ML20087H463

From kanterella
Jump to navigation Jump to search
First Interim Deficiency Rept Re Incorrect Insulation Weights for Intake Pumping Station Piping.Initially Reported on 840221.Util Will Perform Document Insulation Weight Calculations for ERCW Sys
ML20087H463
Person / Time
Site: Bellefonte  
Issue date: 03/14/1984
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
NUDOCS 8403210042
Download: ML20087H463 (2)


Text

.

kv.; a

?/

TENNESSEE; VALLEY AUTHORITY CHATTANOOGA. TENNE'SSEE 37401 400 Chestnut Street Tower II 19 n 9 4ch 14,1984 u.

BLRD-50-438/84-21 BLRD-50-439/84-20 U.S. Nuclear Regulatory Connaission Region.II Attn:

Mr. James P.' O'Reilly,. Regional Administrator 101 Marietta Street,.NW, Suite 2900 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - INCORRECT INSULATION WElGHTS FOR

. INTAKE PUMPING STATION PIPING - BLRD-50-438/84-21, BLRD-50-439/84 FIRST INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector Ross Butcher on February 21, 1984 in accordance with 10 CFR 50 55(e) as NCR BLN BLP 8405. Enclosed is our first interim report.

If 'you have any questions, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear-Regulatory Commission Washington, D.C.

20555

~ Records Center (Enclosure)

Institute.of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500-Atlanta, Georgia 30339 i'

i i

8403210042 840314 PDR ADOCK 05000438 OWICIAL COPY l

S PDR Zd27

?

e 3 1983-TVA SOTH ANNIVERSARY I

An Equal Opportunity Employer

o

~

,1, EN6uuSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 INCORRECT INSULATION WEIGHTS FOR INTAKE PUMPING STATION PIPING BLRD-50-438/hil-21, BLRD-50-439/84-20 E

NCR BLN BLP 8405 10 CFR 50.55(e)

FIRST INTERIM REPORT t

Description of Deficiency 9

During a review of the applicable _ insulation and modes analysis data for the essential raw cooling water (ERCW) system in the intake pumping station (IPS), it was determined that certain insulation weights were in error. Further invest.tgation revealed that documented

. design calculations for determining the actual insulation weights for some pipe sizes did not exist.

Interim Progress TVA will perform and document insulation weight calculations for the ERCW system in the IPS and issue revised insulation and mode analysis data and piping analysis. This work will be.done under tragineering change notice 2919.

_