ML20086U245

From kanterella
Jump to navigation Jump to search
Applicant Exhibit A-82,consisting of 3/4.8 Re Electric Power Sys & 3/4.8.1 Re AC Sources
ML20086U245
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 06/01/1995
From:
GEORGIA POWER CO.
To:
References
OLA-3-A-082, OLA-3-A-82, NUDOCS 9508040013
Download: ML20086U245 (9)


Text

[

yucgnEjutATonycouu:ssion M

g M e W ' ' * " ? ' otr uEs.ref-M A$ css //g 4-00CKETED

"""*"o'4 Jah USNRC stan -

tocuriaco r

3/4.8 ELECTRICAL POWER SYSTEMS Appi m t.

V RECEIVED

/

Interveact-

_ REJECTED

~

L 3/4.8.1 A.C. 55BitCW.14 A10:21 conroce _.

Cor' tractor.

~

OWTING DATE A 91" OFFICE OF SECPETARY W

IWitaen Ju4'#

LIMITING.CONdiNid[0PERAY!UN T

l 3.8.1.1 As a minisuL, the following A.C. electrical power sources shall be OPERA 8LE:

Two physically independent circuits between the offsite transmission a.

network and the onsite Class 1E Distribution Systes, and b.

Two separate and independent diesel generators, each with:

1)

A day tank containing a minimum volume of 650 gallons of fuel (52% of instrument span) (LI-9018, LI-9019),

2)

A separate Fuel Storage System containing a minimum volume of 68,000 gallons of fuel (76% of instrument span) (LI 9024, LI-9025),and 3)

A separate fuel transfer pump.

APPLICA81LITY: MODES 1, 2, 3, and 4.

ACTION:

With one offsite circuit of the above-required A.C. electrical powr a.

sources inoperable, demonstrate the OPERA 81LITY of the remaining A.C.

i sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.

If either diesel generator has not been successfully tested within the past 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, 1

demonstrate its OPERASILITY by performing Surveillance Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 for each such diesel generator, l

1 separately. within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> unless the diesel generator is already operating.

Restore the offsite circuit to OPEAABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STAN08Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

b.

With either diesel generator inoperable, demonstrate the OPERABILITY of the above required A.C. offsite sources by performing Surveillance Requirement 4.8.1.1.1.a within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter.

If the diesel generator became inoperable due to any cause other than preplanned preventive maintenance or testing, demonstrate the OPERABILITY of the remaining 0PERA8LE diesel generator by perform-ing Survel11ance Requirmn s 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> *f.

Restore the inoperable diesel generator to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least NOT ~. Ah0$Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTOOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

"This test is required to be completed regardless of when the inoperable tilesel generator is restored to OPERA 8ILITY.

)

l iThe diesel shall not be rendered inoperable by activities performed to

{

suppoit testing pursuant to the ACTMN 5tatement (e.g., an air roll).

1 V0GTLE UNITS - 1 & 2 3/4 8-1 9508040013 950601 PDR ADOCK 05000424 g

PDR

Est ~.

'l 4 '3 Md.4 l

I ELEC1R! CAL POWER'5YSTEMS

' LIMITING CONDITION FOR OPERATION ACTION (Continued)

I c.

With one offsite circuit and one diesel generator of the above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. offsite source by performing Surveillance Re-quirement 4.8.1.1.1.s within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter, and, if the diesel generator became inoperable due to any cause other than preplanned preventative maintenance or testing, demon-strate the OPERABILITY of the remaining OPERABLE diesel generator by i

performing Surveillance Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 within8gours",unlesstheOPERABLEdieselgeneratorisalready operating.

Restore at least one of th. inoperable sources to OPERABLE status within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> or be.in at least NOT STAND 8) within the next-6 hours and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.. Restore the other A.C. power source (offsite circuit or diesel generatar) to OPERA 8LE status in accordance with the provisions of 3.8.1.1, ACTION Statement a or b, as appropriate,~ with the time requirement of that ACTION Statement based on the time of initial loss of the remaining inoperable A.C. power source. A successful test of diesel generator OPERA 81LITY per Surveillance Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 performed under the ACTION Statement for an OPERABLE diesel generator or a restored to OPERA 8LE diesel generator satisfies the diesel generator test requirement of ACTION Statement a or b.

d.

With one diesel generator inoperable in addition to ACTI0N b. or c.

above, verify that:

1.

All required systems, subsystems, trains, components, and devices that depend on the remaining OPERA 8LE diesel generator as aL source of emergency power are also OPERABLE, and 2.

When in MODE 1, 2, or 3, the steam-driven auxiliary feedwater pump is OPERA 8tE.

If these conditions are not satisfied within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> be n. e least HOT STAN08Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

With two of the above required offsite A.C. circuits inoperable, demon-e.

strate the OPERA 8ILITY of two diesel generators separately by perform-IngtherequirpentsofSpecification4.8.1.1.2.a.4and4.8.1.1.2.a.5 j

within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />, unless the diesel generators are already operating; restore at least one of the inoperable offsite sources to OPERA 8LE status within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or be in at least HOT STAND 8Y within the'next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />. Following restoration of one offsite source, follow ACTION l

Statement a with the time requirement of that-ACTION Statement based l

  • This test i required to be completed regardless of when the inoperable i

EDG is restored to 0PERABILITY.

t

  1. The diesel shall not be rendered inoperable by activities performed to i

support testing pursuant to the ACTION Statement (e.g., an air roll).

l V0GTLE UNITS - 1 & 2 3/4 8 2 i

~

- ~ _ -. - -

t

p[
w ElLCTRICAL POWER SYSTEMS J.

{

LIMITING CONDITION F08 OPERAfl0N ACTION (Continued)

\\

on the time of the initial loss of the. remaining inoperable offsite

~

a.c. circuit. A successful test (s) of diesel OPERA 81LITY. per Surveil-1ance Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 performed under this ACTION Statement for the OPERA 8LE diesels satisfies the diesel generator test requirement for ACTION Statement a.

f.

With two of-the above required diesel generators inoperable, demonstrate l

the OPERA 81LITY of two offsite A.C.. circuits by performing the require-ments of Specification 4.8.1.1.1.a. within l' hour and at least once per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> thereafter; restore at least one of the inoperable diesel i

generators to OPERA 8LE status within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> or be in at least NOT STAN08Y within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />. Following restoration of one diesel generator unit, follow ACTION Statement b with the time requirement of that ACTION Statement based on the time of. Initial loss of the remain'ng inoperable diesel generator. A successful test of diesel OPERA 8ILITY per Surveillece Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 performed under this ACM0N Statement for a restored to OPERABLE diesel satisfies the diasel generator test requirements of ACTION Statement b.-

SURVEILLANCE R @ REMENTS 4.8.1.1.1 Each of the above required independent circuits between the offsite transmission network and the casite Class IE Distribution System shall be:

Determined OPERA 8LE at least once per 7 days by verify!ng correct a.

breaker alignments, and indicated power availability.

4.8.1.1.2 Each diesel generator shall be demonstrated OPERA 8LE:

a.

In accordance with the frequency specified in Table 4.8-1 on a STAGGERED TEST BASIS by:

1)

Verifying the fuel level in the day tank (L1-9018, LI-9019),

2)

Verifying the fuel level in the fuel storage tank (LI-9024, L1-9025),

3)

Verifying the fuel transfer pump starts and. transfers fuel fron the storage system to the day tank, 4)

Verifying the diesel starts and.that the generator voltage and frequency are 4160 + 170, -135 volts and 60 + 1.2 Hz within-11.4 seconds" after the start signal. The dTesei generator shall be started for this test by using one of the following signals:

'All diesel generator starts for the purpose of surveillance testing as required by Specificatton 4.8.1,1.2 may be preceded by an engine prelvbe period as recommended by the manufacturer so that the mechanical stress and wear on the diesel engine is minimited.

V0GTLE UNITS - 1 & 2 3/4 8-3

n ELECTRICAL POWER SYSTEMS SURVL,tLANCE REQUIREMENTS (Continued) a)

Manual, or b)

Slaulated loss-of-offsite power by itself, or c)

Simulated loss-of-of fsite power in conjunction with an ESF Actuation test signal, or l

d)

An ESF Actuation test signal by itself.

5)

Verifying the, generator is synchronized, loaded to an indicated 6800-7000 kW, and operates at this loaded condition for at least 60 minutes, and 6)

Verifying the diesel generator is aligned to provide standby power to the associated emergency busses.

7)

Verifying the p-essu-e in at least one diesel generator airstart receiver (PI-9060, PI-9061. PI-9064, PI-9065) to be greater than or equal to 210 psig.

j b.

At least once per 31 days and af ter each operation of the diesel where the period of operation was greater than or equal to I hour by checking for and removing accumulated water from the day fuel tank; j

c.

At least once per 31 days by checking for and removing accumulated j

water from the fuel oli storage tanks; i

I d.

By sampling new fuel oil in accordance with ASTM 04057 prior to addition to storage tanks and:

1)

By verifying in accordance with the tests specified in y

3 ASTM-0975-81 prior to addition to the storage tanks that the j

sample has:

l a)

An API Gravity of within 0.3 degrees at 60*F, or a specific gravity of within 0.0016 at 60/60'F, when compared to the supplier's certificate or an absolute specific gravity at 60/60'F of greater than or equal to 0.83 but less than or equal to 0.89, or an API gravity of greater than or equal j

to 27 degrees but less than or equal to 39 degrees:

'This band is meant as guidance to avoid routine overloading of the diesel generator.

Loads in encess of the band or momentary variations due to chang-ing bus loads shall not invalidate the test.

  1. All diesel generator starts for the purpose of surveillance testing as required by Specification 4.8.1.1.2 may be preceded by an engine prelube period as recommended by the manufacturer so that the mechanical stress and wear on the diesel engine is miniaired.

V0GTLE UNITS - 1 & 2 3/4 8-4 i

l i

h ELECTRICAL POWER $YSTEMS SURVEILLANCE REQUIREMENTS (Continued) 1 b)

A kinematic viscosity at.40'C of greater than or equal to 1.9 centistokes, but less than or equal to 4.1 centistokes, if gravity was not determined by comparison with supplier's certifica.fon; c)

A flash point equal to or greater than 125'F; and d)

A clear and bright appearance with proper color when tested in accordance with ASTM-04176-82.

2)

By verifying within 30 days of obtaining the sample that the other properties specified in Table 1 of ASTM-0975-81 are met when tested in accordance with ASTM-0975 81 except that the analysis for sulfur may be performed in accordance with

~

ASTM 01552-79 or ASTM-D2622-82.

At least once every 31 days by obtaining a sample of fuel oil in e.

accordance with ASTM-0227F-78, and verifying that total particulate contamination is less than 10 mg/ liter when checked in accordance with ASTM 02276-78, Method A; f.

At least once per 92 days and from new fuel prior to addition to the storage tank obtain a sample and verify that the neutralizattog number is less than 0.2 and the mercaptan content is less than 0.01%

g.

At least once per 184 days by:

1)

Verifying the diesel starts 8 from ambient conditions and the generator voltage and frequency are 4160 + 170. -135 volts and 6011.2 Hz within 11.4 seconds af ter the start signal.

The diesti generator shall be started for this test by using one of the signals listed in Surveillance Requirement 4.8.1.1.2.a.4.

This test, if it is performed so it concides with the testing required by Surveillance Reevirement 4.8.1.1.2.a.4, may also serve to concurrently meet those requirements as well.

"All engine starts for the purpose of surveillance testing as required by Specification 4.8.1.1.2 may be preceded by an engine prelube period as recommended by the manufacturer to minf alze mechanical stress en the diesel engine.

  1. Mercaptan content shall not be required to be verified within specification for new fuel prior to its addition, for up to 15,000 gallons of fuel added to the tank, if the last tank sample had a merceptan contgst of less than j

0.007%. All subsequent new fuel addition will require mercaptan content veri-fication prior to its addition until the tank contents are verified to be less than 0.007%.

1 VDGTLE UNITS - 1 & 2 3/4 8-5 w -

mh b

i ELECTRICAL POWER SYSTEMS SURVEILLANCE REQUIREMENTS (Continued) 2)

Verifying the generator is synchronized. loaded to an indicated value of 6100 - 7000 kW*** in less than or equal to 60 seconds, and operates with a load of 6800-7000 kWa** for at least 60 minutes This test, if it is performed so it coincides with the testing required by Survell ance Requirement 4.8.1.1.2.a.5, may also serve to concurrently meet those requirements as well.

h.

At least once per 18 months.** during shutdown, by:

1)

Subjecting the diesel to an inspection in accordance with proce-dures prepared in conjunction with its manufacturers' recommenda-

'j tions' for thi. class of standby service; 2)

Verifying the diesel generator capability to reject a load of greater than or equal to 671 kW (motor-driven auxiliary feedwater pump) while maintaining voltage at 4160 + 240. -410 volts and speed of less than 484 rps (less than nominal speed plus 75%

of the difference between nominal speed and the Overspeed Trip Setpoint); and recovering voltage to within 4160 + 170. -410 volts within 3 seconds.

3)

Verifying the diesel generator capability to reject a load of 7000 kW without tripping.

The generator voltage shall not exceed 5000 volts during and following the load rejection:

4) 51mulating a loss-of offsite power by itself, and:

a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses, and b)

Verifying the diesel starts on the auto-start signal, i

energizes the emergency busses with permanently connected l

4 loads within 11.5 seconds," energizes the auto-connected shutdown loads through the load' sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the shutdown loads. Af ter energization, the steady state voltage and frequency of the emergency busses shall be maintained at 4160 +170, -410 volts and 60 + 1.2 Hz during this test.

5) verifying that on an ESF Actuation test signal, without loss-of-of fsite power, the diesel generator starts on the auto-start signal and operates on standby for greater than or equal to 5 minutes. The generator voltage and frequency shall be 4160

+170, -135 volts and 6011.2 Hz within 11.4 seconds af ter the

  • A11 engine starts for the purpose of surveillance testing as required by Specification 4.8.1.1.2 may be preceded by an engine prelube period as recom-mended by the manufacturer to ainfaite mechanical stress and wear en the diesel engine.
    • For any start of a olesel, the diesel must be operated with a load in accor-dance with the manufacturer's recommendations.
      • This band is meant as guidance to avoid routine overloading of the engine.

Loads in excess of this band or momentary variations due to changing bus loads shall not invalidate this test.

V0GTLE UNITS - 1 & 2 3/4 8-6

a. - -.. _ -

SURVEILLANCE REQUIREMENTS auto-start signal; the steady-state generator voltage and frequency shall be maintained within these limits during this test; 6)

Simulatingaloss-of-offsitepowerinconjunctionwithanESF 1

Actuation test signal, aid; a)

Verifying deenergization of the emergency busses and load shedding from the emergency busses; j

b)

Verifying the diesel starts on the auto-start signal, energizes the emergency busses with percanently connected loads within 11.5 seconds," energizes the auto-connected emergency (accident) loads through the load sequencer and operates for greater than or equal to 5 minutes while its generator is loaded with the emergency loads. After energization, the steady-state voltage and frequency of the emergency busses shall be maintained at 4160 +170,

-410 volts and 60,+ 1.2 Hz during this test; and c)

Verifying that all automatic diesel generator trips, except engine overspeed, low lube oil pressure, high jacket water temperatures and generator differential, are automatically bypassed upon loss of voltage on the emergency bus concurrent with a Safety Injection Actuation signal.

7)

Verifying the diesel generator operates for at least 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of this test, the diesel generator shall be loaded to an indicated 7600 to 7700 kW,** and during the remaining 22 hours2.546296e-4 days <br />0.00611 hours <br />3.637566e-5 weeks <br />8.371e-6 months <br /> of this test, the diesel generator shall be loaded to an indicated 6800-7000 kW.**

The i,e wrator voltage and frequency shall be 4160 + 170 - 135 volts and 60 :t 1.2 Hz l

within 11.4 seconds after the start signal; the steady-state i

generatorvoltageandfrequencysgallbe 4160 + 170, -410 volts j

and 601 1.2 Hz during this test.

Within 5 minutes after com-pleting this 24-hour test, perform Specification 4.8.1.1.2h.6)b);,,

l*

8)

Verify..ig that the auto-connected loads to each diesel generator do not exceed the continuous rating of 7000 kW; 9)

Verifying the diesel generator's capability to:

"All engines starts for the purpose of surveillance testing as required by Specification 4.8.1.1.2 may be preceded by an engine prelube period as recommended by the manufacturer to minimize mechanical stress and wear on the diesel engine.

"This band is meant as guidance to avoid routine overloading of the engine.

Loads in excess of this band or momentary variations due to changing bus loads shall not invalidate the test.

  1. Failure to maintain voltage and frequency requirements due to grid disturbances does not render a 24-hour test as a failure.
    1. If Specification 4.2.1.1.2h.6)b) is not satisfactorily completed, it is not necessary to repeat the preceding 24-hour test.

Instead, the diesel generator may be operated at the load required by Surveillance Requirerc m 4.8.1.1.2.a5 kW for 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> or until operating temperature has stabilized.

V0GILC UNITS - 1 & 2 3/4 8-7

c.

^

a-w

.c-I ELECTRICAL POWER SYSTEMS juRVEILLANCEREQUIREMENTS(Continued)

I a)

Synchronize with the offsite power source while the l

generator is loaded with its emerger.:y loads upon a simu-lated restoration of offsite power, b)

Transfer its loads to the offsite power source, and c) 8e restored to its standby status.

10) Verifying that with the diesel generator operating in a test mode, connected to its bus, a simulated Safety injection signal i

overrices the test mode by: (1) returning the diesel generator to standby operation, and (2) automatically energizing the emergency loads with offsite power;

11) Verifying that the fuel transfer pump transfers fuel from each fuel storage tank to the day tank of each diesel via the installed cross-connection lines;
12) Verifying that the automatic load sequence timer is OPERA 8LE with the interval between each load block within + 10% of its design interval;

~

i.

At least once per 10 years or after any modifications which could affeet diesel generator interdependence by starting both diesel generators simultaneously, during shutdown, and verifying that both diesel generators accelerate to at least 440 rpm in less than or equal to 11.4 seconds; and j.

At least once per 30 years by:

1)

Draining each fuel oil storage tank, removing the accumulated sediment and cleaning the tank using a sodium hypochlorite i

solution, or equivalent, and j

2)

Performing a pressure tect of those portions of the diesel fuel oil system designed to Section III, subsection N0 of the ASME Code at a test pressure equal to 110% of the system design pressure.

4.8.1.1.3 Reports - All diesel generator failures, valid or nonvalid, shall f

be reported to the Commission in a Special Report pursuant to Specification 6.8.2 within 30 days.

Reports of diesel generator failures shall include the informa-tion recommended in Regulatory Position C.3.b of Regulatory Guide 1.108, Revi-i sion 1, August 1977.

If the number of failures in the last 100 valid tests on a per nuclear unit basis is greater than or eoval to 7 the report shall be supplemented to include the additional information recommended in Regulatory.

Position C 1 h nf Regulatory Guide 1.108, Revision 1. August 1977.

)f.~ %

V0GTLE UNITS - 1 & 2 3/4 8-8

o TABLE 4.8-1 O!ESEL GENERATOR TEST SCHEDULE Number of Failures Number of failures in in Last 100 Valid Last 20 Valid Tests

  • Tests
  • Test Frequency 11 14 Once per 31 days 3 2**

15 Once per 7 days i

l l

' Criteria for determining number of failures and number of valid tests shall be in accordance with Regulatory Position C.2.e of Regulatory Guide 1.108, but determined on a per diesel generator basis.

For the purposes of determining t.he required test frequency, the previous test failure count may be reduced to zero if a complete diesel overhaul to like-new condition is completed, provided that the overhaul, including appro-1 priate post-maintenance operation and testing, is specifically approved by the manufacturer and if acceptable reliability has been demonstreted. The reliability criterion shall be the successful completion of 14 consecutive

}

tests in a single series. Ten of these tests shall be in accordance with the routine Surveillance Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 and four l

tests in accordance with the 184-day testing requirement of Surveillance Requirement 4.8.1.1.2.f.

If this criterion is not satisfied during the first series of tests, any alternate criterion to be used to transvalue the failure count to zero requires NRC approval.

    • The associated test frequency shall be maintained until seven consecutive f ailure free demands have been performed and the number of f ailures in the last 20 valid demands has been reduced to one.

V0GTLE UNITS - 1 & 2 3/4 8-9