED  !  ! CATECG Y D 3-231H(M)  !  !  ! QUALIFIED  !  ! CATECM V D 3-231H(S!)  !  !  ! QUALIFIED  !  ! CATEGORY D 3-231H(X)  !  !  ! QUALIFIED  !  ! CATEC#Y D 231H(X1)  !  !  ! QUALIFIED  !  ! CATECGY D CADM POS IND  ! CEN ELECTRIC !  ! JCO-29  ! NO DOC /QDR  !

REACTOR ~ PROTECTION SYSTEM Pl(5-7A  !  !  ! QUALIFIED  !  ! CATE6ORY D FNL5-7B  !  !  ! GlRIFIED  ! .  ! CATEGORY D PNL5-7C  !  !  ! QUALIFIED  !  ! CATEGORY D PNL5-7D  !  !  ! QUALIFIED  !  ! CATECGY D PNL5-7E  !  !.  ! QUALIFIED  !  ! CATECGY D Pft5-7F-  !  !  ! QUALIFIED  !  ! CATECGY D-

- _ u . ._ - . _ _ . _ . ,___ . _ - _ .-

]

VERM0NT YANKEE NUCLEAR POWER STATION PRODUCED : 64/05/09.

ENVIRONMENTAL QUALIFICATIM OF ELECTRICAL E0VIFMENT MASTER EQUIPMENT LIST PAGE 10

! QUALIFICATION !

~

-!  ! DEFICIENCY /  !

ID RMBER  ! MANUFACTURER ! MODEL NLN ER ! STATUS  ! RESOLUTION  ! COMMENTS REACT 0( PR0TECTION SYSTEM (CONTINlED)

FM.5-70  !  !  ! QUALIFIED  !  ! CATEGORY D PfL5-7H  !  !  ! QLR IFIED -  !  ! CATECGY D PS-5-14A  ! BARKSDALE  ! B2T-A12-SS  ! JCO-36  ! NO TEST DATA /REFLACE  !

PS-5-14B  ! BARKSMLE  ! B2T-Al2-SS  ! JC0-36  ! NO TEST MTA/ REPLACE  !

PS-5-14C  ! BARKSDALE  ! B2T-Al2-SS  ! JCO-36  ! NO TEST DATA /REPLME  !

PS-5-14D  ! BARKSDALE  ! B2T-A12-fS  ! JCO-36  ! NO TEST NTA/REFtKE  !

PS-37  ! FE W  ! P72AA-997  ! JCO-37  ! NO TEST M TA/REFtACE  !

PS-38  ! PENN  ! P72AA-997 ' JCO-37  ! NO TEST N TA/REFtACE '

PS-39  ! PE m  ! P72AA-997  ! JCO-37  ! NO TEST DATA / REPLACE !

PS-40  ! PENN  ! P72AA-997  ! JCO-37  ! NO TEST DATA / REPLACE !

PT-5-12A  ! ROSEM0lNT  ! Il52Cf4N  ! OtR IFIED  !  !

PT-5-12B  ! ROSEM0lNT  ! !!52Cf4N  ! OlR IFIED  !  !

.PT-5-12C  ! ROSEM0thT  ! 1152GP4N  ! OlRIFIED  !  !

PT-5-120  ! ROSEM0UNT  ! 11520F4N  ! QUALIFIED  !  !

SV05-1  ! NAMCO  ! SL-3  ! JCD-38  ! NO TEST M TA/REFtACE  !

SV05-2  ! NAMCO  ! SL-3  ! JCD-38  ! NO TEST M TA/ REPLACE  !

SV05-3  ! NAMCO  ! SL-3  ! JCO-38  ! NO TEST MTA/ REPLACE  !

SVOS-4  ! NANCO  ! SL-3  ! JCD-38  ! NO TEST DATA /REFtACE !

5-12A(M)  ! ROSEMOUNT  ! 5100U  ! QUALIFIED  !  !

5-12A(X)  ! K4 STAT  ! ECfB001  ! OlRIFIED  !  !

5-12B(M)  ! RCSEM0thT  ! 510DU  ! OlR IFIED  !  !

5-12B(X)  ! AC4 STAT  ! EGPB001  ! GlRIFIED  !  !

5-12C(M)  ! ROSEMOUNT  ! 510D0  ! JCO-33  ! HELB TEMP /REPL EE  !

5-12C(X)  ! AC4 STAT  ! EGPB001  ! JCO-34  ! HELB TEMP /QDR  !

5-12D(M)  ! ROSEM0LNT  ! 5100U  ! JCO-33  ! HELB TEMP / REPLACE  !

5-12D(X)  ! ACASTAT  ! E0P9001  ! JCO-34  ! HELB TElf/QDR  !

75-5A-(A1)  ! ELMA  ! 164C5261  ! GlRIFIED  !  !

25-5A-(BI)  ! ELMA  ! 164C5261  ! OUALIFIED  !  !

25-6A-(A2)  ! ELMA  ! 16405261  ! JCO-35  ! HELE TEMF/ RELOCATE  !

25-6A-(B2)  ! ELMA  ! 16405261  ! JCO-35  ! HELB TEMP / RELOCATE  !

' NEUTRON MONITORINO SYSTEM 8

! OlR IFIED '!  ! CATEGORY D

!  !~  ! OlRIFIED  ! .  ! CATEGORY D LPRMS ~!GENELECTRIC ! 129936206026 ! JCO-39  ! NO DOC /0DR  !

, TIP DR  !  !  ! OlR IFIED  !  ! CATEGORY D o _.

..;._ _ _ _ _ .._ ____ _ ...._..-_ __- . . .- _ .~ . _.

VERM0NT YANKEE NUCLEAR P0WER STATION

' PRODUCED : 64/05/09.

ENVIRONMEhTAL QUALIFICATION OF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PACE 11

!  !  ! QUALIFICATICN ! DEFICIENCY /  !

ID NUMBER  ! MANUFACTURER ! MODEL NLMBER ! STATUS ! RESOLUTION  ! COMMENTS l t t l

- -l

'RESIDUbL HEAT REMOVAL SYSTEM CP-82-2  ! PERCLRY  !  ! QUALIFIED  !  !

DPT-10-91A !GEMC  ! 552  ! JCO-40  ! NO TEST DATA / REPLACE  !

IPT-10-91B  ! CEMAC ~! 552 ' JCO-40  ! NO TEST DATA / REPLACE  !

FS-10-148A  ! BARTCW  ! 289A-2553  ! JCO-41  ! NO TEST DATA /QDR  !

FS-10-!46B  ! BARTON  ! 289A-2554  ! JCO-41  ! NO TEST DATA /QDR  !

MOV-10-13A  ! LIMITORQUE  ! SMB-2 8 QUALIFIED  !  !

MOV-10-13B  ! LIMITC60tE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-13C  ! LIMITCRQlE  ! SMB-2  ! GlRIFIED  !  !

N0V-10-13D  ! LIMIT MQlE  ! SMB-2  ! OlR IFIED  !  !

MOV-10-15A  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-15B  ! LIMITORQlE  ! SMB-2  ! OlRIFIED  !  !

MOV-10-15C  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  ! '

MOV-10-15D  ! LIMITORQlE  ! SMB-2  ! QUALIFIED  !  !

MOV-10-16A  ! LIMITORR E  ! SMB  ! QUALIFIED  !  !

MOV-10-16B  ! LIMITC6QlE  ! SMB  ! QUALIFIED  !  !

MOV-10-17  !  !  ! QLR IFIED  !  ! CATEC{6Y D MOV-10-18  ! LIMITC60VE  ! SMB-2  ! JCO-42  ! RAD /REPtACE BRAKE  !

MOV-10-25A  ! LIMITORQUE  ! SMB-3  ! QUALIFIED  !  !

MOV-10-25B ' LIMITORQUE  ! SMB-3  ! QUALIFIED  !  !

MOV-10-26A  ! LIMITORQUE  ! SMB-00  ! QUALIFIED  !  !

MOV-10-26B  ! LIMITORQUE  ! SMB-00  ! QUALIFIED  !  !

MOV-10-27A  ! LIMITORQUE  ! SMS-4T !GlLAIFIED  !  !

MOV-10-27B  ! LIMITC60lE  ! SMB-4T  ! GlRIFIED  !  !

MOV-10-31A  ! LIMITOROLE  ! SMB-0  ! QUALIFIED  !  !

MOV-10-319 8 LIMITC60lE  ! SMB-0  ! QUALIFIED  !  !

MOV-10-33  !  !  ! GlRIFIED  !  ! CATEGORY D MOV-10-34A !LIMITOROUE  ! SMB  ! QUALIFIED  !  !

POV-10-34B  ! LIMITORQlE  ! SMB  ! QUALIFIED  !  !

MON-10-30A  ! LIMITORQlE  ! SMB-00  ! Gl R IFIED  !  !

MOV-10-389  ! LIMITC601.E  ! SMB-00  ! OlRIFIED  !  !

MOV-10-39A  ! LIMITC60lE  ! SMB-0  ! QUALIFIED  !  !

MOV-10-39B  ! LIMITORQlE -  ! SMB-0  ! QUALIFIED  !  !

MOV-10-57  !-  !  ! 9)ALIFIED  !  ! CATEGORY D MOV-10-65A  ! LIMITOROLE  ! SMB-4  ! QUALIFIED  !  !

MOV-10-658  ! LIMITC60VE  ! SMB-4  ! QUALIFIED  !  !

MOV-10-66  !  !  ! QUALIFIED  !  ! CATEGORY D MOV-10-894  ! LIMITORQUE  ! SPG-2  ! QUALIFIED  !  !

MOV-10-998  ! LIMITORE E !SMB-2  ! OlR IFIED  !  !

L - 1

l

  • - VERH0NT YANKEE NUCLEAR P O li E R STATION Ff(ODUCED 64/05/09 ENVIRONMENTAL QUALIFICATICH CF ELECTRICAL EQUIPMENT MASTER EQUIPHENT LIST PAGE 12

!  !  ! QUALIFICATION ! DEFICIENCY /  !

ID NLMBER  ! MNUFACTURER ! tt0CEL NUMIfR ! STATit5  ! RESOLUTION !COMPENTS RESIDUI.L HEAT REM 0 VAL SYSTEM (CCNTINUED)

P-8-1A  ! WESTINGHCUSE ! CSP-USS-PP  ! QUALIFIED  !  !

P-8-1B  ! WESTINGHOUSE ! CSP-USS-PP  ! QUALIFIED  !  !

P-0-lC  ! WESTINCe0VSE '! CSF-USS-PP  ! QUALIFIED  !  !

P-8-ID  ! WESTI G OUSE ! CSP-USS-FP  ! QUA'.IFIED  !  !

P-10-!A  ! GEN ELECTRIC ! BEJ-205002  ! QUALIFIED  !  !

P-10-1B  ! GEN ELECTRIC ! EEJ-212003  ! QUALIFIED  !  !

P-10-lC  ! CEN ELECTRIC ! BEJ-219001  ! QUALIFIED  !  !

P-10-lD  ! GEN ELECTRIC !IEJ-219003  ! QUALIFIED '  !

P0T-10-89A  ! LIMITORCAE  !  ! JCO-44 !NO TEST DATA /QIR OR DC !

POT-10-89B  ! LIMITOROUE  !  ! JCO-44 !NO TEST DATA /QDR C6 [C  !

PS-10-105A  !  !  ! QUALIFIED  !  ! CATEGORY D PS-10-1055  !  !  ! QUALIFIED  !  ! CATECGY D PS-10-10"C  !  ! ' QUALIFIED  !  ! CATEGORY D PS-10-105D  !  !  ! QUALIFIED  !  ! CATEGORY D PS-10-105E  !  !  ! QUALIFIED  !  ! CATECG Y D PS-10-105F  !  !  ! QUALIFIED  !  ! CATECM Y D PS-10-105G  !  !  ! QlELIFIED  !  ! CATEGORY D PS-10-105H  !  !  ! QtALIFIED  !  ! CATECGY D PT-10-101A  ! ROSEM0LNT  ! ll520P4N  ! QUALIFIED  !  !

PT-10-1019  ! ROSEMOLNT  ! 1152GF4N  ! QUALIFIED  !  !

PT-10-1010  ! ROSEM0LNT  ! Il52GF4N  ! QUALIFIED  !  !-

PT-10-1010  ! ROSEM0thT  ! liS20P4N  ! QUALIFIED  !  !

10-101A(M)  ! ROSEMOUhT  ! 510DU  ! JCO-22  ! RAD /IESIGN CJiANCE  !

10-101A(SI)  ! ROSEM3thT  ! 51000  ! JCO-22  ! RAD /IESIGN DiANGE  !

10-10!A(X)  ! AGASTAT  ! E0PB001  ! JCO-23  ! PAD /QM  !

10-101A(XII -! AGASTAT  ! EGFB001  ! JCO-23  ! RAD /QDR  !

10-101B(M)  ! ROSEMOLNT  ! 510[0  ! JCO-24  ! RAD

  • TEMP /REPlKE+DSCW CHG!

10-101B(SI)  ! ROSEM0thT  ! 510S0  ! JCO-24  ! RAD + TEMP / REPLACE +DSCW dig!

10-101B(I)  ! ACASTAT  ! E0F5001  ! JCO-25  ! RAD + TEMP /QM  !

10-101B(X1)  ! ArASTAT  ! EGPB001  ! JCO-25  ! RAD + TEPF/QDR  !

10-101C(M)  ! ROSEMINT  ! 510D0  ! JCO-22  ! RAD /IESICW OiANGE  !

10-101C(SI)  ! ROSEMCONT  ! 510IU  ! JCO-22  ! RAD /EESICW CHANGE  !

10-101C(X)  ! AGASTAT  ! E0PB001  ! JCO-23  ! RAD /QM  !

10-101C(II)  ! ACASTAT-  ! EGPB001  ! JCO-23  ! RAD /QDR  !

10-101D(M)  ! ROSEMOUNT  ! 51000  ! JCO-24  ! RAD + TEMP / REPLACE +DSGN CHG!10-101 DIS 1)  ! ROSEM0lNT  ! 510C0  ! JCO-24  ! RAD + TEMP /REFtACE+DSCW CNG!

10-101D(X)  ! AGASTAT  ! EGP9001  ! JCO-25  ! RAD + TEMP /QM  !

10-10!D(XI) !AGASTAT  ! E0PB001  ! JCO-25  ! RAD + TEMP /QM  !

m _

. . . - - _ _ . . _ . . _ . . . . . _ . . _ _ _ . . ~_.---._ ._

VERM0NT YANKEE NUCLEAR P0WER STATION FR000CED : 84/05/09.

ENVIRCNMENTAL QUALIFICATICN CF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PACE 13

!  !  ! QUALIFICATICW ! DEFICIENCY /  !

ID NLMBER  ! H UFACTLFIR ! MOIEL NLHBER ! STATUS  ! RESOLUTICt. iC0fttENTS f

REACT 0{ WATER CLEANUP SYSTEM FT-12-1A  !  !  ! QUALIFIED  !  ! CATEGORY D FT-12-1B  !  !  ! QUAllFIED  !  ! CATEGORY D MOV-12-15  ! LIMITORQUE  ! SMB-000  ! QUALIFIED  !  !

MOV-12-18  ! LIMITORQUE  ! SMB-000  ! OVALIFIED  !  !

MOV-12-68  !  !  ! QUALIFIED  !  ! CATEGORY D 12-1A(M)  ! ROSEM0UNT  ! 51000  ! JCD-22  ! RAD /EESICW CWCf  !

12-1A(X)  !  !  ! QUALIFIED  !  ! CATEGORY D 12-!B(M)  ! ROSEMOUNT  ! 510DU  ! JCO-24  ! RAD + TEMP / REPLACE +DSCW CHG!

12-1B(X)  !  !  ! QUALIFIED  !  ! CATEGORY D REACTOR CORE ISOLATION COOLING SYSTEM CP-82-3  ! PERCLRY  !  ! QUALIFIED  !  !

MOV-13-15  ! LIMITORQlE  ! SMB-000  ! JCO-46  ! RAD / REPLACE MOTOR  !

MOV-13-16  ! LIMITC60lE  ! fMB-000  ! JCO-47  ! NO DOC /EFtACE LIMIT SWS!

MTS-13-2  ! WESTINGHOUSE ! MTSS  ! QUALIFIED  !  !

TS-13-79A  ! FENWAL  ! 17002-40  ! JCO-48  ! NO TEST DATA / REPLACE  !

TS-13-799  ! FENWAL  ! 17002-40  ! JCO-49  ! NO TEST DATA / REPLACE  !

TS-13-79C  ! FENWAL  ! 17002-40  ! JCO-49  ! NO TEST M TA/ REPLACE  !

TS-13-79D  ! FENkAL  ! 17002-40  ! JCO-50  ! NO TEST N TA/ REPLACE  !

TS-13-80A  ! FENWAL  ! 17002-40  ! JCO-48  ! NO TEST DATA / REPLACE  !

TS-13-808  ! FENWAL  ! 17002-40  ! JCO-49,  ! NO TEST DATA / REPLACE  !

TS-13-80C  ! FENWAL  ! 17002-40  ! JCO-49  ! NO TEST MTA/ REPLACE  !

TS-13-00D  ! FENWAL  ! 17002-40  ! JCO-50  ! NO TEST DATA / REPLACE  !

TS-13-81A  ! FENWAL  ! 17002-40  ! JCO-48  ! NO TEST DATA / REPLACE  !

TS-13-81B  ! FENWAL  ! 17002-40  ! JCO-49  ! NO TEST M TA/ REPLACE  !

TS-13-81C !FENWAL  ! 17002-40  ! JCO-49  ! NO TEST DATA / REPLACE  !

TS-13-81D  ! FENWAL  ! 17002-40  ! JCO-50  ! NO TEST DATA / REPLACE  !

TS-13-82A  ! FENWAL  ! 17002-40  ! JCO-48  ! NO TEST M TA/ REPLACE  !

TS-13-828  ! FENWAL  ! 17002-40  ! JCO-49  ! NO TEST DATA / REPLACE  !

TS-13-82C  ! FENWAL  ! 17002-40  ! JCO-49  ! NO TEST DATA / REPLACE  !

TS-13-82D  ! FEWAL  ! 17002-40  ! JCO-50  ! NO TEST M TA/ REPLACE  !

V-13-16  ! ESTINGHOUSE ! TYPE W  ! JCO-5  ! DOC /QDR.  ! LOCAL STARTER CORE SPRAY SYSTEM .

FS-14-45A  ! BARTON  ! 289A-2456  ! JCO-51  ! NO TEST DATA /QDR  !

FS-14-458  ! SARTON  ! 289A-8122  ! JCO-51  ! NO TEST M TA/QDR  !

MOV-14-54  ! LIMITOR0lE  ! SMB-000  ! QUALIFIED  !  !

N0/-14-5B  ! LIMITORQlE  ! SMB-000  ! QUALIFIED  !  !

L...

- - - . . - . - - - - . . - - - . . . - . . - . - . ~ - - . - - - .

1 VERM0NT YANKEE NUCLEAR POWER STATION PRODLCED : 04/05/09.

". ENVIRONENTAL QUALIFICATION CF ELECTRICAL EQUIFTENT MASTER EQUIPMEWT LIST PAGE 14

~

!  !  ! QUALIFICATION ! DEFICIENCY /  !

ID NUMBER  ! MANJFACTURER ! MODEL NUMEER ! STATUS  ! RESCLUTION !C0ffENTS

=-

c C0RE Sf. PAY SYSTEN (CONTINlED)

MOV-14-7A  ! LIMITORQUE  ! SMB-00  ! QUALIFIED  !  !

MOV-14-7B  ! LIMITCRQlE  ! SMB-00  ! QUALIFIED  !  !

MOV-14-!!A  ! LIMITOR0lE  ! SMB-2  ! QUALIFIED  !  !

MOV-14-11B  ! LIMITORQUE  ! SMB-2  ! GlRIFIED  !  !

MOV-14-12A  ! LIMITORQtE  ! SMB-2  ! JCO-52  ! RAD / REPLACE MOTOR + BRAKE!

MOV-14-12B  ! LIMITORQUE  ! SMB-2  ! JCO-52  ! RAD / REPLACE MOTOR + BRAKE!

MOV-14-26A  !  !  ! QUALIFIED  !  ! CATEGORY D MOV-14-26B  !  !  ! QlR IFIED  !  ! CATECMY D P-46-1A  ! GEN ELECTRIC ! FEJ604010  ! QUALIFIED  !  !

P-46-1B  ! GEN ELECTRIC ! FEJ604011  ! QUALIFIED  !  !

PS-14-44A  !  !  ! QUALIFIED  !  ! CATEGORY D PS-14-44B  !  !  ! QUALIFIED  !  ! CATEGORY D FS-14-44C  !  !  ! QUALIFIED  !  ! CATEGORY D PS-14-44D  !  !  ! QUALIFIED  !  ! CATECG Y D PRIMARY CONTAINMENT ATMOSPHERIC CONTROL SYSTEM DPS-16-19-32A 8 BARTON  ! 288A-6648  ! JC0-53  ! NO TEST DATA /QDR  !

DPS-16-19-32B ! BARTON  ! 288A-6649  ! JCO-53  ! NO TEST DATA /QIR  !

LT-16-19-10A  ! ROSEM0LNT  ! !!53B  ! QUALIFIED  !  !

LT-16-19-10B  ! ROSEMOUNT  ! 1153B -! QUALIFIED  !  !

PT-16-19-29A  ! ROSEM0thT  ! !!53AB7  ! QUALIFIED  !  !

PT-16-19-29B  ! ROSEMCONT  ! Il53AB7  ! QUALIFIED  !  !

RD 16-19-1A  ! VICT0REEN  ! 877  ! QUALIFIED  !  !

RD-16-19-1B  ! VICT0REEN  ! 877  ! QUALIFIED  !  !

SB-16-19-6  !  !  ! QUALIFIED  !  ! CATECGY D SB-16-19-6A  !  !  ! QUALIFIED  !  ! CATEGORY D SP 16-19-6B  !  !  ! QtRIFIED  !  ! CATEGCRY D SB-16-19-7  !  !  ! QUALIFIED  !  ! CATECM Y D SP-16-19-7A  !  !  ! QUALIFIED  ! . ! CATECGY D SB-16-19-7B  !  !  ! QUALIFIED  !  ! CATEGORY D SB 16-19-8  !  !  ! QUALIFIED  !  ! CATEGORY D 58-16-19-9  !  !  ! QlRIFIED  !  ! CATECG Y D 58-16-19-10  !  !  ! OlR IFIED'  !  ! CATEGORY D 55-16-19-11A  ! AcCO  ! NP831654E  ! QUALIFIED  ! - '

LS-SB-16-19-!!A ! MICROSWITCH  ! OPD-AR-6809  ! JCO-54  ! RAD /QDR  !

SB 16-19-!!B  ! ASCO !fF831654E  ! OlRIFIED  !  !

LS-SB-16-19-llB ! MICR0 SWITCH  ! OPD-AR-6909 ! JCO-54  ! RAD /QDR  !

58-16-19-23  !  !  ! QlRIFIED  !  ! CATEGORY D i

j I

L

. - - - . . . . - - . . . - - . . . . . ~. ...- .----. - ---. - .- ~~~~--~

l VERM0NT YANKEE NUCLEAR P0WER STATION Fii0f0CED : 84/05/09.

ENVIR0PtENTAL QUALIFICATICW OF ELECTRICAL EQUIPNENT MASTER EQUIPMENT LIST PAGE 15

-!  !  ! QUALIFICATION ! IEFICIENCY/  !

.ID NLMBER  ! MANUFACTURER ! MOTEL NLMBER ! STATLG  ! RESOLUTION !COMrENTS PRIMARf, CONTAINMENT ATMOSPHERIC CONTROL SYSTEM (CONTINLEId TE-1-149-1  ! CONAX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-2  ! CONAX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-3  ! CONAX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-4  ! CONAX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-5  ! CONAX  ! 7952-10000-04 ! QlRIFIED  !  !

TE-1-149-6  ! CONAX  ! 7952-10000-04 ! QUALIFIED  !  !

TE-1-149-7  ! COPMX  ! 7952-10000-04 ! QUALIFIED  !  !

TE- 1-149-8  ! CONAX  ! 7952-10000-04 ! QlRIFIED  !  !

TE-1-149-9  ! CONAX  ! 7952-10000-03 ! GlRIFIE3  !  !

TE-1-149-10  ! CONAX  ! 7952-10000-03 ! QUALIFIED  !  !

TE-1-149-11  ! CONAX  ! 7952-10000-03 ! QlRIFIED  !  !

TE-1-149-12  ! CONAX  ! 7952-10v00-03 ! QUALIFIED  !  !

TE-16-19-30  ! CONAX  ! 7952-10000-01 ! OlRIFIED  !  !

TE-16-19-33A  ! CONAX  ! 7952-10000-02 ! OlRIFIED  !  !

TE-16-19-33C  ! CONAX  ! 7952-10000-02 ! OlRIFIED  !  !

TE-16-19-34  ! CONAX  ! 7952-10000-01 ! QUALIFIED  !  !

V16-20-20  !  !  ! QUALIFIED  !  ! CATEGORY D V16-20-22A  !  !  ! QUALIJIED  !  ! CATECGY D V16-20-22B  !  !  ! QUALIFIED  !  ! CATECGY D '

RADIATION MONITORINO SYSTEM fc-17-430A  !  !  ! QUALIFIED  !  ! CATEOC6Y D RM-17-430B  !  !  ! QUALIFIED  !  ! CATEOC6Y D RM-17-431A  !  !  ! QUALIFIED  !  ! CATECGY D RM-17-431B  !  !  ! QUALIFIED  !  ! CATER //<Y D FUEL POOL COOLINO SYSTEM LOCAL IND LIGHTS!  !  ! JCO-58  ! NO TEST DATA /IESIC6 ChNG! h0TE 5 LOCAL CONT SW !  !  ! JCO-57  ! NO TEST DATA / REPLACE  !

LSH-19-60 ~! JOBELL -! MODEL B  ! JCO-55  ! NU TEST DATA / REPLACE  ! NOTE 12 LSL-19-60  ! J0 BELL  ! MDIEL K  ! JCO-56  ! NO TEST DATA / REPLACE  ! NOTE 12 P-9-!A  ! WESTINGfOUSE ! 40HP-286T6  ! QUALIFIED  !  !

P-9-1B  ! WESTINGHOUSE = ! 40HP-286T6  ! QlR IFIED  ! .  !

PS-19-68A  ! ASHCRWT  ! 6480  ! JCO-59  ! NO TEST DATA / REPLACE  !

PS-19-688  ! ASHCROFT  ! 6480  ! JCO-59  ! NO TES' DATA / REPLACE  !

RADWASTE SYSTEM j A0V-20-82  !-  !  ! QUALIFIED  !  ! CATEGORY D

q.. -. i _ _.i __ - . _ _ _ - . _ _ . ~ . _ _ _ - - - - - - - - - .

i

  • .VERM0NT YANKEE NUCLEAR P0WER STATION PRODUCED : 64/05/09.

ENVIRCNENTAL QUALIFICATION OF ELECTRICAL EQUIF1ENT

}

MASTER EQUIPMENT LIST PACE 16

'!  !  ! QUALIFICATION ! DEFIClNCY/  !

ID NUMBER  ! MANUFACTtRER ! M0CEL IO!BER ! STATUS  ! RESOLUTION !CC$ TENTS g ,-

RADWAS7,E SYSTEM (CONTINlED)

A0V-20-83  !  !  ! QUALIFIED  !  ! CATEGORY D

DV-20-94  !  !  ! QUALIFIED  !  ! CATEGORY D
AC/.'-20-95  !  !  ! QUALIFIED  !  ! CATEGC6Y D HIGH PRESSURE COOLANT INJECTION SYSTEM MOV-23-15  ! LIMITORQUE  ! SMB-1  ! QUALIFIED  !  !

MOV-23-16  ! LIMITORQLE  ! SMB-1  ! QUALIFIED  !  !

TS-23-101A  ! FENWAL  ! 17002-40  ! JCO-61  ! NO TEST DATA / REPLACE  !

TS-23-101B  ! FEWAL  ! 17002-40  ! JCO-62  ! NO TEST DATA / REPLACE  !

TS-23-101C  ! FENWAL  ! 17002-40  ! JCO-62  ! NO TEST MTA/EPLACE  !

TS-23-1010  ! FENWAL  ! 17002-40  ! JCO-63 '! NO TEST DATA / REPLACE. !

TS-23-102A  ! FENW4.  ! 17002-40  ! JCO-61  ! NO TEST DATA /REFLACE - !

TS-23-102B  ! FENWAL  ! 17002-40  ! JCO-62  ! NO TEST DATA / REPLACE  !

TS-23-102C  ! FENWAL  ! 17002-40  ! JCO-62  ! NO TEST DATA / REPLACE  !

TS-23-102D  ! FENWAL  ! 17002-40  ! JCO-63 -! NO TEST DATA / REPLACE  !

TS-23-103A ~! FENWAL  ! 17002-40  ! JCO-61  ! NO TEST MTA/ REPLACE  !

TS-23-103B  ! FENIA  ! 17002-40  ! JCO-62  ! NO TEST DATA / REPLACE  !

TS-23-103C  ! FEWAL  ! 17002-40 !JCO-62  ! NO TEST DATA /REFtACE  !

.TS-23-103D  ! FENWAL  ! 17002-40 -! JCO-63  ! NO TEST DATA /REFLACE  !

TS-23-104A  ! FENkAL  ! 17002-40  ! JCO-61  ! NO TEST MTA/ REPLACE  !

TS-23-104B  ! FENkAL .! 17002-40  ! JCO-62,  ! NO TEST MTA/REFtACE .!

, TS-23-104C  ! FENWAL  ! 17002-40  ! JCO-62  ! M TEST DATA / REPLACE  !

TS-23-104D  ! FENWAL  ! 17002-40  ! JCO-63  ! NO TEST DATA / REPLACE - !

V-23-16  ! ESTINGHOUSE ! TYPE W -! JCO-5 - ! DOC /QM  ! LOCAL STARTER SERVICE AND COOLING WATER SYSTEM

! MOV-70-19A  ! LIMITORQUE  ! SMB-1  ! QUALIFIED  !  !

MC/.'70-19B  ! LIMITORQUE  ! SMB-! ~! QUAllFIED  !  !

MOV-70-20 -! LIMITORQlE'  ! SMB-1  ! QUALIFIED  !  !

P-59-1A  ! WESTINC+100SE ! LIFELIE T  ! QUALIFIED  ! -

P-59-1B  ! WESTINGkOUSE ! LIFELINE T  ! QUALIFIED  !  !

PS-104-57-1 -!  !  ! QUALIFIED  !  ! CATECM Y D PS-104-57-2  !  !  ! QUALIFIE3  ! -  ! CATEC@ V D SE-70-4A  ! ASCO  ! W X8211C13  ! JCO-66 '! NO TEST DATA / REPLACE  !

SE-70-48  ! ASCO~  ! W X8211Cl3  ! JCO-66  ! NO TEST DATA / REPLACE  !

SE-70-4C  ! ASCO -! W X8211Cl3  ! JCO-66  ! M TEST DATA / REPLACE ' !

SE-70-4D-  ! ASCO  ! WX8211Cl3  ! JCO-M  !.N0 TEST DATA /REFtACE '!

i l

)

a

. . , - . . . - - ~ - . - - - - - - .

~*

VERM0NT YANKEE NUCLEAR P0WER STATION PROIOCED : 84/05/09.

1 ENVIROP# ENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT

[

MASTER EQUIPMENT LIST PAGE 17

~

!  !  ! QUALIFICATION 8 IEFICIENCY/  !

IDfulBER  ! MANUFACTURER ! MODEL NUMBER ! STATUS  ! RESOLUTION  ! COMMENTS 4 f

~

POST AfCIDENT SAMPLING SYSTEM 71-F-1  ! ASCO  ! HBT-8%0-D58F ! JCO-67  !-N0 TEST DATA / REPLACE  !

71-P-1  ! ASCO  ! HPT-8300-D58F ! JCO-67  ! NO TEST [4TA/ REPLACE  !

71-S-1  ! ASCO ~! HBT-6300-D58F ! JCO-67  ! NO TEST DATA / REPLACE  !

71-S-2  ! ASCO  ! HBT-8300-D58F ! JCO-67  ! NO TEST DATA / REPLACE  !

SERVICE AND INSTRUMENT AIR SYSTEM A0V-72-38A  !  !  ! QUALIFIED  !  ! CATEGORY D ADV-72-3GB  !  !  ! QUALIFIED  !  ! CATEGORY D -

CONDENSATE + DW TRANSFER SYSTEM 107-12A(M)  ! ROSEM0lNT  ! 510EU  ! JCO-22  ! RAD /IESIGN OiANCE  !

107-12B(M)  ! ROSEM0lNT  ! 510rC  ! JCD-22  ! RAD / DESIGN CHANCE  !

MISCELLANEOUS ELECTRICAL EQUIPMENT ELEC-3  ! LEWIS  ! SR/SR  ! QUALIFIED  !  ! THERMOCOUPLE CARE ELEC-4  ! ROME  ! XLP/PVC  ! QUALIFIED  !  ! PCSiER CARE' ELEC-5  ! CEN ELECTRIC ! NSO2/NS03/NSO4! QlR IFIED  !  ! PEETRATICN ELEC-6  ! ROE  ! XLP/PVC  ! QUALIFIED  !  ! FCER CARE ELEC-7  ! BUCHANAN  ! 0222 !QUALIFJES  !-  ! TEfftINAL BLOCKS Etic-8  ! RCE  ! XLP/PVC  ! QUALIFIED  !  ! POER CARE ELEC-9 !PERITE  ! HTK/FR  ! QlR IFIED  !  ! POWER CARE ELEC-10 !COLLYER  ! BUTYL /E0  ! JCO-7  ! RAD / REPLACE  ! POWER CA RE ELEC-!!  ! ROME  ! XLP/PVC/PVC ! QUALIFIED-  !  ! CONTROL CARE ELEC-12  ! ROE  ! XLP/PVC/PVC ! QlRIFIED  !  ! CONTROL CARE '

ELEC-13  ! ROME  ! XLP/PVC/PVC ! QUALIFIED  !  ! CONTROL CABLE ELEC-14 ' STATES  ! NT .! QUALIFIED  !  ! TERMINAL ROCK

+

ELEC-15  ! STATES  ! NT  ! QLR IFIED  !  ! TERMINAL R OCK ELEC-16  ! ROCKBESTOS  ! FIREWALL SR ! QUALIFIED  !  ! CONTRCL CARE EtFC-17  ! ROCKBESTOS  ! FIREWALL SR ! QUALIFIED  !  ! CCWTRCL CARE ELEC-18  ! GEN ELECTRIC !CR151  ! QUALIFIED  !  ! TERMINAL ROCK ELEC-19  ! BIW  ! XLP/EOPEE ! QUALIFIED  !  ! CCNTROL CAEJ ELEC-21  ! CINCH J0ES  !  ! QUALIFIED  ! -

! TERMINAL ROCK ELEC-22  ! CERRO  ! XLP/ECFREE ! QUALIFIED  ! ~! POWER CAR E

-ELEC-23  ! LEWIS  ! PE/PVC/SitD ! QUALIFIED  !  ! CONTROL CARE Eli C-25  ! BLEriANAN  !  ! glr IFIED  !  ! TERMINAL ROCK

! NT  ! QUALIFIED ELEC-28  ! STATES  !  ! TERMINAL R OCK

.ELEC-29  ! LEWIS  ! PE/PVC  ! QUALIFIED  !  ! THEFM)C0lPLE CABLE ELEC-30  ! LEWIS  ! PE/PVC  ! QUALIFIED -  !  ! TERHDCOUPLE CARE

_ [. , _ _ . _ _ - - - - . - - -. .- _ - - ~-

VERM0NT YANKEE NUCLEAR POWER STATION PRODUCED : 84/05/09 ENVIRONMENTAL QUALIFICATION OF ELECTRICAL EQUIPMENT MASTER EQUIPMENT LIST PACE 18

'!  !  ! QUALIFICATION ! [EFICIENCY/ !

IDlO!BER  ! MANUFACTURER ! M0 EEL MjMBER ! STATUS  ! RESOLUTION !C0ffENTS

-MISCELbANEOUS ELECTRICAL EQUIPMENT (CONTINLED)

- ELEC-31  ! ROCKBESTOS  ! FIREWALL III ! QUALIFIED  !  ! CfNTM. CARE ELEC-34  ! LEWIS  ! R0-95(H.T.)  ! JC0-39  ! NO DOC /QDR  ! CO-AXIAL CARE ELEC-35  !  :  ! JCO-39  ! NO DCO/QM  ! ELECTRICAL CONNECTCR ELEC-36  ! ENEEVC0  ! 3075M6  ! QUALIFIED  !  ! CO-AXIAL CARE ELEC-38  ! ROCATESTOS ' FIREWALL III ! QUALIFIED  !  ! SIS WIRE ELEC-39  ! OKONITE  ! EPR/HYPALON ! QUALIFIED  !  ! P0FR CARE ELEC-40  ! ROCKBESTOS  ! FIREWALL III ! QUALIFIED  !  ! INSTRUMENT CARE ELEC-42  ! ROCATESTOS  ! FIREWALL III ! QUALIFIED  !  ! CO-AllAL CARE ELFC-43  ! RAYCHEM  ! VARIOUS  ! QUALIFIED  !  ! CARE SFtICE KIT ELEC-44  ! ROCKBESTOS  ! FIREWALL III ! QUALIFIED  !  ! 00-AXIAL CARE ELEC-45  ! LEWIS  ! R0-95  ! JCO-39  ! NO DOC /QDR  ! CO-AXIAL CABLE ELEC-46  ! GEN ELECTRIC ! 175A9132P008 ! QUALIFIED  !  ! FUSE HOLDER ELEC-47  ! CEN ELECTRIC !  ! QUALIFIED.  !  ! SIS WIRE ELEC-48  ! CEN ELECTRIC ! 167A2452P003 ! QUALIFIED  !  ! FUSE ELEC-49  ! ROCKBESTOS  ! FIREWALL 111 ! QUALIFIED  !  ! THERM 0CCW tE CABLE ELIC-50  !  ! 600V, PEPS  ! JCO-29  ! NO DOC /QDR  ! SICMi. CARE ELEC-51  !  ! 600V.V1KENE ! JCO-29  ! NO DOC /QDR  ! SICEL CARE ~

9 4

o_ -

j

VERMONT YANKEE ENVIRONMENTAL QUALIFICATION MASTER EQUIPMENT LIST NOTES

1) The Master Equipment List consists only of electrical components located in a harsh environment for the design basis accident (s) in which it is relied upon to function (or not fail). These are i Category A, B, and D components listed in the EQ Matrix Report.
2) These components are presently included on the Master Equipment List, but will be removed from this list once a planned design change is implemented which will make the component function in a slid environment.
3) Analog Instrument Cabinets25-56A and 25-56B consist of scram discharge volume level instrumentation that is associated with Level Transmitters LT3-231 A-H. The instrumentation in these cabinets will be protected from harsh HELB environments by planned design changes. Although this instrumentation is not now included on the Master List, Justification for Continued Operation (JCO) Number 30 has been prepared for the interim period until the design changes are implemented.
4) A design change is planned which will prevent failures associated with 4

NOV-70-118 from adversely affecting Reactor Building closed cooling water supply to the fuel pool cooling heat exchangers. Although MOV-70-118 and associated controls are not included on the Master List, Justification for Continued Operation (JCO) Number 65 has been-prepared for the interim period until the design change is implemented.

15 ) A design change is planned which will prevent failure of the fuel pool I' cooling pumps' local indicating lights on Racks 10 and 11 from adversely affecting FP cooling pump operation. These lights will be

. removed from the Master List once the design change is implemented.

6) NOV-10-32 is not included on the Master List based upon a pending. i 1

exemption to delete Type C leak rate test requirements. However, 1

. _ _ , - _ . - -. . . - - . . . - - - ~ , - - - - - - - - - - ~ - - - - - , - - -

Justification for Continued Operation (JCO) Number 43 has been prepared for the interim period until the exemption is approved.

7) -MCC-6A and 7A are non-Class 1E and are not included on the Master List. They presently supply power to the fuel pool cooling pumps. A design change 8.s planned that will change the power source for these pumps to Class IE MCCs that are within the scope of the EQ program.

Justification for Continued Operation (JCO) Number 4 has been prepared for the interim period until the design change is implemented.

8) The inverters and Battery System (UPS-1A and 1B) that supply uninterruptible power to LPCI valves are not included on the Master List. A design change is planned that will allow manual transfer of Power supply to LPCI valves if the UPS fails. Justification for continued Operation (JCO) Number 6 has been prepared for the interim period until the design change is implemented.
9) A design change is planr.ed to prevent failure of non-Class lE drywell cooling components from adversely affecting post-accident monitoring drywell air temperature indication. Although these drywell cooling components are not~ included on the Master List, Justification for

~ Continued Operation (JCO) Number 8 has been prepared for the interim period until the design change is implemented.

10) A design change is planned to prevent failure of the auxiliary. relay for the HPCI gland seal condenser blower from adversely affecting the Standby Gas Treatment System. Although this relay is'not included on the Master List, Justification for Continued Operation (JCO) Number 60
has been prepared for the interim period until the design change is implemented.
11) A design change is planned to provide redundant RBCCW surge tank level alarms to aid in long-term post-LOCA makeup. Although the present alarm instrumentation (LSL-104-3) is not included on the Master List, Justification for. Continued Operation (JCO) Number 64 has been prepared for the interim period until the design change is implemented. Also.,

the Master List will be updated to reflect 'the addition of new level .

instruments after. installation.

l i

. ~

12) A design change is planned to replace existing fuel pool level alarm instruments with redundant Class IE instruments.

13). A design change is planned to enhance our RWCU High Space Temperature Detection and Isolation System. Justification for Continued Operation l (JCO) Number 45 has been prepared for the interim period until the design change is implemented. Also, the Master List will be updated to reflect the addition of new temperature detection components after installation.

14) Components designated as " Category D" in the comment column are those components that function prior to the onset of a harsh environment and whose subsequent failure will not adversely affect any safety functions. The technical basis for components in this category is Provided in the " Vermont Yankee Electrical Component Matrix Report".

l

9 44%~ j -- ,

e s.

- ENCLOSURE 1 W W P

O e

f

.g 9

c

/ [

> r s'

-se#,

V k

~'

./

. s e

e s..

4 STATUS OF ITcMS ADDRESSED IN FRANKLIN RESEARCH I

CENTER TER-C5257-496 REVISION 1 J f~

2

/

  • f m f I ,

a

// ,

E

  • w 7

9 O

a k

e n

  1. (^

h 4

  1. ,[

b ,,

4

+

Enclosure 1 Page 1 of 24 STATUS OF ITEMS ADDRESSED IN FRANKT.IN RESEARCH CENTER TER-C5257-496 ITEN NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 1 Limit Switch II.A Similarity Qualification MANCO Aging documentation, not EA740 Qualified Life previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

2 Limit Switch II.A Similarity Qualification NAMCO Aging documentation, not EA740 Qualified Life previously available to

, FRC, which qualifies the J equipment, will be on file at our engineering office.

)

3 Limit Switch I.B Documentat!on Qus11fication Microswitch- documentation, not OPDAR6809 previously available to FRC, which qualifies the equipment, will be on file i at our engineering office.

Some of the equipment performs its function before its exposure to the harsh environment and subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

4 Position Switch I.B Qualification General Electric documentation, not previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

I Enclosure 1 Page 2 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-CS257-496

ITEN-NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 5 Temperature Switch II.A Documentation These switches will be Fenwal Similarity replaced with qualified

'17023-6 Steam Exposure Fenwal switches Model (01-170230-090) during the 1984 Refueling Outage.

6 Pressure Switch I.B These switches will te Static-0-Ring replaced with qualified 6ME3CIAGGMKRTTX10 SOR Model (6TA-B3-NK-ClA-JJTTX6) switches during the 1984 Refueling Outage.

7 Level Indicating I'I.B I This equipment will be Transmitter replaced with qualified YARWAY Rosemount (1153s) during the-4418CE 1984 Refueling Outage.

8 Electric Motor II . A Similarity Qualification General Electric Aging documentation, not FEJ604011 Qualified Life previously available to Radiation FRC, which qualifies the Functional Test equipment, will be on file

, at our engineering office.

M 9 Electric Motor II.A Similarity Qualification General Electric Aging documentation, not BEJ212003 ~ Qualified Life previously available to Radiation FRC,~which qualifies the  ;

Functional Test equipment, will be on file ~

-l at our engineering office. l l

10 Electric Motor II.A Similarity Qualification Westinghouse Aging documentation, not l S069F46553 Qualified Life previously available to l FRC, which qualifies the.

equipment, will be on flie-at our engineering office.

+< ,.. wee

l l

Enclosure 1 Page 3 of 24 STATUS OF ITEMS ADDRESSED l IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEN NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 11 Electric Motor II.A Similarity Qualification Reliance Electric documentation, not previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

12 Electric Motor I.B Documentation Qualified replacement Allis Chalmers equipment has already been RG Frame 215T installed per FRC Item #11.

13 Electric Motor II.A Documentation Qualification Reliance Electric documentation, not previously available to FRC, which qualifies the equipment, will be on file-at our engineering office.

14 Electric Motor II.A Similarity The equipment has been Reliance Electric deleted from the Master Equipment List because it is part of the CAD System, which is not in the scope of 10CFR50.49, 15 Electric Motor I.B Documentation Qualified replacement Allis Chalmers equipment has already been 51308578 installed per FRC Item #13.

l 16 Electric Motor I.B Documentation The equipment has been deleted from the Master Equipment List because it was going to be replaced by l FRC Item 14.

17 Terminal Block I.A None None required.

General Electric CR151

l 1

l Enclosure 1 1 Page 4 of _14_ '

STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM NO. DESCRIPTION CATEGOR% DEFICIENCIES PROPOSED RESOLUTION 18 Terminal Block II.A Documentation Qualification Buchanan Similarity documentation, not 0222 previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

19 Terminal Block I.A. None States Type NT Teaminal States Blocks are used for several NT thermocouple circuits within the primary containment.

The effects of potential leakage currents in this application have been evaluated in documentation on file at our engineering office and the blocks are qualified.

20 Terminal Block I.A None None required.

States NT 21 Terminal Block II.A Documentation Qualification Buchanan Similarity documentation, not previously available to FRC, which' qualifies the equipment, will be on file at our engineering office.

22 Terminal Block I.A None None required.

States NT 23 Electrical I.A None None required. l Penetration 1 General Electric-NS02 l

l

-J

l Enclosure 1 Page 5 of 24 ,

l STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-CS257-496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 24 Electrical I.A Hone None required.

Penetration i General Electric NS03 25 Electrical I.A None -

None required.

Penetration General Electric

NSO4 26 Pressure- II.C Aging The equipment has been Transmitter Qualified Life deleted from the Master Rosemount Equipment List because it 1152 is part of-the CAD System, which is not in the scope of 10CFR50.49.

27 Level Transmitter I.B Qualified replacement Rosemount equipment (Rosemount' 1153s) have already been 1152 installed.

28 Pressure II.A Documentation The equipment has been Transmitter deleted from the Master General Electric ' Equipment List because we 552 are using other qualified equipment in FRC Item #29, and Item #28 is no longer in the scope of_10CFR50.49.

29 Pressure II.C Aging Qualified replacement Transmitter Qualified Life- equipment (Rosemount 1153s)

Rosemountf have already been installed.

.1152-

f. j

~

o 30' Level Transmitter II.C Aging These concerns will be  !

Rosemount -

Qualified Life . addressed in-the ongoing .l 1152T280 Maintenance and Surveillance l - Program.

l 0

1

- , ,- .e-. . ,-,e, - , --v -,- - pe I- - - ,-. <

i i Enclosure 1

{ Page 6 of 24 L

! STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 i ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 31 Level Transmitter I.B Documentation Equipment performs its' General Electric function before its GEMAC 555 exposure to the harsh environment and subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

32 Acoustic I.B Documentation This equipment will be Transmitter replaced with qualified TEC Babcock & Wilcox Models (504E and 160-2) during the 1984 Refueling Outage.

33 Acoustic I.B Documentation Qualification Accelerometer documentation, not Babcock & Wilcox previously available to FRC, which qualifies the equipment, will be on file 1 at our engineering office.

34 Radiation Detector I.B Similarity ~ Qualification Victoreen Pressure documentation, not 877 Steam Exposure previously available to Accuracy FRC, which qualifies the equipment, will be on file at our engineering office.

35 Thermocouple II.A Documentation Qualification Conax Aging documentation, not T 2319029ECSA Qualified Life previously available to Aging Simulation FRC, which qualifies the Functional Test equipment..will be on file at our engineering office.

36 Pressure II.C Aging These concerns will be

, Transmitter Qualified Life addressed in the ongoing Rosemount Maintenance and Surveillance 1152 Program.

Enclosure 1 Page 7 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 37 Hydrogen Analyzer IV Documentation Qualified replacement Comsip Delphi equipment (Teledyne 225 l KI CMA-2s) have already been installed.

38 Power Supply II.A Documentation Equipment performs its Exide function before its 250 kVA exposure to the harsh ,

environment and subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

39 Thermocouple II.A Documentation Qualification Conax Aging documentation, not 1

2310-9029-ESCA Qualified Life previously available to 3- Aging Simulation FRC, which qualifies the Functional Test equipment, will be on file at our engineering office.

40 Electric Motor II.A Similarity Qualification General Electric Aging documentation, not BEJ205002 Qualified Life previously available to Radiation FRC, which qualifies the' Functional Test equipment, will be on file at our engineering office.

41 Temperature II.A Documentation Qualification Element Aging documentation, not Conax Qualified Life previously available to 23109029-ECSA Aging Simulation FRC, Which qualifies the Functional Test equipment, will be on file at our engineering office.

i 42 Electric Motor II.A Similarity Qualification General Electric Aging documentation, not i BEJ219001 Quallfled Life previously available to Radiation FRC, Which qualifies the Functional Test equipment, will be on file at our engineering office.

Enclosure 1 Page 8 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257--496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 43 Motor-Generator II.A Documentation The equipment has been General Electric deleted from the Master Equipment List. It is not required to be qualified since an alternate qualified power source is available.

44 Motor Control II.A Documentation Qualification Center documentation, not Westinghouse previously available to Type W FRC, which qualifies the equipment, will be on file at our engineering office.

45 Motor Control II.A Aging Qualification Center Qualified Life documentation, not 4

ITE Aging Simulation previously available to 5600 Radiation FRC, which qualifies the equipment, will be on file at our engineering office.

46 Power Panel II.A Documentation This power panel is located Westinghouse in one of the MCCs which are evaluated by FRC Item #47.

47 Motor Control II.A Documentation- Qualification l Center documentation, not j Westinghouse previously available to Type W FRC, which qualifies the equipment, will be on file  !

at our engineering office.  !

l

i, Enclosure 1 Page 9 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEN

_NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 48 Thermocouple Cable I.B Documentation A portion of this equipment Lewis has been replaced with SR/SR qualified Rockbestos thermocouple cable.

Qualification documentation, not previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

49 Thermocouple Cable I.B Documentation Qualification Lewis documentation, not PE/PVC previously available to FRC, which quellfles the equipment, will be on file at our engineering office.

50 Thermocouple cable I.A Mone None required.

Lewis PE/PVC 51 Power Cable II.C Aging These concerns will be 2 Kerite Qualified Life addressed in the ongoing HTK/FR Maintenance and Surveillance Program.

52 Power Cable I.A None The environment that this Collyer equipment is exposed to is Buty1/ Neoprene harsher than evaluated by FRC. This equipment will be replaced with qualified Rockbestos 5kV cable during the 1984 Refueling Outage.

53 Power Cable II.C Aging These concerns will be Cerro Qualified Life addressed in the ongoing XLP/ Neoprene Maintenance and Surveillance l Firewall III Program. 1 1

Enclosure 1

- Page 10 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM

. 50. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 54 Power Cable II.A Similarity The equipment has been cerro deleted from the Master EPR/ Neoprene Equipment List because it supports the CAD System, which is not in the scope of 10CFR50.49. Also, a portion of this cable is associated l with components that function prior to a harsh environment.

4 55 Power Cable II.A Documentation Qualification Rome documentation, not

XLP/PVC previously available to FRC, which qualifies the j equipment, will be on flie

! at our engineering office.

56 Power Cable II.A Documentation Qualification Rome documentation, not ,

4 XLP/PVC- previously available to '

FRC, which qualifies the equipment, will be on file at our engineering office.

57 Power Cable II.A Documentation Qualification Rome documentation, not XLP/PVC previously available to FRC, which qualifies the equipment, will be on flie at our engineering office.

58 Control cable II.A Similarity Qualification Rockbestos documentation, not Firewall SR previously evallable to FRC, which qualifies the equipment, will be on file

,. at our engineering office.

c _  ;

Fnclosure 1 Page 11 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEN NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 59 Control Cable II.A Similarity Qualificaticn Rockbestos documentation, not Firewall SR previously available to FRC, which qualifies the equipment, will be on flie at our engineering office.

60 Control Cable II.A Similarity The equipment has been Cerro deleted from the Master XLPE/ Neoprene Equipment List because it is part of the CAD System, which is not in the scope of 10CFR50.49.

61 Control Cable II.A Documentation Qualification Rome documentation, not l XLP/PVC/PVC previously available to j FRC, which qualifies the 4

equipment, will be on flie at our engineering office.

l 62 Control Cable II.A Documentation Qualification Rome documentation, not XLP/PVC/PVC previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

63 Contevi Cable II.A Documentation Qualification Rome documentation, not XLP/PVC/PVC previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

64 Control Cable I.A Mone None required.

Lewis PE/PVC/SHLD i

l Enclosure 1 l Page 12 of 24 STATUS OF ITEMS ADDRESSED i IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 65 Control Cable II.A Documentation Qualification BIW documentation, not XLP/ Neoprene previously available to

! FRC, which qualifies the l equipment, will be on file at our engineering office.

l e 66 MOV I.B Documentation These deficiencies will be Limitorque Aging corrected by replacement of SNB-000 Qualified Life certain subcomponents with Radiation qualified subcomponents during the 1984 Refueling Outage. In addition, our Maintenance and Surveillance Program will address ongoing Aging and Qualified Life.

67 Electric Motor II.A Similarity Qualification General Electric Aging documentation, not -

BEJ219003 Qualified Life previously available to Radiation FRC, which qualifies the Functional Test equipment, will be on file at our engineering office.

68 MOV II.A Aging These deficiencies will be i Limitorque Qualified Life corrected by replacement of ,

SMB-1 Radiation certain subcomponents with '

SMB-00 qualified subcomponents during the 1984 Refueling ,

Outage. In addition, our i Maintenance and Surveillance l Program will address ongoing Aging and Qualified Life.  !

One component has been '

deleted from the Master Equipment List. NOV 10-32 is not required to be qualified since a design change was installed that blanka off the downstream piping and eliminates the safety function of this valve.

Enclosure 1 Page 13 of 24 I

STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 69 Electric Motor II.A Similarity Qualification General Electric Aging documentation, not

, FEJ604010 Qualified Life previously available to Radiation FRC, which qualifies the Functional Test equipment, will be on file at our engineering office.

70 NOV II.C Aging These concerns will be Limitorque Qualified Life addressed in the ongoing SMB-4T Maintenance and Surveillance Program.

71 MOV I.B Documentation These deficiencies will be Limitorque Aging corrected by replacement of SNB-000 Qualified Life certain subcomponents with Radiation qualified subcomponents i during the 1984 Refueling Outage. In addition, our

Maintenance and Survelliance f

Program will address ongoing Aging and Qualified Life.

72 MOV II.C Aging These concerns will be Limitorque Qualified Life addressed in the ongoing SKB-4 Maintenance and Surveillance I

Program.

73 MOV I.B. Documentation The equipment performs its

Limitorque Aging function before its exposure SMB-000 Qualified Life to the harsh environment Radiation and subsequent failure of the equipment does not degrade other safety functions or mislead the 4

operator.

f

, - - - , . , w ,, -

e -,s > - - , - - ~ - - - - - - - mi---nn..ww,, - - - ----e - - Jy p r-., ,,e , , ~

i Enclosure 1 Page 14 of 24 l

STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-CS257-496 ITEN

50. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 74 NOV II.A Documentation These deficiencies will be Limitorgae Similarity corrected by replacement of SMB-000 Aging certain.subcomponents with DC Motor Qualified Life qualified subcomponents Radiation during the 1984 Refueling Outage. In addition, our 1 Maintenance and Surveillance Program will address ongoing Aging and Qualified Life.

1 75 MOV II.C Aging These concerns will be Limitorque Qualified Life addressed in the ongoing SMB-000 Maintenance and Surveillance Prostan.

76 MOV I.B Documentation Part of these deficiencies Limitorque Aging have been resolved by SNB-000 Qualified Life additional qualification Radiation SNB-2 documentation, which qualifies the equipment, not previously available to FRC which will be on file at 4

our engineering office. The remaining deficiencies will be corrected by replacement

, of certain subcomponents l '

with qualified subcomponents during the 1984 Refueling Outage. In addition, our j Maintenance and Surveillance Program will address ongoing Aging and Qualified Life.

77 MOV II.A Documentation The equipment has been Limitorque similarity deleted from the Master SMB-2 Aging Equipment List because it DC Motor Qualified Life is equipment Which is Radiation required for cold shutdown which is not in the scope of 10CFR50.49.

J

I Enclosure 1 Page 15 of 24  ;

1 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM

30. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 78' MOV I.B Documentation The equipment performs its Limitorque Aging function before its exposure SMB-000 Qualified Life to the harsh environment Radiation and subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

79 SOV I.B Documentation Equipment perforww its ASCO function before its exposure 8320/8311A31F to the harsh equipment and subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

80 NOV II.C Aging These concerns will be Limitorque Qualified Life addressed in the ongoing SMB-2 Maintenance and Surveillance Program.

81 MOV II.C Aging There concerns will be Limitorque Qualified Life addressed in the ongoing SMB-1 Maintenance and Surveillance Program.

82 MOV III.A Exempt This item was originally Limitorque exempt. It is now required, SMB-1 and has been determined to be qualified.

83 MOV II.C Aging Equipment performs its LimLtorque Qualified Life function before its exposure SMB-0 to the harsh environment and  ;

SMB-1 subsequent failure of the l BMB-3 equipment does not degrade l SMB-4 other safety functiot:s or mislead the operator.  ;

1 l

t- . _ _ _ . . _ . _ , . _ . - _ _ . _ _ _ . _ _ . _ _ _ -

Enclosure 1 Page 16 of 24

[ STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 4 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 84 MOV II.C Aging These concerns will be l Limitorque Qualified Life addressed in the ongoing SMB-1 Maintenance and Surveillance SMB-000 Program.

85 Turbine Controls III.B This equipment has been Terry deleted froa the Master CCS Equipment List since this equipment is only required to function for a small break LOCA event, and its environment is nild for this event. Therefore it is not in the scope of 10CFR50.49 86 Flow Transmitters III.B The equipment has been General Electric deleted from the Master 555111BDAAPBJ Equipment List since this equipment is only required to function for a senil break LOCA event, and its 4 environment is mild for this event. Therefore it is not in the scope of 10CFR50.49.

4 87 MOV II.A Documentation Qualification i Limitorque Aging documentation, not Qualified Life previously avaliable to Radiation FRC, which qualifies the

equipment, will be on file
at our engineering office.

88 Temperature Switch II.A Documentation These switches will be 4 Fenwel Similarity replaced with qualified 17023-6 Steam Exposure Fenwel switches Model (01-170-230-090) during the 1984 Refueling Outage.

i J

L Enclosure 1 Page 17 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEN

.l 30. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 89 NOV II.A Documentation The ultimate injection valves Limitorque Simliarity have been deleted from the

, BMB-0 Aging Master Equipment List because SMB-2 Qualified Life they are no longer required, Radiation and therefore are not in the scope of 10CFR50.49.

90 Pressure Switch II.A Documentation Qualification Barton Similarity documentation, not 288 previously available to FRC, which qualifies the equipment, will be on file at our engineering office.

91 MOV II.A Aging Qualification Limitorque Qualified Life documentation, not SNB-0 Radiation previously available to ,

SMB-00 FRC, which qualifies the i SNB-2 equipment, will be on file at our engineering office.

I SMB-3 SMB-4 s

i 92 NOV II.C Aging These concerns will be i

Limitorque Qualified Life addressed in the ongoing SMB-0 Maintenance and Survalliance ,

SNB-2 Program.

BNB-4T 1

93 Level Transmitter II.C Aging These concerns will be Rosemount Qualified Life addressed in the ongoins 1152T200 Maintenance and Surveillance Program.

94 Pressure Switch II.A Documentation One of these switches has Barton Similarity already been replaced with 2s8 que1Lfied equipment l

(Rosennunt 1153). The other i

will be replaced during the l 1984 Refueling Outage,

_ _ . _ _ _ _ _ _ _ _ . . . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ . . . _ . _ _ _ _ _ _ _ _ _ _ . ._____.__.__________._.___._________.__._______.__________.________________._.____m_ _ _ _ _

7 1

Enclosure 1 Page IS of 24 I STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496  !

ITEN 50, DESCRIPTION CATEGO.R1 DEFICIENCIES PROPOSED RRSOLUTION 95 NOV II.A Documentation some of this equipment i Limitorque Aging performs its function before SNB-1 Qualified Life its exposure to the harsh SMB-2 Temperature environment and subsequent Radiation failure of the equipment does not degrade other

safety functions or mislead the operator. Some will be qualified by installing replacement subcomponents during the 1934 Refueling
Outage. The remaining have qualification documentation, not previously available to FRC, which qualifies the equipment and is on file at our engineering office. In addition, our Maintenance and Surveillance Program will address ongoing Aging and Qualified Life.

96 Pressure Switch II.A Aging The equipment has been Barksdale Qualified Life deleted from the Nester B2TA12SS Temperature Equipment List because we Steam Exposure are using other qualified Radiation equipment, and therefore Margin it is no longer in the scope of 10CFR50.49, 97 Turbine Controls III.A This equipment has been Terry deleted from the Master 081 Equipment List since this equipment is only required to function for a maail break LOCA event, and its environment is slid for this event. Theesfore it is not in the scope of 10CFR50.49.

i d

Inclosure 1 Page 19 of 24 STATUS OF ITEMS ADDRESSgD IN FRANKLIN RgSEARCH CENTER TER-C5257-496 ITEN B0. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 98 Pressure Switch III.B This equipment has been Barksdale deleted from the Master D2HA150SS Equipment List since this equipment is only required to function for a small break .ACA event, and its environment is mild for this event. Therefore it is not in the scope of 10CFR50.49.

99 SOV II.C Aging The equipment has been ASCO deleted from the Master NP831654E Equipment List because this equipment is associated with the fast closing valves which will not be installed.

100 SOV I.B Documentation Qualification ASCO Similarity documentation, not 2063816F previously available to FRC, which quellfles the equipment, will be on flie at our engineering office.

101 MOV II.A Documentation This equipment has been Limitorque Aging deleted from the Master SMB-1 Qualified Life Equipment' List since this Radiation equipment is only required to function'for a ses11 break LOCA event, and its environment is mild for this event. Therefore it is not in the scone of 10CFR50.49.

102 SOV I.B Documentation Qus11fication ASCO Similarity t.ocumentation, not 2068323 previously available to FRC, which qualifies the equipment, will be on flie-at our engineering office.

Enclosure 1 Page 20 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 103 SOV I.B Documentation Qualified replacement ASCO valves ASCO (206-380-7F) have 8320C29F already been installed.

8311A31F 104 NOV Aging Qualification Limitorque II.A Qualified Life documentation, not SMB-3 Radiation previously available to SMB-4T FRC, Which qualifies the equipment, will be on file at our engineering office.

105 SOV I.B Documentation Equipment performs its ASCO function before its exposure 8315C22 to the harsh environment and subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

106 SOV II.A Aging Qualification ASCO Similarity documentation, not NP1 previously available to FRC, Which qualifies the equipment, will be on file at our engineering office.

107 Radiation Monitor II.A Documentation Equipment performs its General Electric function before its exposure 194K927Cl2 to the harsh environment and

,1 subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

L _

_J

Enclosure 1 Page 21 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM

30. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 108 SOV II.A Documentation Equipment performs its ASCO Similarity function before its exposure NP1 Aging to the harsh environment and Duration subsequent failure of the equipment does not degrade other safety functions or mislead the operator.

109 SOV II.A Similarity Some of these valves have Target Rock Aging qualification documentation 75E002 not previously available to FRC, which qualifies them and is on file at our engineering office. Some of the valves perform their function before their exposure to the harsh environment and subsequent failure of the valve does i

not degrade other safety functions or mislead the

operator. One valve will be replaced with qualified i

Target Rock Model 82-U valve during the 1984 Refueling Outage.

110 SOV II.A Similarity FRC Item #110 has been Target Rock Aging superseded by FRC Item #109.

75E001 111 SOV I.B Documentation These valves will be replaced Atkomstic with qualified Target Rock  !

15840VPINOD Nodel (82-U) valves during i the 1984 Refueling Outage. l l

l

Enclosure 1 l Page 22 of 24 STATUS OF ITEMS ADDRESSED l IN FRANKLIN RESEARCH CENTER TER-CS257-496

{

ITEM-

50. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION l 112 SOV II.A Similarity One valve performs its Target Rock Aging function before its exposure 75E002 to the harsh environment and subsequent failure of the valve does not degrade other safety functions or mislead the operator. Two valves will be replaced with qualified Target Rock Model 82-U valves during the 1984 Refueling Outage.

113 SOV I.B Documentation These valves will be replaced Atkomatic with qualified Target Rock 15840VPIMOD Model 82-U valves during the 1984 Refueling Outage.

114 SOV II.C Aging These concerns will be ASCO addressed in the ongoing NP8323A36V Maintenance and Surveillance Program.

115 SOV II.C Aging These concerns will be ASCO addressed in the ongoing NP8323A36V Maintenance and Surveillance Program.

116 Motor Control II.A Documentation This equipment has been Center deleted from the Marter Westinghouse Equiprent List since this Type W equipment is only required to function for a small break LOCA event, and its environment is mild for this event. Therefore, it is not in the scope of 10CFR50.49.

l i

Enclosure 1 Page 23 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM NO. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 117 Motor Control II.A Documentation The equipment has been Center deleted from the Master Westinghouse Equipment List since this Type W equipment is only required to function for a small break LOCA event and its environment is mild for this event. Therefore, it is not in the scope of 10CFR50.49.

118 Temperature II.A Documentation These switches will be Switch similarity replaced with qualified Fenwal Steam Exposure Fenwal switches Model 17023-6 (01-170-230-090) during the 1984 Refueling Outage.

119 Pressure Switch III.B This equipment has been Barksdale deleted from the Master B2TM12SS Equipment List since this equipment is only required to function for a small break LOCA event, and its environment is mild for this event. Therefore, it is not in the scope of 10CFR50.49.

120 Flow Transmitter III.B This equipment has been General Electric deleted from the Master GE/MAC 555 Equipment List since this equipment is only required to function for a small besak LCCA event, and its environment is slid for this event. Therefore, it is not in the scope of 10CFR50.49.

l I

4 f

)

k

Enclosure 1 Page 24 of 24 STATUS OF ITEMS ADDRESSED IN FRANKLIN RESEARCH CENTER TER-C5257-496 ITEM

30. DESCRIPTION CATEGORY DEFICIENCIES PROPOSED RESOLUTION 121 Pressure Stritch III.B This equipment has been Barksdale deleted from the Master J D2HN12SS Equipment List since this equipment is only required to function for a small break LOCA event, and its environment is mild for this event. Therefore, it is not in the scope of 10CFR50.49.

122 Pressure II.A Documentation The equipment has been Transmitter deleted from the Master General Electric Equipment List because we GE/NAC 552 are using other qualified equipment and it is no longer in the scope of 10CFR50.49.

l L

l

. . )

l Page 1 of 6 ADDITIONAL ITEMS ADDED SINCE THE FRC TECHNICAL EVALUATION REPORT Description Status Solenoid Valve Documentation which demonstrates that this Target Rock equipment is environmentally qualified will be 82-U on file in our engineering office.

H2 /02 Monitors Documentation which demonstrates that this Teledyne equipment is environmentally qualified will be 225CMA-2 on file in our engineering office.

Solenoid Valve Documentation which demonstrates that this Asco equipment is environmentally qualified will be HVA90-405-2A on file in our engineering office.

Solenoid Valve This equipment will be replaced by ASCO Model Asco (NP-8316 A77E) valves, which are HPK 8211C13 environmentally qualified, during the 1984 refueling outage.

Solanoid Valve This equipment will be replaced by ASCO Model Asco (206-380-2F) valves, which are environmentally HBT-8300-D58F qualified, during the 1984 refueling outage.

Battery Documentation which demonstrates that this C&D equipment is environmentally qualified will be KC-9 on file in our engineering office.

Battery Charger This equipment will be relocated to an area C&D with a mild environment during the 1984 ARR24CE50F3 refueling outago.

Distribution Panel Documentation which demonstrates that this Mercury equipment is environmentally qualified will be

. on file in our engineering office.

Distribution Panel (VAC-B) Documentation which demonstrates that this General Electric equipment is environmentally qualified will be on file in our engineering office.

Page 2 of 6 ADDITIONAL ITEMS ADDED SINCg THE FRC TECHNICAL EVALUATION REPORT Description Status Electric Heaters and Documentation which demonstrates that this i Thermostat equipment is environmentally qualified will be Chromalox on f11e in our engineering office.

D106-114426-000 i

Flow Switch This equipment will be qualified or will be Mcdonald-Miller replaced by environmentally qualifled NP-8 equipment during the 1984 refueling outage.

Temperature Switch This equipment will be replaced by Fenwal Model Fenwal (01-170020-090) switches, which are

17002-40 environmentally qualified, during the 1984 refueling outage.

Level Transmitters Documentation which demonstrates that this Rosemount equipment is environmentally qualified will be 1152's on file in our engineering office.

Pressure Switch This equipment will be replaced by .

Barksdale Static-0-Ring Model (5TA-B45-NK-CIA-JJTTI6)

B2T-A12-SS and Model (9TA-B45-MI-C1A-JJTT16) switches,

. which are environmentally qualified, during the 1984 refueling outage.

Trip Cards Documentation which demonstrates that this l Rosemount equipment is environmentally qualifled will be 510 DU's on file in our engineering office.

Relays Documentation which demonstrates that this Agastat equipment is environmentally qualified will be EGPB001 on flie in our engineering office.

Trip Cards This equipment will be replaced by Rosemount Rosemount Model (710 DUs), which are environmentally 510 DU's qualified, during the 1984 refueling outage, i' Relays Documentation which demonstrates that this Agastat equipment is environmentally qualified will be ETR14B38001 on file in our engineering office.

Level Transmitters Documentation which demonstrates that this Rosemount equipment is environmentally qualified will be 1153's on file in our engineering office. 1 Pressure Switches Documentation which demonstrates that this i PCI equipment'is environmentally qualified'will be

[ A1711 on file in our engineering office.

Page 3 of 6 ADDITIONAL ITEMS ADDED SINCE THE FRC TECHNICAL EVALUATION REPORT Description Status Pressure Switches This equipment will be replaced by

. PENN Static-O-Ring Model (STA-BB45-NX-C1A-JJTTX6)

P72AA-997 switches, which are environmentally qualified, during the 1984 refueling outage.

Limit Switches This equipment will be replaced by Namco Model Namco (EA-740-20000) switches, which are SL-3 environmentally qualified, during the 1984 refueling outage.

Power Supply Documentation which demonstrates that this Elma equipment is environmentally qualified will be 164CS261 on file in our engineering office.

Power Supply This equipment will be relocated to an area Elma where the environment is within the 164C5261 qualification limits of the equipment during the 1984 refueling outage.

! Control Panel (RHR Alt S/D) Documentation which demonstrates that this

, Mercury equipment is environmentally qualified will be N/A on file in our engineering office.

Differential Pressure This equipment will be replaced by Rosemount Transmitter ,(1153s), which are m vironmentally quellfied.

GE/NAC 552 during the 1984 refueling outage.

Flow Switch Documentation which demonstrates that this Barton equipment is environmentally qualified will be f 289A on file in our engineering office.

Motor Operator Documentation which demonstrates that this Limitorque equipment is environmentally qualified will be on file in our engineering office.

Position Transmitter This equipment is currently being Limitorque re-evaluated, this item will be deleted from N/A the Master squipment List or environmentally quellfied.

Alternate Shutdown Documentation which demonstrates that this control Panel (RCIC) equipment is environmentally qualified will be Mercury on file in our engineering office.

N/A Manual Transfer Switch (D.C.) Documentation which demonstrates that-this Westinghouse equipment is environmentally qualified will be

-NT88 on file in our engineering office, i

)

l l

l Page 4 of 6  ;

ADDITIO4&L 1753$8,ADDgD SINCE i THE FRC TECHNICAL FVALVATION_ REP 08T Descristion_ '

Status t ,

Local Starter jV13-16) Documentation which demonstrates that this l Westinghouse equipment is environmentally qualified will be Type W on f11e in our ensineering office.

Local Indicating A design change is planned during the 1984 Lights refueling outage which will prevent failure of

. the fuel pool. cooling pumps' local indicating lights from adversely affecting FP cooling pur.p operation. These lights will be removed  ;

from the Master List once the design changs is

~

implement,d.

Local control Switch This switch will be replaced by an

- Electroswitch Series 20 PDG switch, which is ,

environmentally qualified, during the US4 refueling outage.

Level Switch 'This equipment will be replaced by a FCI Jobe11 Model (8-66) level sensor, which is Model 8 ~ - environeentally quellfied, during the 1984 refueling outage. '

Level Switch Tht$ equipment will be replaced by a FCI Jobell.. Model (8-66) level sensor, ohich is  ;

Model K environmentally qualified, during the 1984 cefueling outete.

Pump Motor Documentation which demonstrates that this Weatinghouse Lifeline T equipment is environmentally qualified will be 460V, 125Hp Frame 405T on file in our enaineering office.

Pressure Switch This equipment will be replaced by Ashcroft Static-0 Ring Model (12TA-545-NX-CIA-TTJJg6) 6480 dwitches, which are environmentally qualified,

, 'during the 1984 refueling outage .

Terminal Block Documentation which demonstrates that this cinch Jones equipsont is environmentally qualified will be on file in our engineering office.

Terminal 91ock Documentation which demonstrates that this Buchanan equipment is environmentally qualified will be 0222 on file in our engineering offlee.

Control Cable "

Documentation which demonstrates that this Rockbestos equipment.,is environmentally quellfied will be Firewell III '

on flie'in'our engineering office.

,j s j h ,-

. +

f

,.-%,- .Ls. .m,_ -,,r----

it . ..

Page 5 of 6 ADDITIONAL ITEh8 ADDED SINCE 2 THE FRC TECHNICAL EVALUATION REPORT 4

Description Status

! Co-Axial Cable Documentation which demonstrates that this j Endevco equipment is environmentally qualified will be 3075N6 on file in our engineering office.

SIE Wire Documentation which demonstrates that this Rockbestos equipment is environmentally qualified will be i Firewall III on file in our engineering office, i

Power Cable This equipment will be replaced during the

! Okonite 1934 outage with Rockbestos Rocktherm 5 kV EPR/Hypalon power cable which is quellfled.

! Instrument Cable Documentation which demonstrates that this j Rockbestos equipment is environmentally qualified will be Firews11 III on file in our engineering office.

i Cable Splice Kit Documentation which demonstrates that this Raychem equipment is environmentally qualifled will be

on file in our engineering office.

I

! Co-Axial Cable Documentation which demonstrates that this i Rockbestos equipment is environmentally qualified will be l Firewall III on file in our engineering office.

Fuseholder Documentation which demonstrates that this

. General Electric equipment is environmentally qualified will be i 175A9132P008 on file in our engineering office.

i

! SIS Wire Documentation which demonstrates that this General Electric equipment is environmentally qualified will be on file in our engineering office.

Fuse Documentation which demonstrates that this i General Electric equipment is environmentally qualified will be

. 167A2452P003 on file in our engineering office..

h

Thermocouple Wire Documentation which demonstrates that this Rockbestos equipment is environmentally qualified will be Firewall III on file in our engineering office.

Local Power Range Monitor Documentation which demonstrates that this i General Electric equipment is environmentally qualified will be i 129836200024 on flie in our engineering office.

I m

)

l Page 6 of 6 l ADDITIONAL ITRMS ADDED SINCE THE FRC TECHNICAL EVALUATION REPORT _

Description Status Co-Axial Cable Documentation which demonstrates that this Lewis equipment is environmentally qualified will be RG-95 high temperature on file in our engineering office.

Co-Axial Cable Documentation which demonstrates that this Lewis equipment is environmentally qualified will be RG-95 on file in our engineering office.

Connector Documentation which demonstrates that'this Neutron Monitoring equipment is environmentally qualified will be on file in our engineering office.

Control Rod Documentation which demonstrates that this Position Indication equipment is environmentally qualified will be General Electric on file in our engineering office. '

Signal Cable Documentation which demonstrates that this 600V equipment is environmentally qualified will be Vulkene/ Neoprene on file in our engineering office.

Signal Cable Documentation which demonstrates that this 600V equipment is environmentally qualified will be PEPS on file in our engineering office.

=

'&=

,e-f a .y

\

~

Y -

-yl

q. - #

4 g

-s. , ,

-^, * ._ ;

e v '

  • t,' '.iQ,.

4

\ I- , - . ,