()ccu a & Cenfr,/
oa - nc.
Cp&L Carolina Power & Light Company SERIAL: NLS-84-138
- MAR 3 01984 Mr. James' P. O'Reilly, Regional' Administrator
- United States Nuclear Regulatory Commission
. Suite 2900
- 101 Marietta Street, NW Atlanta, GA 30303 H. B. ROBINSON STEAM ELECTRIC PLANT, UNIT No. 2 DOCKET NO. 50-261/ LICENSE NO. DPR-23 RESPONSE TO IEB 83-08
Dear Mr. O'Reilly:
SUMMARY
In the Inspection and Enforcement Bulletin (IEB) 83-08, NRC requested that
- Carolina Power & Light Company (CP&L) provide information pertaining to operation of circuit breakers with un.:ervoltage trip attachments (WTAs) used in' safety related applications other than as reactor trip breakers (RTBs) at
/
the H. B. Robinson Steam Electric Plant Unit No. 2 (HBR2). Carolina Power &
Light. Company has reviewed this Bulletin and provides the following response.
, BACKGROUND,
^
Issued December. 28, 1983, IEB B3-08 required that CP&L identify safety related
. applications of the breakers cnd the systems in which they are used; review their design, testing, and maintenance adequacy in light of their operating experience and information in IEB 83-08; and evaluate the need for corrective actions.
- DTSCUSSION J
'The safety related breakers other than the RTBs used at HBR2 are the breakers on Emergency Buses El and E2 for safety-related pumps and fans, and the molded
- breakers on Motor Control. Center MCC-5, 6, 9, and 10 for valves of safety related systems.- Emergency buses El and E2 use external undervoltage relays which are not a part of the breakers, and some of the breakers on MCC-5, 6, 9 and 10 have encased'undervoltage relays. These relays are not similar to the WTAs described in 'IEB 83-01 and 83-04 and are not considered within the scope of'83-08.
It should be noted that these undervoltage relays have not had reliability problems.
The non-safety.related Dedicated Shutdown (DS) System contains DS-416 and DS-532 breakers which have WTAs. The design criteria for these breakers do
.not take credit for their automatic action, and HBR2 procedures require that Carolina Power
. they are verified open prior to energizing. the DS system bus.
& Light Company is avare that other -plants are modifying DS-416 WTAs used for RTBs; and e.lthough these breakers are used only in a non-safety related system at ' HBR2, CP&L has ordered replacement WTAs for them. -
g 8404030357 840330
-lDRADOCK 05000261-PDR
=
e:
JJames P. d'Reilly MAR 3 01984 CONCLUSION Carolina Power & Light Company has determined. that circuit breakers with UVTAs as described 'in IEB 83-01 and 83-04 are not used in safety. related systems
- other than as RTBs at HBR2. Therefore, other actions required by IEB 83-08
.are not applicable. This' response provides the report of CP&L's actions as
- required in the Bulletin..
- As requested, CP&L estimates the staff time required to prepare this response to be'100 hours0.00116 days <br />0.0278 hours <br />1.653439e-4 weeks <br />3.805e-5 months <br />.
If you have any questions concerning this response, please contact a member of our Nuclear Licensing Unit staff.
I Yours very ly, n
/
A. B. Cutter, Vice President s
Nuclear Engineering & Licensing CGL/pgp.(9767CGL).
l cc:
Mr. J. P.~.0'Reilly '(NRC-RII)
Mr. G. Requa (NRC)
~
Mr. Steve Weise (NRC-HBR)
A..B. Cutter, having been first duly sworn, did depose and say that the information contained herein is true and correct.to the best of his information, knowledge and belief; and the sources of his information are o """"81,,
officers,: employees, contractors, and. agents of Carolina Power & Light s
4 p
Company.-