AO 74-38:on 740719,setpoint of Core Spray Sparger to Reactor Vessel Differential Pressure Switch DPIS-2-14-43B Found Less Conservative than Allowed by Tech Specs.Caused by Setpoint Drift.Switch Recalibr & Returned to Svc
ML20086K405
Person / Time
Site: Peach Bottom 
Issue date: 07/29/1974
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
References
AO-74-38, NUDOCS 8401270073
Download: ML20086K405 (2)


Text

-

7 w.:.x O

O e

\\

PHILADELPHIA ELECTRIC COMPANY

\\p

?

/

aJ

]

2301 MARKET STREET

. _7 g

AUG 11974" k PHILADELPHIA PA.19101 ll. s t.t A

(21518414o00

.[ _

[

' > /' s

_,. ;3 N

>\\

pp July 29, 1974 Mr. A. Giambuss 50-277 Deputy Director of Reactor Projects United States Atomic Energy Cormiission Directorate of Licensing Washington, DC 20545

Dear Mr. Giambusso:

Subject:

Abnormal Occurrence The following occurrence was reported to Mr. Donald Caphton, A.E.C. Region I Regulatory Operations Office on July 19, 1974. Writ-

' ten notification was made to Mr. James P. O'Reilly, Region I Regulatory Guc aiivn= Giii< e on.soiy i s, i9fh.

in arcordaaca '." t h Sectien 6.7.2.P.

of the Technical Specifications, Appendix A of DPR-44 for Unit 2 Peach Bottom Atomic Power Station, the following report is being ;ubmitted to the Directorate of Licensing as an Abr,armal Occurrence.

Reference:

License Number DPR-44, Amendment Number 1

' Technical Specification Table 3 5.B Report No.:

50-277-74-38 Report Date:

July 29, 1974 Occurrence Date:

July 19, 19/4

~

Facility:

Peach Bottom Atomic Power Station R.D. 1, Delta, Pennsylvania 17314 Identificatien of Occurrenc.e:

Setpoint of the Core Spray Sparger to Reactor Vessel differ-ential pressure switch, dPIS-2-14-438, found to be less conservative than allowed by the Technical Specifications.

a

./

_ Conditions Prior to Occurrence:

rf l

i, > \\,

r 8

a The reactor was at 100% power.

.l

s lL ' t

,g 8401270073'740729'

/

(.

PDR ADOCK 05700277 g L"d b-n.

S PDR 8

t g sNT ntkliWL l

r1

~

Mr. A. Giambuss

.. '. J, July 29, 1974 Page 2.

l t

j Description of Occurrence:

During a routine instrument surveillance test the setpoint of dPIS-2-14-438 was found to have drifted outside the Technical Specification limits of 5 + 1 5 psid. The switch was found to trip at 6.7 psid.

Designation of Apparent Cause of Occurrence:

The cause of this setpoint failure is attributed to slight setpoint drift.

Analysis of Occurrence:

Due to the slight magnitude of the setpoint deviation, this occurrence has minimal safety implications.

Corrective Action:

The switch was immediately recalibrated and returned to service.

Very truly yours, J)V ' uw

/

/ M.

J,. C'o' ne'y o

3 Ass,' t Gen' 1 Superin'tendent.