ML20086K405

From kanterella
Jump to navigation Jump to search
AO 74-38:on 740719,setpoint of Core Spray Sparger to Reactor Vessel Differential Pressure Switch DPIS-2-14-43B Found Less Conservative than Allowed by Tech Specs.Caused by Setpoint Drift.Switch Recalibr & Returned to Svc
ML20086K405
Person / Time
Site: Peach Bottom Constellation icon.png
Issue date: 07/29/1974
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Giambusso A
US ATOMIC ENERGY COMMISSION (AEC)
References
AO-74-38, NUDOCS 8401270073
Download: ML20086K405 (2)


Text

-

7 w.: .x

. O O e PHILADELPHIA ELECTRIC COMPANY . \

2301 MARKET STREET

?g  :\p  %

_7

/

aJ ]

PHILADELPHIA PA.19101 AUG 11974" A k

ll. s t.t (21518414o00 .[ _ [

' > /' s <

_, . ;3 N

. >\ pp July 29, 1974 Mr. A. Giambuss Deputy Director of Reactor Projects 50-277 United States Atomic Energy Cormiission Directorate of Licensing Washington, DC 20545

Dear Mr. Giambusso:

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. Donald Caphton, A.E.C. Region I Regulatory Operations Office on July 19, 1974. Writ- ,

' ten notification was made to Mr. James P. O'Reilly, Region I Regulatory Guc aiivn= Giii< e on .soiy i s, i9fh. in arcordaaca '." t h Sectien 6.7.2.P.

of the Technical Specifications, Appendix A of DPR-44 for Unit 2 Peach Bottom Atomic Power Station, the following report is being ;ubmitted to the Directorate of Licensing as an Abr,armal Occurrence.

Reference:

License Number DPR-44, Amendment Number 1

' Technical Specification Table 3 5.B Report No.: 50-277-74-38 Report Date: July 29, 1974 Occurrence Date:

~

July 19, 19/4 Facility: Peach Bottom Atomic Power Station R.D. 1, Delta, Pennsylvania 17314 Identificatien of Occurrenc.e:

Setpoint of the Core Spray Sparger to Reactor Vessel differ-ential pressure switch, dPIS-2-14-438, found to be less conservative  ;

than allowed by the Technical Specifications.

a ' ,

_ Conditions Prior to Occurrence:  !; rf ./

l a  ;

r i, > \ ,  ;

8 The reactor was at 100% power. .l ,

s  ;'

lL ' t ,g 8401270073'740729' / (.

PDR ADOCK 05700277 > n.

S PDR g L"d b- -

g sNT ntkliWL 8 -

t l

~

r1 Mr. A. Giambuss

.. ' . J, July 29, 1974 '

Page 2.

l t

j Description of Occurrence:

During a routine instrument surveillance test the setpoint of dPIS-2-14-438 was found to have drifted outside the Technical Specification limits of 5 + 1 5 psid. The switch was found to trip at 6.7 psid.

Designation of Apparent Cause of Occurrence:

The cause of this setpoint failure is attributed to slight setpoint drift.

Analysis of Occurrence:

Due to the slight magnitude of the setpoint deviation, this occurrence has minimal safety implications.

Corrective Action:

The switch was immediately recalibrated and returned to service.

Very truly yours, 3

J)V ' uw

/ M . J,. C'o'o ne'y

/

i Ass,' t Gen' 1 Superin'tendent.

4 Generation Division ~

cc: Mr. J. P. O'Reilly Director,. Region 1 linited States Atomic Energy Commission K ng of P us a, PA 19406 i

1

!E u

. 1 i

.i 4