ML20092L308

From kanterella
Jump to navigation Jump to search
Revised Page 71B to Application for Amend to Licenses DPR-44 & DPR-56,correcting Typographical Error Re Setpoint of CV-6 Relay
ML20092L308
Person / Time
Site: Peach Bottom  
Issue date: 06/25/1984
From:
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To:
Shared Package
ML20092L297 List:
References
NUDOCS 8406290346
Download: ML20092L308 (1)


Text

v

~

"*Q; TABLE:3.2.B (CONTINUED)

INSTRUMENTATION'THAT INITIATES OR CONTROLS THE CORE AND CONTAINMENT' COOLING SYSTEMS NInimum No.

Of Operable Number of Instru-Instrument Trip Function Trip Level Setting ment Channels Pro-Remarks Channels Per

_vided by Design Trip System (l) 2 per 4 KV Emergency Trans-87% (+/- 5%) of

1. Trips emergency Bus former Degraded Rated Voltage.

transformer feed to voltage (Inverse Tests at 2940 4KV emergency bus, time - voltage).

' volts in 30 seconds

2. Fast transfer (CV-6 )

(+/- 10 %).

permissive.

I 8406290346 840625 PDR ADOCK 050002{

P