. _ _ _ _ _ _ .

~

' C311-95-2071-Page 1

6. 8. 4" ' . Radioloaical' Environmental Monitorina Proaram A program shall be provided to monitor the radiation and radionuclides in the environs of the plant. The program shall provide (1) representative measurements of radioactivity in the highest potential exposure pathways, and (2) verification of the accuracy of the effluent. .

monitoring program and modeling of environmental exposure pathways.

The program shall (1) be contained in the ODCM, (2) conform to the guidance of Appendix I to 10 CFR Part 50, and (3) include the s following:

(1)  : Monitoring, sampling, analysis, and reporting of radiation and radionuclides in the environment in accordance with the methodology and parameters in the ODCM, t

(2) A Land Use Census to ensure-that changes in the use of areas at and beyond the-SITE BOUNDARY are identified and that ,

modifications to the monitoring prograra are made if required by the results of this census, and (3) Participation in an Interlaboratory Comparison Program to ensure that independent checks on the precision and accuracy of the measurements of radioactive materials in environmental sample matrices are performed as part of the quality assurance program ,

for environmental monitoring. )

b. Radioactive Effluent Controls Program A program shall be provided conforming with 10 CFR 50.36a for the control of radioactive effluents and for maintaining the doses to MEMBERS OF THE PUBLIC from radioactive effluents as low as reasonably 1 achievable. The program (1) shall be contained in the ODCM, (2) shall be implemented by operating procedures, and (3) shall include remedial actions to be taken whenever the program limits are exceeded. The  !

program shall include the following elements:

(1) Limitations on the operability of radioactive liquid and gaseous monitoring instrumentation including surveillance tests and setpoint determination in accordance with the methodology in the ODCM, (2) Limitations on the concentrations of radioactive material released in liquid effluents to unrestricted areas conforming to 10 times the concentrations specified in 10 CFR Part 20.1001.-

20.2402, Appendix B, Table 2, Column 2, (3) Monitoring, sampling, and analysis of radioactive liquid and gaseous effluents in accordance with 10 CFR 20.1302 and with the methodology and parameters in the ODCM, 6-11a Amendment No. W , .

4 9508290112 950823 PDR ADOCK 05000289 p PDR j