i TENNESSEE VALLEY AUTHORITY 5"0 6 $est$ t M EEef YEwe P fl BLRD-50-438/8NM g A B *. 4 8May 15, 1984 BLRD-50-439/83-49 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - MASS OF HVAC SUPPORTS NOT INCLUDED IN FREQUENCY CALCULATIONS - BLRD-50-438/83-56, BLRD-50-439/83 SECOND INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector P. E. Fredrickson on October 20, 1983 in accordance with 10 CFR 50.55(e) as NCR BLN BLP 8336. This was followed by our interim report dated November 18, 1983 Below is our second interim report. We expect to submit our next report by February 5,1985.

TVA is still in the process of investigating the subject deficiency. A review of calculations for duct supports in safety-related systems is

. continuing. Of approximately 600 duct supports in the Reactor Building that have been reviewed, only two required field modifications.

If you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, j

TENNESSEE VALLEY AUTHORITY h$

hL.M. Mills, Manager I

Nuclear Licensing cc:

Mr. Richard C. DeYoung, Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Records Center Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 8405240042 840515 DR ADOCK 05000 oyylCIAL col}Yj 1983-TVA SOTH ANNIVERSARY g

An Equal Opportunity Employer

- _ _ _ - _ _ _ _ _ _ _ _ _