I 4

p

.4 TENNESSEE VALLEY AUTHORITY CHATTANOOGA, TENNESSEE 37401 400 Chestnut Street Tower II r

i AdeJ W W84 j2: y P

BLRD-50-438/84-34 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. ' James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia. 30303.

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNIT 1 - CONDUIT SUPPORT STIFFENER PLATES NOT INSTALLED PER DRAWING - BLRD-50-438/84-34, - FIRST INTERIM REPORT The subject deficiency was initially reported to NRC-OIE Inspector P. E. Fredrickson on May 10, 1984 in accordance with 10 CFR 50 55(e) as NCR

't 3069 Enclosed is our first interim report. We expect to submit our next report by September 28, 1984.

If you have any questions, please get in touch with R. H. Shell at FTS 858-2688. " -

Very truly yours, TENNESSEE VALLEY AUTHORITY D S k-~

L. M. Mills, Manager Nuclear Licensing Enclosure oc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Records Center (Enclosure)

Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia. 30339 8406190249 840604 PDR ADOCK 05000438 S

PDR h

4 1983-TVA 50rH ANNIVERSARY w

An Equal Opportunity Employer

[b

.v

c.

(r ENCLOSURE

/ / ;,

, v, BELLEFONTE NUCLEAR PLANT UNIT 1 CONDUIT SUPPORT STIFFENER PLATES NOT INSTALLED PER DRAWING BLRD-50-438/84-34 NCR 3069 10 CFR 50.55(e)

FIRST INTERIM REPORT s.

Description of Deficiency During a quality control audit, it was identified that two stiffener plates for support FF-768-6,, Mark No. 31, were installed approximately 2 inches fr'om the proper location as shown on TVA design drawing 4RA0560-X2-32 R3 The support is a seismic category I support for electrical conduit carrying safety-related gables. It is located inside the unit 1 Reactor Building.

..y Interim Progress TVA is neanalyzing the as-built. configuration for support FF-768-6, Mark TVA is also No. 31, to determine whether modifications are necessary.

conducting' an investigation into the possibility of other supports being affected by this deficiency.