ML20090L670

From kanterella
Jump to navigation Jump to search
Rev 4 to Special Process Std NUT-NC-1E, Nuclear Ultrasonic Weld Exam Calibr Procedure
ML20090L670
Person / Time
Site: Monticello 
Issue date: 01/10/1975
From: Lambert T
NORTHERN STATES POWER CO.
To:
Shared Package
ML20090L649 List:
References
NUT-NC-1E, NUDOCS 9102120501
Download: ML20090L670 (22)


Text

_ _ _. _ _ _. _ _

4 SPECIAL PROCESS STANDARD

'f * "

u eettaste et. past 4 t t tt tivt tia tt Huelcar Ultraconic Wold Examination T. G. Lv.bert-1/5/75 A n'rirv 1 1975

""' B " /'"

Calibration Procedure

  • f' k h J d llLefr1 (

22 l

oa S

1.0 SCOPE s

This document definec procedures for preparing ultraconic testing equiprent calibration records to meet or exceed the requirements of Appendix IX,Section III Su=er 197h Addenda,Section V, Sumner 1974 Addenda, and Section XI, Sumer 197h Addenda of the AS!!E Boiler & Precoure Vescel Code.

l 2.0 SPECIFICATIONS 2.1 The indicated revision of the folle:Ving specification shull form a part of this document.

2.1.1 AS!'E Boiler and Pressure Vessel Code Section XI (Su=cr 197h) l 2.1.2 SNT-TC-1A, Qualification and Certification of Mondestructive Testing Personnel Suppleme.it C '

2.1.3 ASTM E-317-68. Evaluating Performance Characteristics of Pulce Echo Ultrasonic Testing Systems 2.1.h ASPE loiler and Pressure Virssel Code,Section III,(Sumner 197L) l 2.1.5 NUT-NO-1A, Nuclear Ultrasonic Testing Procedures Ultrasonic Insrection of Welds 2.1.6 NUT-NC-10. Ultrasonic Exanf. nation of Inner Radius of Prescure Vessels at Monticello 2.1. 'i NUT-NC-7, Nuclear Ultrason!c Examination of Beactor Precr.ure Vessel Butt and Nozzle Welc.s j

2.1.8 NUT-NC-3, Procedure for Automatic Recording of Ultrasonic Test Data.

2.1 9 ASME Boiler and Pressure Vessel Code Section V (Su..er 197L) 2.1.10 ASTM E-16h, Standard Recor.. ended Practice for Ultrasonic Contact Examination of Weldmento l

3.0 PERSONNEL OUALIFICATIONS I

l 3.1 All personnel performinn ultraconie inspectiono shall be qualified in accordance: vith Code accepted r.tandarde and proceduren ac either Level I (Operator), Level II (Inspector), or Level III (Exttniner),

9102120501 750624 PDR ADGCK 05000263 P

PDR l

NUCLEAR SERVICES CORPORATION l.

l

"" ^

SPECIAL PROCESS STANDARD

/F" "

2 or 22 31 (continued) 4 as defined in SNT-TC-1A, Supplement C and NUT-PQ-1, Rev. O.

Only a Level II Inspector or Level III Examiner shall make judgnent as to the neceptance or rejection of indications.

The Nuclear Services Corpora-j tion Level III Examiner vill submit to the purchaser, upon request, a copy of personnel qualification and ultrasonic procedures. Percennel j

shall, at the request of the Purchaser, demonstrate their kncvledge and understanding of pertinent specifications and procedures and their 4

ability to satisfactorily operate all required equipment pritr to per-l forming an ultrasonic inspection.

h.O TEST EQUIPMMjT h.1 Ultrasonic test instruments calibrated per ASTM E317-68 shall be j

used.

J h.2 Electronic calibration records shall be maintained for all instruments i

and certification for all transducers.

Instrument calibration stall

)

be performed at three month intervals.

l b.3 Battery povered instruments shall ir. elude internal stabilization re-l sulting in gain changes of less than 1 db and horizontal linearity i

changes of less than 6 percent of scale length during battery operating life.

4.4 Ultrasonic testing instruments shall have a calibrated gain control 1

adjustable in, at most, 2 decibel steps over a range of at least 60 db.

The accuracy of the gain control setting shall be verified as a part of system calibration as per item h.l.

j h.5 Ultrasonic transducer, either angle or straight beam, shall produce a sourd beam within + 3 degrees of the stated nominal value, i.e.,

j 0, h5', etc., as measured using an IIV-2 veld test block.

h.6 The nominal transducer parameters shall be clearly and permanently marked on the transducer.

These must include size, frequency, materials, angle, and index point. Transducers shall be serialiced.

50 CALIBRATION STANDARDS 51 Basic Calibration Blocks typified by those shown in Figures 1. h, 5, and 6 shall be used to determine the primary reference response of the equipment. These blocks conform to the requirements of Section III and XI of the ASME Boiler and Pressure Vessel Code, and the applicable Nucicar Services Weld Inspection procedure.

l 5.2 Curved basic calibration blocks for testing piping may contain an ad-ditional notch reference reflector.

?

NUCLEAR SERVICES CORPORATION

^

s o.o.

!iUT-N C-i r' P"v.

b SPECIAL PROCESS STANDARD

-i 3

o' 22 53 An International Institute of Welding Block (IIW-2) may be used for calibration check it, situations where the primary standard cannot be conveniently applied.

5.h An International Institute of Welding Block (IIW-2) may be used for determining transducer delay and display sweep settings.

5.5 Basic calibration Blocks shall be certified as to material and shall be traceable.

6.0 COUP! ANT 6.1 A Water base couplant certified free from halogen sball be used and its type shall be recorded on the Calibration Record Sheet.

7.0 CALIBRATION OF THE SYSTD4 FOR TESTING OF kTLDS - FXCLUDING THE FEACTOR FRESSURE VESSEL WELDS 7.1 Basic calibration blocks similar to those shown in Figures 1, 3, snd 5 shall be used.

a) The calibration reference reflectors shall be side drilled holes.

These reference reflectors shall be used to establish the primary reference response and to construct a distance amplitude correc-tion curve (DAC),

b) The Basic Calibration Block shall have thickness as indicated in the table of Figure 1 to match production material thickness.

Calibration for tests of circumferential velds on material lecs than 20" in diameter shall be cade using curved Basic Calibration B3ocks.

A curved block may be used to calibrate tests on mat erial h6ving diameters ranging from 90% to 150% of the basic block diameter.

c) The appropriate calibration reference reflector shall be machined in the block as shown in Figures 3 and 5 d) The completed block shall be permanently marked to enable trace-atility te material documentation.

7.2 Calibration Interval For the Examinstion Of Welds Other Than the Reactor Pressure Vessel 7.2.1 Calibration shall be performed on a daily basic before each day's examination and shall be checked before the performance

~

of each examination.

NUCLEAR SERVICES CORPORATION

SPECIAL PROCESS STANDARD X-""-'"

h or 22 7 2.2 Calibration checks may be made using a conveniently portable test block such as the IIW in lieu of the basie :alibration block.

7 2.3 Should a check indicate a change in amplitude response greater than 20% (2 db) the tester shall be immediately recalibrated.

7.2.h Performance of the calibration check shall be indicated on the inspection report er chart record generated for each examina-tion.

7.3 Generction Of the Dintance Amplitude Curve For Angle Beam Testing Of Nuclear Piping and Components - Excluding the Reactor Pressure Vesse:,

7.3.1 The distance amplitude correction curve shall be constructed by plot'ing responses from the Basic Calibration Reflector.

The first plotted point is the response from the reflector at the nearest point. This response shall be obtained by posi-tioning the transducer for maximum return. The gain control is then set so that this response is 75 percent of full nereen.

Without further changing the gain, the search unit shall be placed similarly at other nodal positions and the indication response shall be marked on the tester screen, and its metal path (in microseconds) and amplitude marked on the DAC curve plot of Figure 2.

This point is the PRIMARY REFELENCE RESPONSE.

The tester sweep shall be adjusted to display 2-1/2 moden when-ever possible.

7.3.2 Connect the plotted points on the tester screen and on the DAC cut 7e plot with a smooth line to form the DISTANCE A!PLITUDE CORREC2 ION curve.

7.h Generation Of the Distance Amplitude Curve For St*

ght Beam Tesiing Of Piping and Component Welds - Excludin6 the Reactor Pressure Vessel 7.h.1 A bistance Amplitude Correction Curve is not required for material one inch or less in thickness.

7.h.2 For material over one inch thick a Distance Amplitude Corree-tion Curve may be constructed using the proper calibratien block (determined by Figure 1).

With the search unit positioned for maximum response from the basic calibration hole at 1/h T (see Figure h), set the signal amplitude to 50% of screen height.

This is the PRIMARY STRAIGHT BEAM REFERENCE RESPONSE.

Without changing the instruments cettings, cimilarly position the search units over the reference reflector at 3/h T.

Mark the amplitude and position of both points on the screen and on the DAC Curve plot on the Calibration Record Sheet.

l NUCLEAR SERVICES CORPORATION

1 I

1 i

j in..

l SPECIAL PROCESS STANDARD A7-"~'"

e, or 22 l

{

7.h.3 Join the points generated in 7.h.2 vith a straight line.

This i

is the STRAIGHT BEAM DISTANCE AMPLITUDE CORRECTION curve.

It shall be plotted on the tester screen and on the DAC curve i

plot on the Calibration Record Sheet.

8.0 CALIBRATION OF THE SYSTEM TO PERFORM ULTRASONIC TESTING OF REACTOR PRESSURE 1

]

VESSEL WELDS 8.1 Basic Calibration Block (Figure 6) 5 8.1.1 Basic Calibration Blocks shall be utilized in accordance with the Tabic and drawing of Figure 6.

j 8.1.2 Basic Calibration Blocks shall be fabricated frrm reactor pres-sure vessel material, such as a nozzle dropout.

8.1.3 T' 3 Basic Calibration Block shall be c2ad in a nanner sinilar i

to the reactor pressure vessel. The cladding shall be 1/h +

1/8" thick.

j l

8.1.h The Basic Calibration Block shall receive heat treatment as re-j quired by the material specification type and grade.

8.1.5 Surface finish of the Basic Calibration Block shall be repre-

]

sentative of the pressure vessel.

8.1.6 The block shall not utilize areas containing ultrasonica.*.ly detectable defects producing indications larger than the back i

reflection.

8.1 7 Curved Blocks are required for surface curvatures less than 20" in diameter, i

8.2 Basic Calibration Reflector l

8.2.1 A side. drilled hole, parallti to the surface and perpendicular to the edge of the material is the Basic Calibration Ref]ector.

8.2.2 A square notch reflector vill be utilized in the calibration procedure.

i l

8.2.3 other reficctors may be incorporated but may not interfere with the pritrary reference.

8.3 Test for Instrument Amplitude Linearity (Figure 7A) 8.3.1 Place the angle beam transducer on the basic calibration block i

so that echoes from both the 1/2 T and 3/L T can be observed.

i NUCLEAR SERVICES CORPORATION

=_-.. -

... c..

SPECIAL PROCESS STANDARD

.?" - "

22 g

or d

j 8.3.1 (continued) l Adjust the transducer position and gain controls to obtain a l

2/1 amplitude ratio between them with the larger at.80% of full screen height.

Adjust the gain controls or the attenuator to vary the larger indication from 20% to 100% of full screen i

height in 10% increments, or 2 d'o stops. Read the indiention at each settiDg.

The sms11er echo must be 50% of the larger, within 5% of full screen height. Amplitude readings shall be read from a signal height meter or estimated to 1%.

t j

8.3.2 Amplitude control linearity is verified by placing the search unit on the basic calibration block so that the echo from the

]

1/2 T hole is peaked on the screen. The db attenuator controls shall be varied as shown belov and the echo amplitude must 1

increase and decrease accordingly.

If the tester is not equipped with a meter to measure signal amplitude the signal height must be estimated to the nearest 1% of full screen.

J Indication Change db Control Besultant Indication 4

80%

- 6 db 32 to h8%

80%

-12 16 to 2h%

l h0%

+6 6h to 96%

20%

+12 6h to 96%

i 8.h Exemination System Calibration General Conditions l

8.h.1 Calibration shall include the complete system.

Any chance in the components of the system shall be cause for recalibration.

i L

8.L.2 The original calibration must be performed on a basic versel j

calibration block.

Calibration checks may be performed on a calibration block simulator.

8.h.3 The temperature of the basic calibration block shall be sithin 25'F of the component temperature.

8.h.h Complete calibration shall be performed prior to the use of the cyctem in each inservice inspection.

8.h.5 Calibration verification shall be performed at the beginning of each day's testing, at the start and finish of each examina-tion, with any change in examination personnel, and at no greater than four hour intervals.

{

l 1

NUCLEAR SERVICES CORPORATION 1

6 8 6 =0.

SPECIAL PROCESS STANDARD F - " - "' " " '

j 7

or 22 e

3 I

i i

8.h.6 Calibration verification shall be performed by verifying the Distance Amplitude Curve.

If any point on the curve has changed in amplitude by more than 20% (2 db) all data a

i sheets since the last successful verification chall be marked void, a new calibration performed and recorded, and the voided examinations repeated.

e 6.h.7 If any indication on the DAC curve has moved more than 5% of j

the sweep division reading, correct the sweep range calibration and note the correction in the examination record.

I f.'e-cordable indications are noted on the data shects, those data l

sheets shall be voided, a new calibration performed and re-j corded, and the voided examinations repeated.

8.h.8 The calibration parameters (Figure 7B) are:

svecp range, l

test sensitivity, distance amplitude correction, position j

calibration with respect to the front of the cearch unit and l

the examination surface, calibration correction for planner reflectors at or near the material surface, team angle and j

beam spread.

l 8.5 Angle Beam Calibration 8.51 Angle Beam Sweep Calibraticn for metal path (Figure TC).

8.5 1.1 Using the 2" and h" reflectors on a h3bo IIW 2 block, adjust the sweep zero and range controls to show 2" and h" appropriately on the tester screen.

Record range meter readings.

)

8.5 1.2 Position the transducer for maximum first indication i

from the 1/h T side drilled holes.

Record rance i

meter reading.

Feasure actual metal path from the l

transducer index to the hole and compare with nereen i

indication and meter reading. Values must agree vithin 5%.

l 8.51.3 Repeat step b using the 3/h T hole. Trim range and delay controls if necessary to perform calibration.

(

8.5.1.h Repeat step b using the h/h T notch. Trim ranne and i

delay controls if necessary to perform calibration.

l 8.5.2 Angle Beam Testing Distance Amplitude Correction (Figure TD and 7E),

i I

e i

NUCLEAR SERVICES CORPORATION

)

SPECIAL PROCESS STANDARD P "~* ""

4 8

or PP l

i 8.5 2.1 Position the search unit for maximum response from j

the hole which Sives the Sreatest amplitude, u

l 8.5 2.2 With at least 20 db gain remaining available at the tester adjust the gain control to place the. indica-l tor of step A at 80% of screen height. Make the peak of the indication on the tester screen plot trim point on the calibration record sheet plot.

i 8.5 2.3 Repeat step 8.5 2.2 for the remaining two holes in the basic calibration block.

Connect the peak response points both on the tester screen and the DAC.

8.5.2.h Position the transducer for maximum amplitude indi-cation from the square notch on the opposite surface j

of the basic calibration block.

Mark the peak of the indication on the tester screen and on the DAC plot.

Consider the response of this reflector in evaluating surface reflectors.

l 8.5.2.5 Electronic Distan:e Amplitude Correction shall l

equalize the response of the basic calibration bicek l

to 50% of screen height over the range of the test.

8.5.3 Angle Beam Position Calibration (Figure 70) j 8.5 3 1 Position the Transducer for maximum response from the 1/h T hole in the basic calibration block. Met.sure and record on the Calibration Record Sheet the dis-tance from the front of the transducer to the cribe

^

line abo-the hole.

Alco record the depth of the 2

notch, i

8.5.3.2-Repeat step 8.5 3.1 for the remaining holes and the notch.

8.5.h Angic Beam Vertical Plane Beam Spread (Figure TH) 8.5.h.1 Position the transducer for maximum response from the 1/h T hole, with the tester set at twice the primary reference (DAC) sensitivity of step 11.h.6.

Move the transducer forward and backward from the point of J

maximum response until the response falls to the 50%

level as indicated by the DAC curve drawn on the screen. Record the maximum point on the distance movement to the 50% pointo in each direction no n a-I sured from the front of the transducer to the r.cr1be line above the hole.

NUCLEAR SERVICES CORPORATION

1, i

]

SPECIAL PROCESS STANDARD 2P" -"' "" '

9 or 22 i

8.5.h.2 Bepeat step 8.5.h.1 for the remaining holes.

l f

8.5.h.3 Prepare a full scale drawing of the beam profile by correcting common response points from each hole, J

J 8.6 Strai8ht Beam Test Calibration j

8.6.1 Straight Beam Sweep Range Calibration i

8.6.1.1 Adjust the range and delay controls of the instrument 3

to place the left edge of the maximized responses from the 1/h T and 3/h T side drilled holes at 20%

arid 60% of the hcrizontal scale, respectively, i

l 8.6.2 Distance Amplitude Correction

)

8.6.2.1 Position the transducer for the maximum response from the side drilled holl, which gives the highest j

amplitude.

8.6.2.2 With at least 20 db of gain remaining adjust the gain controls to provide an 80% of scale indication from the hole.

Mark the peak of the indication on the a

i tester screen and on the DAC plot in the Calibration ReJord.

4 8.6.2.3 obtain maximum ir.dications, and similarly plot the responses of the remaining side drilled holes.

8.6.2 h Where electronic distance amplitude correction is used, the response of all holes must be adjusted to 50% of screen height.

8.7 Transfer Methods 8.7.1 Transfer methods are not permitted.

90 CALIBRATION RECORD SHEET 91 Record required calibration information on Ultrasonic Calibration Test Record Sheets NSC-TS-026-6-2h and NSC-TS-027-6-7h.

9 1.1 Site 9 1.2 Date and Time 9.1.3 Examiners and Level NUCLEAR SERVICES CORPORATION u..

1 j

SPECIAL PROCESS STANDARD

,P"-E 10 0'

22 i

9 1. 14 Instrument, S/N and modules (if any) i t

910 Celibration Procedure and Test Block No.

9 1. (.

Examination Procedure i

j 917 Transducer Index and Beam Angle j

92 When the tester is provided with a range meter calibrated in micro-seconds, calculate and record, f

9 2.1 Two way sonic Velocity factor, developed from IIW-2 Test Block Data.

j 9 2.2 Transducer delay in microseconds, j

93 Record the reference sensitivity.

9 3.1 Record the response of the stability reference (IIV-2) at the i

reference sensitivity.

j 9.h Plot the DAC curve on a separate page.

95 Record angic beam vidth and position data.

/

96 Record pertinent instrument settings.

97 Record scanning and evaluation sensitivities.

4 98 The completed calibration record shall accompat.y the examination team during,the dayt inspection as a necessary reference.

It shall then l

be filed with other examination documentation; 10.0 STRIP CHART CALIBRATION RECORDS 10.1 The NORTEC 130 D tester used by Nuclear Services Corporation sha31 be used to generate a strip chart record of the amplitude and range of an ultrasonic examination. Test information chall be related directly to the basic calibration block response through Nuclear Services I

Corporation Procedure NUT-NC-3 10.1.1 Strip chart recordings shall be made of the calibration re-sponse of this reference reficetor used in generating the DAC curve plot, and these recordings shall become an attachment record sheet.

10.1.2 A strip chart recording shall be made of the stability re-ference reflector for comparison with Inter recordings made at e

s t

NUCLEAR SERVICES CORPORATION

d 1

i SPECIAL PROCESS STANDARD

/?"-" ~ ' " "" ' '

13 o'

??

l

}

l 10.1.2 (continued) t j

the time examinations are performed, to prove that no change in calibration took place in the interval.

j 10.1.3 Recordings of the basic reference reflectors response and/or the stability reference reflectors response shall be used in the evaluation of examination records.

j I

11.0 QUALITY ASSURANCE a

11.1 Calibration records shall be maintained in a field file in such condi-tion as to be readily available for audit.

.,1 l

11.2 It is the responsibility of the Nuclear Services Corporation Level III Examiner to enforce the requirements of this procedure.

J i

)

)

{

4 i

P 4

a i

i l

l l

l l

l i

NUCLEAR SERVICES CORPORATION

Page 12 of 22 NLT-NC-1E, llev.14 u

la MIN tst t Noti 2 go iVT l 1 0

t !

I r

L 4

IQ i

o LOCATION OF HOLE F ROM

~~

CONTACT SURFACE DETERMINED FROM THE TABLE BELOW BASIC CAllBRATI.ON HOLE 14 DES PARALLEL T.

OF DIAMETER *d WITHlH t 0.015 IN./ FT 1

t t Length of block deteemmed by the an$le of search unit and the vee path used T= Thickness of basse calibration block Isse table below)

- D = Depth of side 4relled hole (see table belowl d = Diameter of side 4 rilled hole (see table belowl i

  • Nominal production material thickness j

Nominal Production Basic Calibration Hole Hole M.nir.tum Hole i

Material Thickness (t) in.

Block Thickness (T), in.

Location Diamete, (d), in.

Ospth (D),in.

Up to I insl.

af, og g of,7 af,,

g of, Over i thru 2 l'/, or t

  • /. T

'4 18 /,

Over 2 thru 4 3 or t

'A T sj,,

g if, O.et 4 thru 6

$ or t

'47

'A l ' /,

Over 6 tt'ru 8 7 or i

'/. T

'/.

I'/

Over N thru 10 9 or t

'A T 8/.

l'h Over 10 t

'/. T see Note I l'4 4

I Nole 1 For cash increase in thitknew of 2 in or J fr.Belion thereof, lhe hole diameter shall mercase '/.. in.

N.ite 2 -l nr hiosk stics met 3 in. In thidncit tTs. lhe distante trum tl'c hole to the end ot'the block shall be 8)T min. to prevent coinckleni ref1cetions from the hole and the corner in the */. th scetath position. Diocks fabricated with a l'i-in. minimum diniension need not be mmlifici: if the corner and hele indications can be easily resolved.

i I

Figure 1 i

,e,-

~, - - -


.-n

.nw

Page 13 of 22 NUT-NC-1E Rev.h i

9' Si e

if MIN.

y y,

,o,.

N s

.g..

a FOR THICKNESS 1 INCH OR LESS PRIMARY REFERENCE RESPONSE l

~~ ~5ET AT 7EK Of FULL SCREEN jqy i

REFERENCE LEVEL g

1

"'20Y Or

~,'

REFERENCE LEVEL

  1. ,~~~~

L.

~~-

s,l.

i (NODE EXTRAPOLATED FPOM EURVE

, TYPICAL DISTANCE AMPLITUDE CORRECTION CURVE (ANGLC BCAM METHOD) cistett iN tecntHS or A woot. Fo9 Exont 64 o'yNoot i,

ly MIN.

m

^

-R gN r-I s

\\

s A

sd N YY FOR THICKNESS CVER I INCH 1

i l

PPIMARY REFERENCE RESPONSE

~~ ~ ~~5E T AT 75 % Of FULL SCREEN 1

g

,50*/ OF

,/,

r ERENCE LEVEL

\\

~~~~~~

I..

~~~

R.E.FERENCE LEVEL' ' '. ',

~-

~

<- - - - n

..i t

~-(---..

l NODE EXTR APOLATED FROM CURVE TYPICAL DISTANCE AMPLITUDE CCRRECTION CURVE l

(ANGLC BCAM MCTHOD)

Di$1ANC[ IN lignins Of A NODt. FO8L [AAMPLL I4 45 'dg-MOOC I

l f

F1 ure 2 6

PQge 14 of 22 NUT-NC-1E, Rev.h 9

l

.)____.

72, T

Q--

m.

i 7

AT l

3 ir

_o_..__

i

=

(ii.uis.

.6.

Figure 3 PRIMARY REFEF.ENCE RESPONSE N

.ET (T

DISTANCE

.B.

TYPICAL DISTANCC AMPLITUDE CORRECTION CURVE (STRAIGHT BEAM METHOD) l Figure b

~~

I

+

Page 15 of 22 3

l NUT.NC-1E.Bev.h I,

t i

4 1

i 1

2 I

\\

Q ~ ~~"" "'~

J 1

j

/

j j

/

.....n j

/

/

i

'/

i 9-

........i..

f 2

_. T

./

e, s-7-

j D,,

/

q I

/

/

4 7

' O#0 4 D I A J,

/

b.

/

I O

/.

Q I

l

!beQ g

.p l

ej i

1 j

/

Y V'

' ' ~

i

/

l

/

j...

%s

.. !. i..

.,i g.

l 9

2 p

1 i

I i

1 1

Figure 5 i

Typical Curved Basic Calibration Block i

.m..

v-

__~___..__,,,_,..-.,..,_....m_.m-..,

,,,_...._..,_,..___...,_.~.m.,_.

NUT-NC-1E Revik Pcge 16 of 22 t,,,.,.

N d

j 2"

~ [ 3" 1* LONS [ DIA FL AT EMD WILL NO I

2 % T DEEP T

N I

g h

N

-: 9 s

x*

y, x M/

T s

THROUGH CLAD

'7 THKKNESS 2 % T DEEP

{f ',,,,',

NTO THE B A SE WETAL g

y TN

\\

I 37 4

,p k';-92 fD I

A CLAD

{~

af',

4 33 DRILLED &

^

[ OR 6" MIN 4

R,E ED LES

\\

2%

3T OR 6" MIN

\\

SCRIBE LINE BASIC CAllBRATION HOLE WELD THICKNES S (T)_

BLOCK THlCKNESS Q)_

DIAMETER OVER I" THRU 2" l-1/2" OR T 1/ 8 ".

OVER 2" THRU 4" 3" OR T 3/16" OVER4"THRU 6" 5" OR T 1/4" OVER 6*THRU 8" 7" OR T 5A6" OVER 8"THRU 10" 9" OR T 3/8 "

OVER 10"

  • FOR EACH INCREASE IN THICKNESS OF 2" OR FRACTION THEREOF THE HOLE DIAMETER SHALL INCREASE 1/16'.'

FIG. 6 BASIC CALIBRATION BLOCK AS PER ASME II APPENDIX I FOR PRESSURE VESSEL WELDS ONLY

1 e

NUT-NC-1E,Rev Face 17 Of 29 i

5 l

i a

\\

10 " r $ENSif tvlTY t

i 80

)

e-e h

.)

<{'k U(C

]

40 4

c D

a e s 4

12 4 11\\6 8

~ PWTl0h

\\

~IOY s ' swl;t e R Av.E.

/

^

^

"4%

i T

s gypd PLANAR i

BEAM SPREAD

()

\\

v 1

i Figure 7A Test for Linearity Figure 7B Calibration Parameters I

DELAY D

I 3

RANGE g

{

1 DH. t..

I D3 l ? ut 5

a

=>

...e os f

4 IN LINE a

e REFLECTORS HOLES AND h MOVEC' lNTO NOTCHl:S WILL OEAM BE USED FOR ANGLE BEAM C ALIBR ATION g

Figure 7C Sweep Range Calibration 0-SENSITIVITY j

6-

'i A

ll C

'fl I

ll

)

  • I I

I I I l>

I 2

I LJ dL.Ll..L.,v1.

..g l

g 1

I b

~~

~

~~

IN LINE IN LINE HOLE HOLES AND REFLECTORS l

AND NOTCHES l

NOTCHES WILL DE ~ ~{TOBEAM WILT. OE USED FOR INTO Bi M USED FOR ANGLE ANGLE BE AM J

/

BEAM CAllBRATION C All8R AT10N C

.._..._...n._

Figure TD Ser.sitivity Adjustment Figure 7E DAC Generation

Puio AS.sf 22 NUT-NC-1E, Rev. 14 1

MFl n

(

l s

%)sM.

. _ h' 4.

's

~. s N

' O..

d Figure 7F Planar Surface Reflecter

. ' 'ifg

]

s.

s i

s g

N i

'i -

1.

't

~

.. ^.....,...'.L.l..., } '. g...

4.W.1.

_ U. _ J.. 2 _.. K. l.

A yl l

t l

._......erf l

1.,

. ri.e.r : n g'.,

i.

i

.; v; o c:

t t

ny,...

..r3 r., s. w

_. _.._..... _. %. g)/, hc w.-

p..

/ -

,-4.....>....._..

- _.. g, Figure 70 Position Calibration n

<g

,a s, 5,#

g o\\

.s 4s og V

223 4 d 64 6 6

s w'n -l l

\\

- dq t o. ?N N

/

Ni p q.s.

/

e

'w l

x 'v Figure 711 Beam Pp. cad tteasurement

-N lb Bev.h //fs 3

l-DELar 9 t.M f l

1

\\

'f L.

L.-

\\

8 6

+- T--"(l -

sit.v.r R LD No.Es w i. ' et, v%o 5 0,4 s r *.)' ',4 : JLA9 U

RE F'L EC T'A'.

I C#' 'I" AIIC N woito b

IN TO C F. A M Figure 8A Sweep Range Calibration

/

)

l

o.. I s S E.N3.l ivlT Y

\\

1' N

\\

0

)

[

i 6'

A i

l H '

41 l\\

4-:

g\\

l g\\

s i

.i

.I L..

.. __ / L _. > L J L f~ o e

a r,

e

.)

f

\\ ___'~1

. <7 l

b o

O Figure 8B Sensitivity Ce.libration f

/

f i

8 i

AN '

i

}

_,/.

'1.s.

I u,

t.._ ;

u

/

l g

_c

.. 3

"#.... O r.

m.

Page 20 of 22 NUT-NC-1 E, Bev. L ULTRASONIC CALIBRATION TEST RECORD s

Site:

Cal. No.:

Examiners:

Level:

Date:

Time:

Calib. Procedure:

Test Block S/N Examination Procedure :

Instruments & Modules:

TRANSDUCER DATA Mfg.:

Freq.:

Mat.:

Size:

S/N Mfg.:

Freq.-

Mat.:

Size:

S/N CALIBRATION DATA 1.0 IIW-2 Angle Beam Transducer Beam Angle:

Transducer Index Checked:

2.0 Sweep Range & Delay Setting from IIW-2 Block 2.1 Angle Beam Setting Using 2" and h" Radius Reflectors a.

2"=

us b.

L"=

ur 2.2 Straight Beam-Set using 1" block thickness us 2.3 Velocity =

2 in./ microsecond (ps) 2.1.b - 2.1.a 2.h Transducer Delay = (2.1.a) - 2"/(2.3) =

microsecond (us )

3.0 Instrurent Reference Sensitivity Data from Basic Calibration Block 3.1 A=pl.Lin.Chk.

20%

30%

LO%

50%

60%

70%

80%

100%

3.2 Amp 1. Control Lin. 76db

-12db 76db

+12db

~

3. 3 Primary Refereni:e Reflector:

Angle Beam us Straight Beam us.

3.L IIW-2 Bleck 1/8" DH Response: Angle Beam us Straight Beam i

us.

h.0 An-le Beam Data from Basic Cal. Block Side Drilled Holes 1/L T 1/2 m j3/h "

  • Planar h.1 Signal Amplitude (max.):

b.2 Distance "a"* and range at max. signal:

b.3 Distance "a"* and range at leading ray (50% nax. )

k.h Distance "a"* and range at trailing ray (50% max. )

~~

5.0 Instrument Settings et Reference Sensitivity

~

Angle Beam Straight bear 5.1 Gain 5.2 Attenuation 5.3 Svecp 5.L Delay 5.5 Fbrkers 5.6 Pulse Length 5.7 Damping 5.8 Beject 59 PRF 5.10 VIDEO o.0 Gain and/or Attenuation at Scanning Sensitivity 70 Gain and/or Attenuation at Evaluation Sensitivity

  • "a" Longitudinal distance from the line scribed above the hole to the transducer cace front.

Sheet 1 of

NUi-WC-1E, Rev. k TLTRASONTC CALTBRATTON TEST REL

.0 N

Site:

Cal. No.

Examiners:

i 4

Date:

Time:

Level:

Transducers S/N Instrument S/N,

n 1

Test Block S/N 4

?

i I

i i

i i

)

=

i i

i i

i I

a 1

i

~

i l

l NSC-TS-027-6-7h Sheet _ of 4

~-

n

+~-

.----e m

.,.--.-.r, w

e,

..m---

t Pasa 22 of 22

~

Record of Revisions NUT-NC-1E a

j 9

I 1

i k

1/10/75 Revision to 197h code l

I 3

3/1/7h Revision s

2 1/11/Th Revision 1

7/1/73 Revised _

0 Issued for Cor.rer.ts vfo7/7, To.

Date ROVi5 IOU I V l

ttSC-TS-010-7-71