ML20090K606
| ML20090K606 | |
| Person / Time | |
|---|---|
| Site: | Bellefonte |
| Issue date: | 05/08/1984 |
| From: | Mills L TENNESSEE VALLEY AUTHORITY |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| NCR-2496, NUDOCS 8405240272 | |
| Download: ML20090K606 (2) | |
Text
...
.e-j TENNESSEE VALLEY AUTHORITY CHATTANOOGA. TENNESSEE 37401 400 Chestnut Street Tower I May 8, 1984
/8 48*.8
~BLRD-50-438/84-01 BLRD-50-439/84-01 f
U.S. Nuclear Regulatory Commission Region II Attn: - Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303
Dear Mr. O'Reilly:
BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - FAILED G.E. TRIP BREAKERS
- BLRD-50-438/84-01, BLRD-50-439/84 SECOND INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector
- P. E. Fredrickson on December 14, 1983 in accordance with 10 CFR 50.55(e) as NCR 2496~. This was followed by our interim report dated January 11, 1984.. Enclosed is our second interim report. We expect to submit our next report by July 23, 1985.
If you have any questions, please get in touch with R. H. Shell at
- FTS 858-2688.
r l
Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager J-Nuolear Licensing Enclosure
. cc :
Mr.. Richard C. DeYoung, Director (Enclosure) l
. Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.
20555 i:
Records Center (Enclosure)
Institute of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 l
Atlanta, Georgia 30339 j.
$$0'$$oE0 O F FI CI,q, r o g s
1983-TVA 5OTH ANNIVERSARY Mk\\
An Equal Opportunity Employer
ENCLOSURE 3
BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 FAILED G.E. TRIP BREAKERS ik.-
,~
BLRD-50-438/84-01, BLRD-50-439/84-01 NCR 2496 10 CFR 50.55(e)
SECOND INTERIM REPORT Description of Deficiency Trip breakers 1NR-52-015-F and 016-G failed testing because they would not close. Some of the electrical contacts that function during the close stroke also appear to be burned. A contributing factor of the failure appears to be a lack of proper maintenance or storage.
~
Interim Progress TVA is pursuing resolution of this issue through the B&W Owners Group in coordination with General Electric. Both short-term technical resolutions for operating plants and long-term resolutions for all plants are being examined. TVA will submit a final report on this nonconformance when corrective action for this condition has been determined.
b
-, - -