Text
Initial T'elephone m D;ts cf R:p;;rt Date:
Ohcr 16,1975 Occurrence: October 15, 1975 y
Initial Tritten Time of R: port Date:
October 16, 1975 Occurrence:
2325 OYSTER CREEK NUCLEAR GENERATING STATION FORKED RIVER, NEW JERSEY 08731 Abnormal Occurrence Report No. 50-219/75/28 IDENTIFICATION OF OCCURRENCE:
Failure of solenoid for valve V-28-24 (Standby Gas Treatment Orifice Valve) which subsequently rendered Standby Gas Treatment System #1 inoperabic.
This event is considered to be an Abnorrtl Occurrence as defined in the Technical Specifications, para-grrph 1.15D.
CONDITIONS PRIOR TO OCCURRENCE:
X Steady State Power Routine Shutdown Operation llot Standby Load Changes During
~ Cold Shutdown Routine Power Operation Refueling Shutdown Other (Specify)
Routine Startup Operation The major plant parameters at the time of the event were as follows:
Power:
Core 700 FMt Electric 191Mlje Flow:
Recire. 6.1x1g gpm Feed. 2.19x10 lb/hr.
Stack Gas:
3300 pei/sec.
DESCRIPTION OF OCCURRENCE:
On Wednesday, October 15, 1975 at approximately 2325 the " Emergency Exhaust System EF-1-8 Fan Trip" alarm was received in the Control Room. Subsequently it was found that the control circuit fuse for fan EF-1-8 was blown.
APPARENT CAUSE OF OCCUlUGNCE:
Design Procedure Manu facture Unusual Service Condition Installation /
Inc. Environmental Construction X Component Failure Operator Other (Specify) i l
Failure of the air solenoid valve coil for air operated valve V-28-24 is the cause of the abnormal oc6urrence.
8302240060 751024 PDR ADOCK 05000219 S
Abnsit.a1 Occurrsnce
(
Page 2 R;part No. 50-219/7S/28( )
/
ANALYSIS OF OCCURRENCE:
Since the Standby Gas Treatment System is a redundant system and full required processing capability is availabic through the other system (System #2) the only safety significance of this event is the loss of Standby Gas Treatment System redundancy.
CORRECTIVE ACTION:
Initial corrective action was to replace the. defective solenoid coil with a new one.
FAILURE DATA:
Basic Valve Data:
I Manufacturer:
Skinner Electric Valve Div.
New Britain, Conn.
Valve No.:
V53ADB2100 Voltage:
11S Volts
{
Power:
10 Watts Design Pressure:
100 psig J
PREPARED BY:
f4 5-"m Date: - /0/67
/
,g/
T. Quir'tenz Asso, ngineer 2
l I
i
.m
"/M4. 8 MM*
((
r TO:
James P.,0'Reilly Directorate of Regulatory Operations Region I
~
631 Park Avenue x-King of Prussia, Pennsylvania 19A h[j;..pf, q
3 b-OGYd9W '..=
T a
g.
- 0. ;'
3 L
.s 4
eXTJT't -
m FROM:
Jersey Central Power G Light Company-Oyster Creek Nuclear Generating Station Docket #50-219 Forked River, New Jersey 08731
SUBJECT:
Abnormal Occurrence Report No. 50-219/75/ 28 The following is a preliminary report being submitted in compliance with the Technical Specifications, paragraph 6.6.2.
Prc1' inary Approval:
G
_ _ the tobhbf w,
J.
T.' Carroll, J Date CC:
Mr. A. Ciambusso Sb W
'I