Preliminary AO-50-219/75-05:on 750306,containment Spray Pump 51A Failed to Start When Subjected to Simulated Signals.Caused by Breaker Trip Bar Failing to Reset After Previous Breaker Trip.Trip Bar Bushings Cleaned
ML20090D824
Person / Time
Site: Oyster Creek
Issue date: 03/06/1975
From: Carroll J
JERSEY CENTRAL POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
AO-50-219-75-05, AO-50-219-75-5, NUDOCS 8303020427
Download: ML20090D824 (3)


Text

/"3 V

~e

    • .g n, g1

,.,9... --

To:

James P. O'Reilly s f, Directorate of Regulatory Operations l ZI g, if Region I 631 Park Avenue

l

,,', l King of Prussia, Pennsylvania 19406

-, f . '.x

.i,4 n; g 7,,

From:

Jersey Central Power 6 Light Company Oyster Creek Nuclear Generating Station Docket #50-219 Forked River, New Jersey 08731 Subject Abnormal Occurrence Report No. 50-219/75/5 incfo1Jowing$sapreliminaryreportbeingsubmitted in compliance with the Technical Specifications, paragraph 6.6.2.

Preliminary Approval:

/

Q/w Mn.+h.s// 7.f J'. T. Carroll, Jr. /

Date

/

cc: Mr. A. Giambusso 2[3d 8303020427 750306 PDR ADOCK 05000219 8

PDR

?

O Da(Q'/

Init ial Telephone tc of Report luto:

3/6/75 Occurrence:

3/6/75 Initial Written Time of Report Date:

3/6/75 Occurrence:

0950 OYSTER CREEK NUCLEAR GENERATING STATION FORKED RIVER, FEW JERSEY 08731 Abnormal Occurrence Report No. 50-219/75/5 IDENTIFICATION Failure of containment spray pump 51A to start when called 0F OCCURRENCE:

upon to do so.

This event is considered to be an abnormal occurrence as defined in the Technical Specifications, paragraph 1.15D.

CONDITIONS PRIOR X Steady State Power Routine Shutdown TO OCCURRENCE:

Hot Standby Operation Cold Shutdown Load Changes During Refueling Shutdown Routine Power Operation Routine Startun Other (Specify)

Operation Poucr:

n: etar,1 ^; :".?L Electric, 665 Mh'c 4

Flou:

Recirculation, 615.8 X 10 8PM Feed, 7.67 X 10 lb/hr Stack Gas:

29,600,uci/sec DESCRIPTION OF It was observed on Thursday, March 6,1975, at 0950, during OCCURRENCE:

the monthly surveillance test of the containment spray system that containment spray pump 51A failed to start in the automatic mode when subjected to simulated low-low reactor water Icyc1 and high drywell pressure signals.

It was observed that the " pump failure" alarm initiated approximately 64 seconds after the start signal was applied. An operability check was performed on the redundant System 1 Containment Spray Pump 518.

Containment Spray Pump 51A was then removed from scr. ice for-investigative analysis as to the cause of the failure.

l l

t

i O

O Abnomal Occurrence Pace 2 Report N,o. 50-219/75/5 APPAIENT CAUSE Design Procedure 4

0F OCCURRENCE:

!fanufacture Unusual Service Condition Installation /

Inc. Environmental Construction.

Component Failure Operator other (Specify)

~

The cause of the occurrence is presently under investigation.

l ANALYSIS OF The only significance associated with the failure of 51A to OCCURRENCE:

start is in a 2oss of system redundancy. Ilad conditions 4

arisen requiring containment spray, pump 51C would have started i

nutomatically and performed the containment heat removal function.

1 4

In addition, the manually initiated backup pump.51B.for System I was checked to be operabic and could have been initiated.

The containment heat removal function can be adequately supplied hv a sinolo conteinnont spray pump.

i CORRECTIVE The failure monitor installed as the result of a similar ACTION:

occurrence on October 21, 1974 functioned during this event nnd the information obtained is under analysis in an effort to i g determine the cause.

FAILURE liATA:

Previous abnormal occurrences involving the containment spray system:

4 1.

Abnormal Occurrence Report No. 50-219/75/3 2.

Abnormal Occurrence Report No. 50-219/74/55 3.

Abnormal Occurrence Report No. 50-219/73/12 4.

Abnormal Occurrence Report No. 50-219/72/12 i

j Prepared by: