__

11:' _ W4.

i uThorras J. Martin Public Service Electric and Gas Company 80 Park Plaza Newark, N.J. 07101 201/4304316

- Vice PresWent '

Engineering and Construction February 24, 1984 Dr. Thomas E.

Murley, Administrator U. S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region I

'631 Park Avenue

' King of Prussia,_ Pennsylvania 19406

Dear Dr. Murley:

JCONSTRUCTION DEFICIENCY GE TYPE AKR-30 CIRCUIT BREAKERS HOPE CREEK GENERATING STATION On December 23, 1983, a verbal report was made to Region I, Office'of Inspection and Enforcement representative, Mr. W.

Cook, advising of a potentially significant construction deficiency concerning the failure of several General Electric AKR-30 circuit breakers to operate properly.

On January 18, 1984,'an interim report was sent to your office. 'The following supplemental information is provided in accordance with 10CFR50.55(e).

During on-site rework of the subject AKR-30 circuit breakers, performed under the guidance of General Electric representatives, additional fabrication deficiencies in the breakers were identified, including:

1.

Loose buffer assembly hardware 2.

Short motor spacers 3.

Broken solder joints 4.

Defective spring charging motor b;:

5.

Broken driving pawl shear pin l4 6.

Improperly installed cut off switch plate K.

7.

Cut-off and closing circuit switches becoming loose in

(

cperation v

W

' 9403210118 840224 DR ADOCK 05 g

fi 6

f.i cs Q% ~

{;

Dr.:T.

E.

Murley-2 2/24/84 Consequently, General Electric has agreed tu) ' completely reinspect all~ Hope. Creek AKR-30 circuit breakers in accordance with detailed

!. inspection procedures reviewed by Public Service and our Architect /

Sngineer, Bechtel-Power Corporation.

We'have also instructed'Bechtel to press General Electric to identify the cause of the breakdown in their quality program that-permitted these_ fabrication deficiencies.to leave their shop.

-- An additional interim report will be provided by May 14, 1984, if

.the final' report is not available' prior to that date.

Very truly yours, l

/

/

4 cc:

Office of Inspection and Enforcement Division of Reactor Construction Inspection F

Washington, D.

C.

20555 h

NRC Resident Inspector - Hope Creek P. 0. Box 241 Hancocks: Bridge, NJ 08038 i'L l.

Records Center-

[-

Institute of Nuclear Power Operations

[

.1100~ Circle-75 Parkway, Suite 1500 Atlanta, GA 30339 k'

]