ML20091Q992
| ML20091Q992 | |
| Person / Time | |
|---|---|
| Site: | Monticello |
| Issue date: | 12/31/1994 |
| From: | NORTHERN STATES POWER CO. |
| To: | |
| Shared Package | |
| ML20091Q987 | List: |
| References | |
| NUDOCS 9509060170 | |
| Download: ML20091Q992 (10) | |
Text
.
Attachment B Updated Effluent and Waste Disposal Semi-Annual Report, Period July-December 1994 Analysis of Sr-89 and Sr-90 for the 4th quarter of 1994 were not completed in time to be included with the semi-annual report for the second half of 1994. The semi-annual report for the second half of 1994 with 4th quarter Sr-89 and Sr-90 results is attached.
9509060170 950829 PDR ADOCK 05000263 R
.PDR
- - -.. + _, _.. _ _
NORTHERN STATES POWER COMPANY MONTICELLO NUCLEAR GENERATING PLANT License No. DPR-22 i
1 EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT Period Jul - Dec 1994 Supplemental Information 1.
Regulatory Limits - Quarterly levels requiring reporting to Nuclear Regulatory Commission A.
Noble Gases :
5 mrad / quarter gamma radiation 10 mrad / quarter beta radiation B.
Long Lived Iodines, Particulates, and Tritium 7.5 mrem / quarter dose to any organ C.
Liquid Effluents 1.5 mrem / quarter dose to the total body 5.0 mrem / quarter dose to any organ 2.
Maximum Permissible Concentrations A.
Noble Gases 10 CFR Part 20, Appendix B, Table II, Column 1 B.
Long Lived Iodines, Particulates, and Tritium 10 CFR Part 20, Appendix B, Table II, Column 1 C.
Liquid Effluents 10 CFR Part 20, Appendix B, Table II, Column 2 2.0 E-4 uci/ml for dissolved and entrained gases
- 3. Average Energy (Not Applicable)
. - ~ -.
l-Page 2
o EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT t
Period : Jul - Dec 1994 Supplemental Information (continued)
- 4. Measurements and Approximations of Total Radioactivty A,
Noble Gases :
Continuous gross activity monitors in Reactor Building Vent and Plant l
Stack exhaust streams.
Weekly isotopic analysis of exhaust streams.
f B.
Iodines in Gaseous Effluent :
t Continuous monitoring with charcoal cartridges in Reactor Building Vent and Plant Stack exhaust streams with weekly analysis, i
C.
Particulates in Gaseous Effluent :
Continuous monitoring with particulate tilters in Reactor Building Vent and Plant Stack exhaust streams with weekly analysis.
D.
Tritium in Gaseous Effluent :
j
'Continous monitoring with silica gel cartridges in Reactor Building Vent and Plant Stack exhaust streams with weekly analysis.
E.
Liquid Effluents :
Tank sample analyzed prior to each planned release and continuous l
monitoring of gross activity during planned release.
i
- 5. Batch Releases i
4 A.
Liquid :
- 1. Number of Batch Releasee 0
- 2. Total Time Period for Batch Releases 0.0 min
- 3. Maximum Time Period for a Batch Release 0.0 min
- 4. Average Time Period for a Batch Release 0.0 min
- 5. Minimum Time Period for a Batch Release 0.0 min
- 6. Average River Flow During Release 0.0 cf/sec B. Gaseous :
1.
Number of Batch Releases 4
- 2. Total Time Period for Batch Releases 3137.0 min
- 3. Maximum Time Period for a Batch Release 1962.0 min
- 4. Average Time Period for a Batch Release 784.3 min i
- 5. Minimum Time Period for a Batch Release 293.0 min l
l
Page 3
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL' REPORT i
Period : Jul - Dec 1994 Supplemental Information (continued)
' 6 Abnormal Releases i
A. Liquid :
'1.
Number of Releases 0
- 2. Total Activity Released 0.0 Ci i
B.
Gaseous :
1.
Number of Releases 0
- 2. Total Activity Released 0.0 Ci f
i 9
i 1
1 t
I r
L i
l 8
?
h b
er
=
<--1 r
T
Page
.4 l
4 + -
l EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT Period : Jul - Dec 1994 Table 1A Gaseous Effluents - Summation of all Releases Units 3rd Qtr 4th Qtr Est. Total Error, %
j A.
Fission & Activation gases 1.
Total Release Ci 1.06E+02 9.67E+01 2.00E+01 l 2.
Averace Release Rate uci/sec 1.33E+01 1.22E+01 3.
Percent Tech Spec Qtrly Reporting Level Gamma Radiation 8.34E-02 6.14E-02 Beta Radiation 4.13E-02 2.04E-02 B.
Iodines 1.
Total I-131 Release Ci 2.54E-03 8.39E-04 1.00E+01 l l
2.
Average I-131 Release Rate uci/sec 3.19E-04 1.06E-04 C.
Particulates 1.
Total Particulates Ci 8.29E-04 6.36E-04 3.00E+01 l
- 2. Averaae Release Rate uci/sec 1.04E-04 8.01E-05 3.
Gross Aloha Radioactivity Ci 6.41E-06 3.98E-06 D.
Tritium 1.
Total Release Ci 2.11E+01 1.33E+01 1.00E+01 l 2.
Average Release Rate uci/sec 2.65E+00 1.68E+00 E.
Percent Qtrly Tech Spec Reporting Levels 1.
Iodines, Particulates, and Tritium 4.28E-01 1.06E-01
~
Page 5
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT Period : Jul - Dec 1994 Table 1B Gaseous Effluents - Elevated Releases Continuous Mode Batch Mode Nuclides Released Unit 3rd Otr l 4th Otr 3rd Otr i 4th Otr 1.
Fission Gases KR-85M Ci 1.27E-02 1.21E+00 0.00E+00 0.00E+00 KR-87 Ci 7.42E-01 1.79E+00 0.00E+00 0.00E+00 KR-88 Ci 7.96E-01 2.86E+00 0.00E+00 0.00E+00 KR-89 Ci 9.39E-01 0.00E+00 0.00E+00 0.00E+00 XE-133 Ci 3.65E+01 2.50E+01 0.00E+00 8.08E-03 XE-133M Ci 4.70E-01 3.58E-01 0.00E+00 0.00E+00 XE-135 Ci 2.86E+00 1.83E+01 0.00E+00 4.76E-03 XE-135M Ci 5.68E+00 8.12E+00 0.00E+00 0.00E+00 XE-137 Ci 3.04E+01 1.48E+01 0.00E+00 0.00E+00 XE-138 Ci 1.59E+01 1.89E+01 0.00E+00 0.00E+00 AR-41 Ci 0.00E+00 6.46E-02 0.00E+00 1.87E-02 Total for Period Ci 9.43E+01 9.13E+01 0.00E+00 3.15E-02 2.
Iodines I-131 Ci 5.73E-04 5.80E-04 0.00E+00 0.00E+00 I-133 Ci 2.13E-03 2.19E-03 0.00E+00 0.00E+00 I-135 Ci 2.69E-03 1.17E-03 0.00E+00 0.00E+00 Total for Period Ci 5.39E-03 3.94E-03 0.00E+00 0.00E+00 3.
Particulates CR-51 Ci 7.54E-07 0.00E+00 0.00E+00 0.00E+00 MN-54 Ci 1.97E-07 8.40E-07 0.00E+00 0.00E+00 CO-60 Ci 2.79E-06 6.54E-06 0.00E+00 1.47E-07 ZN-65 Ci 4.37E-06 4.66E-06 0.00E+00 0.00E+00 RU-103 Ci 0.00E+00 4.63E-08 0.00E+00 0.00E+00 CS-137 Ci 1.05E-06 2.01E-06 0.00E+00 0.00E+00 BA-140 Ci 1.36E-04 9.73E-05 0.00E+00 0.00E+00 SR-89 Ci 7.06E-05 7.73E-05 0.00E+00 0.00E+00 SR-90 Ci 3.73E-07 2.52E-07 0.00E+00 0.00E+00 Total for Period Ci 2.16E-04 1.89E-04 0.00E+00 1.47E-07
Page 6
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT Period : Jul - Dec 1994 Table 1C Gaseous Effluents - Building Vent Releases Continuous Mode Batch Mode Nuclides Released Unit 3rd Otr i 4th Otr 3rd Otr l 4th Otr 1.
Fission Gases XE-133 Ci 3.94E-01 0.00E+00 7.31E-03 3.24E-03 XE-135 Ci 1.04E+01 4.68E+00 6.01E-03 0.00E+00 XE-135M Ci 8.29E-01 5.99E-01 0.00E+00 0.00E+00 AR-41 Ci 0.00E+00 0.00E+00 1.23E-03 1.41E-02 Total for Period Ci 1.16E+01 5.28E+00 1.46E-02 1.73E-02 2.
Iodines I-131 Ci l 1.96E-03 2.59E-04 0.00E+00 0.00E+00 I-133 Ci 1.24E-02 1.32E-03 0.00E+00 0.00E+00 I-135 Ci 1.92E-02 2.13E-04 0.00E+00 0.00E+00 Total for Period Ci 3.36E-02 1.79E-03 0.00E+00 0.00E+00 3.
Particulates MN-54 Ci 3.91E-06 6.03E-06 0.00E+00 0.00E+00 CO-58 Ci 5.57E-06 0.00E+00 0.00E+00 0.00E+00 CO-60 Ci 1.96E-04 1.45E-04 2.02E-06 0.00E+00 ZN-65 Ci 2.87E-04 2.64E-04 0.00E+00 1.35E-05 CS-137 Ci 6.80E-05 1.18E-05 0.00E+00 0.00E+00 BA-140 Ci 3.24E-05 0.00E+00 0.00E+00 0.00E+00 CE-141 Ci 1.00E-06 0.00E+00 0.00E+00 0.00E+00 SR-89 Ci 1.73E-05 6.71E-06 0.00E+00 0.00E+00 SR-90 Ci 1.25E-07 2.25E-07 0.00E+00 0.00E+00 Total for Period Ci 6.11E-04 4.34E-04 2.02E-06 1.35E-05
__.m Page 7
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT Period : Jul - Dec 1994 Table 2A Liquid Effluents - Summation of all Releases Units 3rd Qtr 4th Qtr Est. Total Error, %
A.
Fission & Activation products 1.
Total Release (not including tritium, cases, alpha)
Ci 0.00E+00 0.00E+00 0.00E+00 i
2.
Ava Diluted Concentration uci/ml 0.00E+00 0.00E+00 B. Tritium 1.
Total Release Ci 0.00E+00 0.00E+00 0.00E+00 l 2.
Ava Diluted Concentration uci/ml 0.00E+00 0.00E+00 C.
Dissolved and Entrained Gases 1.
Total Release Ci 0.00E+00 0.00E+00 0.00E+00 l 2.
Ava Diluted Concentration uci/ml 0.00E+00 0.00E+00 D.
Percent Qtrly Tech Spec Reporting Level 1.
Whole Body Dose 0.00E+00 0.00E+00 2.
Oraan Dose, 0.00E+00 0.00E+00 E.
Gross Alpha Radioactivity l
1.
Total Release l
Ci l 0.00E+00 l 0.00E+00 1 0.00E+00 l lF. Volume of Waste Released l
Liters I 0.00E+00 l 0.00E+00 l 0.00E+00 l t
lF. Volume of Dilution Water Used l Liters I 0.00E+00 l 0.00E+00 l 0.00E+0Q_l Table 2B Liquid Effluents Continuous Mode Batch Mode Nuclides Released Unit 3rd Otr I 4th Otr 3rd Otr l 4th Otr None Released This Period L
Page 8
(
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT Period : Jul - Dec 1994 Table 3 Solid Waste and Irradiated Fuel Shipments A.
Solid Waste Shipped Offsite for Burial or Disposal (not irradiated fuel) 1.
Type of Waste Units 6-month Est. Total Period Error. %
a.
Spent resins, filter sludges, Cu. Meter 0.00E+00 evaporator bottoms. etc.
Ci 0.00E+00 0.00E+00
- b. Dry compressible waste, Cu. Meter 0.00E+00 contaminated eauipment. etc.
Ci 0.00E+00 0.00E+00 c.
Irradiated components, Cu. Meter 0.00E+00 control rods. etc.
Ci 0.00E+00 0.00E+00
- d. Other (describe)
Cu. Meter 0.00E+00 Ci 0.00E+00 0.00E+00 2.
Estimate of major nuclide composition (by type of waste)
Type A Type B Type C Type D Nuclide cercent percent percent percent No Shipments this period.
l
Page 9
EFFLUENT AND WASTE DISPOSAL SEMIANNUAL REPORT j
Period : Jul - Dec 1994 I
I Table 3 Solid Waste and Irradiated Fuel Shipments j
1 3.
Solid waste disposal Number of Mode of Destination Shinments Transoortation i
None This Period B.
Irradiated Fuel Shipments I
1.
Disposition Number of Mode of Destination Shioments Transportation None This Period f
C.
Shipping Container and Solidification Method No.
Volume Activity Type of Container Solidification M3 Ci Waste Code Code No Shipments this period.
Container Codes :
Solidification Codes :
L-LSA C - Cement A - Type A U - Urea Formaldehyde l
B - Type B D - Dewatering O - Large Quantity N-Not Applicalble i
t 7
p
-