ML20091N344

From kanterella
Jump to navigation Jump to search
Responds to IE Bulletin 80-13 Re Core Spray Spargers & Associated Internal Piping.Reexam Indicates Two Cracks Found in Sys During 1984 Refueling/Maint Outage May Be One Unique Crack.No Corrective Action Required
ML20091N344
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 05/31/1984
From: Mangan C
NIAGARA MOHAWK POWER CORP.
To: Murley T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
IEB-80-13, NUDOCS 8406120286
Download: ML20091N344 (1)


Text

,.

l NUMOHAWK Y NIAGARA l'i NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST, SYRACUSE. N Y.13202/TELEPbhE (316) 474-1511 e

-b 7..

U May 31, 1984

[] "l Dr. Thomas E. Murley Regional Administrator U. S. Nuclear Regulatory Consnission Region I 631 Park Avenue King of Prussia, PA 19406 Re: Nine Mile Point Unit 1 Docket No. 50-220 DPR-63

Dear Dr. Murley:

In accordance with Information and Enforcement Bulletin 80-13, Niagara Mohawk has visually inspected the Nine Mile Point Unit I core spray spargers and associated internal piping during the 1984~ refueling and maintenance outage.

Our submittal of May 13, 1981 indicated two small cracks existed in the core spray system. Our recent reexamination appears to indicate that the two cracks may be one unique crack. The combined total length of the crack (s),

however, remains insignificant (at present, 3/4 inch + 1/4 inch)..Since no other indications of cracks were found, no corrective action is required at this time. Furtner, Niagara Mohawx will continue to visually inspect the core spray spargers and associated internal piping during future refueling outages.

Sincerely, NIAGARA M0 HAWK POWER CORPORATION C. V. Mangan Vice President Nuclear Engineering and Licensing

-AJP:bd t

cc: NRC Office of Inspection and Enforcement Division of Reactor Operations Inspection Washington, D.C.

20555 Director Nuclear Reactor Regulation

. Attention: Mr. Domenic B. Vassallo, Chief 4

Operating Reactors Branch No. 2 Division of Licensing U. S. -Nuclear Regulatory Consnission Washington, D.C. -'20555

'8406120286 840531 PDR ADOCK 05000220

$ 0 a

_st_