ML20087P757

From kanterella
Jump to navigation Jump to search
Interim Deficiency Repts 84-01 & 84-03 Re Failure of Pacific Air Products Co (Papco) Linear Torque Converters. Initially Reported on 840228.PAPCO Will Publish Final Rept on Interim Lubrication Procedure by 840417
ML20087P757
Person / Time
Site: Byron, Braidwood, 05000000
Issue date: 03/28/1984
From: Tramm T
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
8298N, 84-01, 84-03, 84-1, 84-3, NUDOCS 8404090345
Download: ML20087P757 (2)


Text

'

d O/M 8 A

C>mmonwealth Edison I

I one First Nabon11 PITza, Chicago. Ilknots l Address Reply to. Post Office Box 767 Chicago, Ilknois 60690 March 28, 1984 Mr. James G. Keppler Regional Administrator U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Byron Generating Station Units 1 and 2 Braidwood Generating Station Units 1 and 2 Pacific Air Products Linear Torque Conveet e Sr -456 s 50-457 NRC Docket Nos. 50-454, 50-455, s

Dear Mr. Keppler:

On February 28, 1984 Commonwealth Edsion Company notified tir.

Robert Lerch of your office of a deficiency reportable pursuant to 1G CFR 50.55(e) regarding the failure of linear torque converters in HVAC damper actuators at Byron Station during flow testing.

This deficincy pertains to equipment being installed at both the Byron and Braidwood Stations.

For NRC tracking purposes this report is numbered 84-01 for Byron and 84-03 for Braidwood.

This letter provides an interim report to satisfy the 30-day reporting requirement of the regulations.

Description of Deficiency During flow testing at Byron Station, linear torque converters failed OVC94Y, and OVC199Y.

The failure on safety related dampers OVC04Y, occured because of excessive wear of the brass shaft guides on the input The linear torque converter is a mechanical device and output shafts.

that converts the linear (push-pull) motion of an ITT electro-hydraulic actuator into rotary motion for damper operation.

The three linear torque converters sent back to Pacific Air Products Company (PAPCo) for analysis.

Three replacements were also furnished by PAPCo.

Preliminary analysis by PAPCo indicates that side loading of the linear torque converter by the rack portion of the rack-and-pinion gear is responsible for the bushing wear.

Preliminary evaluation by PAPCo indicates that lubrication of the brass shaft guide bushings corrects bushing wear.

Analysis of Safety Implications The linear torque converter failure occured prior to pre-operational testing of the control room ventilation system.

Bushing wear appears to be a generic problem as it has happened elsewhere in the utility industry (Edgewater Project, fossil plant, Wisconsin Power and Light).

Byron Station has 165 damper-actuator units (138 safety-related units) and Braidwood Station has 157 damper-actuator units (138 safety-related units) supplied by PAPCo.

Failure of a linear torque converter during plant operation would cause the damper to fail-as-is.

Presently, all safety-related dampers are designed to fail-open or fail-close (fail-safe position).

8404090345 840328 MAR 3 0 1984 PDR ADOCK 05000454 S

PDR l}Uf i,

~

I-FX 1

J. G. Keppler March 28, 1984 Dampers that fail-as-is would not allow proper isolation or modulation operation.

This.may be important in certain applications such as:

(1) -Switch'ing from control room ventilation train A to train B because of a problem with train A.

(2) ' Isolating portions of the non-accessible exhaust areas of the auxiliary building.

(3)

Maintaining temperature contrcl in control room boundary.

Corrective Action Pacific Air Products Company has submitted a preliminary report of

.their findings-along with an interim lubrication procedure.

PAPCo will publish the final report by April 17, 1984.

Based on PAPCo's preliminary recommendations, Commonwealth Edison is returning linear torque converters to PAPCo for refurbishment on a weekly basis.

Refurbishment includes lubrication of moving parts, shaft polishing, and replacing brass shaft guide bushings with an-alternate material that PAPCo has shown by analysis to meet IEEE 382-1980 standards for cyclic wear.

CECO anticipates that this program of refurbishment will be completed before fuel loading at Byron Station.

Based on the above information, and the fact that PAPCo's final report is not complete, a final response will be forthcoming in sixty days.

Please address any questions regarding this matter to this office.

Very truly yours, f. f M '^

~

T. R.

Tramm Nuclear Licensing Administrator 1m-cc:l Director of-Inspection and Enforcement Byron Resident Inspector Braidwood Resident Inspector 8298N