Rev 19 to Station Procedure OP 2323A, Turbine
ML20087B285
Person / Time
Site: Millstone 
(OP-2323A)
Issue date: 05/23/1995
From: Ferguson B
NORTHEAST NUCLEAR ENERGY CO.
To:
Shared Package
ML20087B268 List:
References
NUDOCS 9508070389
Download: ML20087B285 (5)


Text

- _ -__ __ __..-_-

l

~

STATION PROCEDURE COVER SHEET 1.

IDENTIFICATION Number:

OP 2323A Rev. _12

Title:

TURBINE Prepared By:

B. Ferguson 2.

REVIEW l have reviewed the above procedure and have found it to be satisfactory.

SIGNATURE /EATE TITLE SIGNATURE /DATE TITLE p

DEPARTMENT HEAD V(

/

PWG M

fM SYSTEM ENG y'u/f/414I IND REVIEW

/

/

3.

SPECIFIC UNREVIEWED SAFETY OUESTION EVALUATION REQUIRED:

Modifies intent of procedure and changes operation h]

of systems as described in design documents.

YES [ ]

N (if yes, perform written USO determination and Safety Evaluation, and contact Manager, Safety Analysis Branch to determine need for Integrated Safety Evaluation.)

ENVIRONMENTAL REVIEW REQUIRED (Adverse environmentalimpact)

YES [ ]

NO

]

4.

SPECIFIC SAFETY EVALUATION REQUIRED Affects response of safety systems, performance of systems which may have been credited in the safety analysis or non-credited systems which may indirectly affect safety system response.

YES [ ]

N (if yes, coordinate Safety Evaluations and contact Manager, Safety Analysis Branch to determine need for Integrated Safety Evaluation.)

5.

INTEGRATED SAFETY EVALUATION REQUIRED YES [ ]

NOk 6.

BIENNIAL REVIEW This revision satisfies biennial review requirements.

YES [ ]

NO 7.

PROCEDURE REQUIRES PORC/SORC REVIEW (In addition to review, items with a YES response must be documented in the PORC/SORC meeting minutes.)

YES NO[]

8.

PORC/SORC APPROVAL PORC/SORG Meeting Number 2 / 7 '

9.

APPROVAL ANDIMPLEMENT TION The attgched pr cecjure is hereby approved, and effective on the date belpw:

7 7) L S/26/ff Sr.,VfCE PRESIDENT /p! RECTOR - UNIT / SERVICES EFFECTIVE DATE SF301/14/s/DBM/93-53/1of1 hhR D

Koo 6

P

  • i 1

OP 2323A Page1 Rev.19 UNIT 2 TURBINE Page No.

Eff. Rev.

1 - 30 19 l

W

-u*

OP 2323A Page 2 Rev.19 TABIR OF CONTENTS PROCEDURE SECTION SECTION TITIE PAGE NO.

5.1 Preparing for Turbine Startup.......................

7 5.2 Placing Wrbine Lube Oil System in Service and Placing Wrbine on Turning Gear..........................

8 5.3 Low Pressure Warming...........................

9 5.4 Turbine Shell Warming..........................

10 5.5

%rbine Chest Warming.........................

13 5.6 Turbine Startup to 1,800 rpm.....................

15 5.7 Load Set Operation.............................

19 5.8 Turbine Shutdown..............................

20 5.9 Erning Gear Operation.........................

22

(

-)

1*

OP 2323A Page 20 Rev.19 5.8 Turbine Shutdown p.-.-.-.-.-.-.-.-.-.-.-.5 CAUTION e

e 1

Turbine shutdown must be accomplished as expeditiously as possible to avoid unnecessary cooling of low pressure turbine rotor wheels while 8

8 L.

perating at low steam flows..-.-.-.-.-.-.-.-.-.-.J o

5.8.1 Refer To Section 5.9 and VERIFY turning gear aligned for automatic operation.

5.8.2 E the turbine will not be restarted within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, PERFORM the l

following:

5.8.2.1 Prior to turbine trip, VERIFY 3 out of 4 RPS linear drawer level I bistables are reset.

5.8.2.2 To prevent FRV bypass valve motion, PRESS and HOLD both FRV downcomer reset and ramp stop buttons.

5.8.2.3 PRESS red " TRIP" button.

5.S.2.4 OPEN 2-FV-1 as necessary to raise running EHC pump amps to between 45 and 55 amps. (unloaded amps are between 35 and 40 amps) 5.8.3 E the turbine will be restarted within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, PRESS " SPEED SET RPM, CLOSE VALVES" button and OBSERVE light lit.

5.8.4 SET turbine bearing oil temperature controller, TIC-7209, to 85*E 5.8.5 Refer To OP 2324C," Generator Hydrogen System and Carbon Dioxide Purge" and SHIFT hydrogen purity analyzer to standstill operation.

p.-.-.-.

.-.-.5 e

CAUTION e

Following turbine shutdown, bearing oil flow must be maintained L. -. -. -.

. gardless of turning gear operation...-.

.J e

for 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after shutdown re e

5.8.6 WHEN turbine rotor stops, PERFORM the following:

5.8.6.1 Refer To Section 5.9 and VERIFY proper turning gear engagement.

5.8.6.2 STOP " MOTOR SUCT PP, P-61" and PLACE switch in

" PULL TO LOCK" (C-07).

5.8.6.3 START "TURB BRG LIFT PP" "A'" (C-07).

OP 2323A Page 21 e

Rev.19 5.8.7 IE turbine overhaul is to be performed while shutdown, Refer To SP26511," Emergency Bearing Oil Pump Surveillances," and PERFORM test.

5.8.8 When a minimum of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> on the turning gear have elapsed and it is desired to secure the turbine lube oil system, PERFORM the following:

5.8.8.1 PLACE " TURN GEAR MTR, L-40" switch in " PULL TO LOCK"(C-07).

5.8.8.2 PLACE all bearing lift pump switches in " PULL TO LOCK" (C-07).

5.8.8.3 OPEN and RACK OUT emergency bearing oil pump breaker, D0305.

5.8.8.4 VERIFY " MOTOR SUCT PP, P-61" switch in " PULL TO LOCK"(C-07).

5.8.8.5 PLACE " TURN GEAR OIL PP, P-62" switch in " PULL TO LOCK" (C-07).

2