Telecopy AO 74-32:on 740612,RHR LPCI Injection Valve MO-2-10-154B Motor Failed.Caused by Rotor Shaft Slippage. Motor Removed & Inspected
ML20086K513
Person / Time
Site: Peach Bottom 
Issue date: 06/13/1974
From: Ullrich W
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20086K512 List:
References
AO-74-32, NUDOCS 8401270176
Download: ML20086K513 (2)


Text

-- ----

$*S0 nf

. [.

June 13,1974 Mr. James P. O'Reilly, Director United Staten Atomic Energy Cccciosion Directorate of Regulatory Operations 631 Park Avenue King of Prussia, Pennsylvania 19406 Confireing my conversation Uth-P.riEdir,7LE.CZRe

~

Operations Office on June 12, 1974'. ~ ~ - -

Reference:

License Number DPR-44, Amendment Number 1 Technical Specification: 3 5.A Report No.:

50-277-74-32 Report Date:

June 13,1974 Occurrence Date:

June 12, 1974 Facility:

P uch Bottom Atomic Power Station R.D. 1, Delta, Pennsylvan'.a 17314 Identification of Occurrencer The RER IICI infection valve HO-2-10-154B motor failure.

Conditions Prior to Occurrence:

Reactor operating at approximately 70% power.

l Description of Occurrence:

l During curveillance testing the valve failed to open. Investigation l

revealed that the motor had failed electrically.

Dcsignation of Apparent Cause of Occurrence:

i Possible rotor shaft slippage resulting in cechanical damage which then caused electrical failure.

Analysis of Occurrence:

Failure of this valve in the closed position resulted in an inoperable LFCI system. Surveillance testing was in=ediately begun on the diesel i

generators and core spray sub-cyste=a as required by the Technical I

Specifications. Prior to the completion of this testing, the valve was epened canually and left open. Because the valve in norcally in the crea positiert and in open during IJCI injection it was determined that the I.FCI sycte= was then operable. This occurrence, therefore..has minimum safety significance.

Corrective Action:

The valve motor has been reened and inspected. The cause of the damage will be deter =ined and the raotor vill be repaired or replaced. As indicated above, the valve has been manually opened and left in that position, thus rectoring the LPCI system to full operability.

t 8401270176 740622 11 PDR ADOCK 05000277 PDR (e

m-ilures have been reported for this valve; however, No previous motor fa internal other motor failu{ q have been reported not cauced

~*mechanical dassgek/

o Very truly youro.

N ?/ N Y W. T. Ullrich, Superintendent Peach Bottom Atomic Power Station

. y-N,?

_-s_ +. _ _..

_ = _ _

,m_m_m.,__.,

c__..

______2--

O O

e D

.